6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
151
5163667/00 EN
TRAFOGUARD® ISM®
2.
Press the
Log
button.
Figure 117: Event memory
Filtering events
To adjust the display, you can define a filter. To do so, proceed as follows:
1.
Press the
Filter
button.
2.
Set the desired filter and press the
Accept
button.
Exporting events
You can export the event memory entries currently displayed as a csv file. If
you first create a filter, only the filtered entries are exported.
To export the events, proceed as follows:
ü
First connect using Connect PC [
74] or connect a storage medium to
1.
Press the
Export
button.
2.
Select the option you want for data transmission (PC or USB).
ð
The data is exported.
Measured values
You can display the measured values for the device. Note that the displayed
measured values may differ from the raw values displayed in the information
display of assembly UI 1 or UI 3. The measured values are prepared for the
measured value display by device as follows:
▪
The circuit set for the current transformer and voltage transformer is tak-
en into account, as is a corresponding phase displacement.
▪
The assemblies UI 1 or UI 3 use the generator sign convention. The de-
vice displays the measured values using the load sign convention.
6.21