6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
158
5163667/00 EN
TRAFOGUARD® ISM®
Access point
You can use this parameter to assign the access point a name in the IEC
61850 network.
To set the access point name, proceed as follows:
1.
Go to
Settings > Parameters > IEC
61850 > Access point
.
2.
Enter access point.
3.
Press the
Accept
button to save the modified parameter.
Edition
You can use this parameter to switch between edition 1 and edition 2 of the
control system protocol IEC 61850.
To select the edition of the IEC 61850 control system protocol, proceed as
follows:
1.
Go to
Settings > Parameters > IEC
61850 > Edition
.
2.
Select the option you want.
3.
Press the
Accept
button to save the modified parameter.
Downloading ICD file
You can download the ICD file from the device via the Import/Export Manag-
er [
183]. To do this, you have to establish an Ethernet connection be-
tween the device and your PC.
For a smooth download with Windows Vista/7/8 operating systems, use
Windows Explorer.