8 Fitting protective devices and drive components
Maschinenfabrik Reinhausen GmbH 2015
180
4349315/00 EN
VACUTAP® VR®
6.
Connect main grounding conductor to grounding conductor terminal on
terminal bar X1 (minimum connection cross-section 2.5 mm
2
).
Figure 239: Main grounding conductor
Fitting bevel gear
The stamped serial number of the bevel gear must match the serial number
of the on-load tap-changer.
The horizontal drive shaft must align with the shaft end of the upper gear
unit on the on-load tap-changer head.
264] to support on the transformer cover with 2
bolts (through-holes 18 mm in diameter).
The information provided above applies analogously to special design bevel
gears and angle gears, as well as to intermediate bearings of the vertical or
horizontal drive shaft. Refer to the information about the drive shaft in this
technical file for more information.
Fitting drive shaft
In accordance with IEC standard 60214, all drive shafts located on the out-
side of the transformer need to be protected with safety coverings.