10 Maintenance
Maschinenfabrik Reinhausen GmbH 2021
105
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
10 Maintenance
DANGER
Electric shock!
An energized transformer could cause death or serious injuries.
► Switch off transformer on high and low-voltage side.
► Lock transformer to prevent unintentional restart.
► Ensure that everything is de-energized.
► Visibly connect all transformer terminals to ground (grounding leads,
grounding disconnectors) and short circuit them.
► Cover or cordon off adjacent energized parts.
DANGER
Electric shock!
Working on the on-load tap-changer when components are energized can
lead to death or serious injuries.
► De-energize all auxiliary circuits, such as the tap-change supervisory de-
vice, pressure relief device, pressure monitoring device.
► Ensure that everything is de-energized.
WARNING
Danger of explosion!
Explosive gases in the oil compartment of the on-load tap-changer, trans-
former, pipe system, oil conservator and at the dehydrating breather open-
ing can deflagrate or explode and result in severe injury or death.
► Ensure that there are no ignition sources such as naked flames, hot sur-
faces or sparks (e.g. caused by the build-up of static charge) in the trans-
former's immediate surroundings and that none occur.
► Do not operate any electrical devices (e.g. risk of sparks from impact
wrench).
► Only use conductive and grounded hoses, pipes, and pump equipment
that are approved for flammable liquids.
10.1 Inspection
When inspecting the transformer, at the same time undertake an inspection
of the motor-drive unit and control unit. To do so, proceed as follows:
10.1.1 Visual check
Start with the visual check as follows:
► Check whether any external damage or leaks are visible.
ð
In the event of visible damage, contact Maschinenfabrik Reinhausen
GmbH's Technical Service department.
If a problem occurs with the control unit and you want to contact Maschinen-
fabrik Reinhausen GmbH, first read out the software version.