6 Functions and settings
Maschinenfabrik Reinhausen 2014
80
2374092/04 EN
TAPCON® 260
CAN bus
V
V
Figure 50: Cross-monitoring
For the check, the measured voltage of the device
is transmitted to the
device
via a second separate measurement input and vice versa. The
calculated measured voltage is compared with the original measured values
via the CAN bus. If the measured values deviate, the
Measured value error
message is issued.
When checking the limit values, one device transmits a measured voltage to
the other via the second separate measurement input. You can set the fol-
lowing limit values for this measured value:
▪
▪
▪
As soon as one of the set limit values is exceeded, once the set delay time
for the error message [
83] has lapsed, the
Measured value error
mes-
sage is output. If wired accordingly, relay contacts can block the raise/lower
pulse to the motor-drive unit. Regulation of individual devices is not affected
by limit value monitoring.
The following sections describe how you set the relevant parameters for the
monitoring device.
Also refer to
2
Setting delay time for error message [
2
Setting desired value for regulator 2 [
2
Setting undervoltage limit value V< for regulator 2 [
2
Setting overvoltage limit value V> for regulator 2 [
Setting desired value for regulator 2
You can use this parameter to set the desired value for the device to be
monitored.
You can use the
key to change the display to the following units:
No measured value or
measurement card error
Checking the limit values
6.8.1