6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
124
5163667/00 EN
TRAFOGUARD® ISM®
To set the DGA monitoring, proceed as follows:
1.
Go to
Settings > Parameters > DGA monitoring
.
2.
Select the parameter you want.
3.
Set parameter.
4.
Press the
Accept
button to save the modified parameter.
Tap position monitoring
You can set 2 limit values for tap position monitoring:
▪
Pos<
▪
Pos>
You can set the following parameters for each limit value. A detailed descrip-
tion of the limit value concept and parameters can be found in the Limit val-
ues [
▪
Lower/upper tap position
▪
Behavior limit value
▪
Delay time (optional)
To set tap position monitoring, proceed as follows:
1.
Go to
Settings > Parameters > Tap position monitoring
.
2.
Select the parameter you want.
3.
Set parameter.
4.
Press the
Accept
button to save the modified parameter.
Hot-spot calculation (optional)
You can set the parameters for the hot-spot calculation in the Hot-spot
menu.
Figure 90: Hot-spot calculation
6.7.8
6.8