9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
92
4453918/14 EN
ETOS
®
TD
Reference time
You can use this parameter to set which time is to be transmitted by the con-
trol system. The device uses this information for time synchronization
[
Section 9.5, Page 83]. You can select the following options:
Option
Description
Local
The control system transmits the local time.
Page 84]. Otherwise the device will use
an incorrect time.
UTC
The control system transmits the time as UTC. The de-
vice calculates the local time from UTC and the set time
zone [
Table 24: Reference time
9.7.3 Configuring IEC 60870-5-103 (optional)
If you want to use the IEC 60870-5-103 control system protocol, you must
set the following parameters.
Settings
Parameters
IEC 60870-5-103
Name
Value
Serial interface
RS232
Baud rate
9600
ASDU address
1
Number of databits
8
Parity
Even
Number of stop bits
1
DFC compatibility
Standard
Reference time
UTC
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
31.01.2020 13:05
Figure 66: IEC 60870-5-103
1. Go to
Settings > Parameters > System > IEC 60870-5-103
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Serial interface
You can use this parameter to select the serial interface for data transmis-
sion. You can select the following options:
▪ RS232
▪ RS485
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......