5 Overview of parameters
24
Overview of parameters
This section contains an overview of the relevant menus
and parameters. The availability of individual parameters
varies depending on the device ordered.
Parameter
Setting range
Factory setting
Current setting
NORMset
Normset activation
On, Off
Off
Desired value 1
49...140 V
100 V
Primary voltage
0...9,999 kV
0 kV
Secondary voltage
57...123 V
100 V
Control parameters > Voltage regulation
Desired value 1
49...140 V
100.0 V
Desired value 2
49...140 V
100.0 V
Desired value 3
49...140 V
100.0 %
Desired value selec-
tion
Desired value 1;
Desired value 2;
Desired value 3
Desired value 1
Bandwidth
0.5...9 %
2.00 %
Delay time T1
0...600 s
40 s
Control response T1
T1 linear, T1 inte-
gral
T1 linear
Activation T2
T2 on, T2 off
T2 off
Delay time T2
1...10 s
10.0 s