Installation Instructions and Owner’s Manual

Unvented LP-Gas Vent Free Heaters

OBSERVED SYMPTOM 

POSSIBLE CAUSE

REMEDY 

When ignitor button is pressed in, there is 
no spark at pilot

1. Ignitor electrode positioned wrong.

2. Ignitor electrode is broken.

3. Ignitor electrode not connected to 

ignitor.

4. Ignitor cable pinched or wet.
5. Broken ignitor cable.
6. Bad Piezo ignitor.
7. Low Battery.

1. Reposition electrode

2. Replace electrode

3. Reconnect ignitor cable

4. Free ignitor cable if pinched by any 

metal or tubing. Keep ignitor cable dry.

5. Replace ignitor cable

6. Replace control valve

7. Replace battery

ODS/pilot lights but fl ame goes out when 
control knob is released

1. Gas supply turned off or equipment 

shutoff valve closed.

2. Control knob not  fully pressed in while 

pressing ignition button.

3. Air in gas line when installed.
4. ODS/pilot is clogged.
5. Gas regulator setting is not correct
6. Control knob not in pilot position
7. Thermocouple connection loose at 

control valve

8. Pilot fl ame not touching thermocouple, 

which allows thermocouple to cool, 
causing pilot fl ame to go out. This 
problem could be caused by one or 
both of the following:

a. Low gas pressure
b. Dirty or partially clogged ODS/pilot

1. Turn on gas supply turn off or open 

equipment shutoff valve closed

2. Fully press in control knob while press-

ing ignition button

3. Continue holding down control knob. 

Repeat ignition operation until air is 
removed.

4. Clean ODS/pilot (see Cleaning and 

Maintenance pages 11 and12).

5. Replace gas regulator

6. Turn Control knob to pilot position

When ignitor button is pressed in, there is 
a spark at the ODS/pilot but no ignition

1. Control knob not fully pressed in.
2. Control knob not pressed in long 

enough

3. Equipment shutoff valve not fully open

4. Thermocouple damaged
5. Control valve damaged

1. Press in control knob fully
2. After ODS/pilot lights, keep control 

knob pressed in for 30 seconds

3. Fully open equipment shutoff valve
4. Hand tighten thermocouple nut until 

snug, and then tighten 1/4 turn more.

5. -
a. Contact local gas company
b. Clean ODS/pilot (see Cleaning and 

Maintenance, pages 11 and 12).

6. Replace thermocouple
7. Replace Control valve.

TROUBLESHOOTING

NOTE:

 All troubleshooting items are listed in order of operation and likely occurrence.

WARNING:

 Only a qualifi ed service person should service and repair heater. 

CAUTION:

 Never use a wire needle, or similar object to clean ODS/pilot. This can damage ODS/pilot unit. 

Make sure grille guard is in place before running heater. If screen or grille guard is removed for servicing it must be 
replaced prior to operating the heater. 

WARNING:

 If you smell gas: 

• 

Shut off gas supply 

• 

Do not try to light any appliance 

• 

Do not touch any electrical switch; do not use any phone in your building 

• 

Immediately call you gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. 

• 

If you cannot reach your gas supplier, call the fi re department. 

IMPORTANT:

 Operating heater where impurities in air exist may create odors. Cleaning supplies, paint, paint remov-

er, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These fumes may mix with com-
bustion air and create odors and possible discoloration of walls and ceilings.

 

Содержание MHVFG30TB LP

Страница 1: ...rovisions for adequate combustion and ventilation air must be provided Refer to Fresh Air for Combustion and Ventilation section on page 4 of this manual WARNING Improper installation adjustment alter...

Страница 2: ...to avoid burns or clothing igni tion Heater will remain hot for a time after shutdown Allow heater surfaces to cool before handling Young children should be carefully supervised when they are in the...

Страница 3: ...eds outside ventilation air to run properly The Oxygen Depletion Sensor ODS safety shutoff system shuts down the heater if not enough fresh air is available See Fresh Air for Combustion and Ventilatio...

Страница 4: ...excerpts from National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Com bustion and Ventilation All spaces in homes fall into one of the three following ventilation classifications 1 Unusuall...

Страница 5: ...t Free Heater 20 000 Btu hr Total 60 000 Btu hr 4 Compare the maximum Btu hr the space can support with the actual amount of Btu hr used Example 51 800 Btu hr maximum Btu hr the space can support 60 0...

Страница 6: ...enough fresh air to supply all ap pliance in both spaces Ventilation from Outdoors If necessary provide extra fresh air by using ventila tion grills or ducts Connect these items directly to the outdo...

Страница 7: ...ill be located Make sure mounting bracket is level For wall stud mounting locate one end of the mounting bracket over a wall stud WARNING Maintain minimum clearances shown in figure 7 If you can provi...

Страница 8: ...tom Mounting Screws 1 Locate two bottom mounting holes These holes are near bottom on back panel of heater see figure 10 Figure 10 2 Mark screws locations on wall 3 Remove heater from mounting bracket...

Страница 9: ...n Equipment Shutoff Valve From regulated LP tank 11 W C to 14 W C Pressure Tee Joint 1 8 NPT Plug Tap Cap Pipe Nipple Tee Joint 3 8 NPT Pipe Nipple Sediment Trap Test Gauge Connection Reducer Bushing...

Страница 10: ...DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the ga...

Страница 11: ...ding material pet hair etc Make sure grille guard is in place before running heater If screen or grille guard is removed for servicing it must be replaced prior to operating the heater push in or turn...

Страница 12: ...ODS PILOT AND BURNER Use as vacuum cleaner pressurized air or small soft bristled brush to clean CLEANING BURNER PILOT AIR HOLE INLET We recommend that you clean the unit ever 2 500 hours of operatio...

Страница 13: ...ulator 6 Turn Control knob to pilot position When ignitor button is pressed in there is a spark at the ODS pilot but no ignition 1 Control knob not fully pressed in 2 Control knob not pressed in long...

Страница 14: ...Figure 4 page 7 4 Clean burner orifice see Cleaning and Maintenance on pages 11 and 12 or replace burner orifice White powder residue forming within burner box or on adjacent walls or furni ture 1 Wh...

Страница 15: ...15 Installation Instructions and Owner s Manual Unvented LP Gas Vent Free Heaters MHVFG30LP...

Страница 16: ...any Mr Heater local dealer or direct from the factory FOR INFORMATION REGARDING SERVICE Please call Toll Free 800 251 0001 www mrheater com Our office hours are 8 00 AM 5 00 PM EST Monday through Frid...

Отзывы: