Mr. Heater MHVFBF20LPBT Скачать руководство пользователя страница 5

Installation Instructions and Owner’s Manual

Unvented LP-Gas Vent Free Room Heaters

5

*Adjoining rooms are communication only if there 

are door less passageways or ventilation grills 

between them.

DETERMINING THE TYPE OF HEATER 

LOCATION SPACE:

Use this method to determine if you have a confined or 

unconfined space.

Note:

 the space includes the room in which you 

install heater plus any adjoining rooms with doorless 

passageways or ventilation grills between the rooms.

1. Find the volume of the space by multiplying room 

length x width x height.

Example: Space size 18ft (length) x 18ft. (width) x 8ft.  

 

(height) = 2592

If additional ventilation to adjoining room is supplied 

with grills or openings, add the volume of these rooms 

to the total volume of the space.
2. Divide the space volume by 50 cubic feet to deter

-

mine the maximum Btu/hr the space can support.

Example: 2592 cu.ft. (volume of space) / 50 cu.ft. =  

 

51.8 or 51,800 (maximum Btu/hr the space  

 

can support)

WARNING:

 If the area in which the heater may be 

operated is smaller than defined as an unconfined 

space or if the building is of unusually tight 

construction, provide adequate combustion and 

ventilation air by the methods described in the 

National Fuel Gas Code, NFPA 54/ ANSI Z223.1, 

Section 5.3 or applicable local codes. 

3. Add the Btu/hr of all the fuel-burning appliances 

in the space such as, Vent–free heater, Gas water 

heater, Gas furnace, Vented gas heater, Gas fire

-

place logs, and Other gas appliances*

*Do not include direct-vent gas appliances. Direct-

vent draws combustion air from the outdoors and 

vents to the outdoors.
Example:  Gas water heater 

40,000 Btu/hr

 

 

Vent Free  

20,000 Btu/hr

 

 

Total   

 

=60,000 Btu/hr

4. Compare the maximum Btu/hr the space can support 

with the actual amount of Btu/hr used.

Example:   51,800 Btu/hr (maximum Btu/hr the  

 

 

space can support)

 

 

60,000 Btu/hr (Actual amount of Btu/hr  

 

 

used)

The space in the above example is a confined 

space because the actual Btu/hr used is more than 

the maximum Btu/hr the space can support.

You must provide additional fresh air. Your options 

are as follows:

A. Rework worksheet, and the space of an adjoining 

room. If the extra space provides an unconfined 

space, remove door to adjoining room or add 

ventilation grills between the rooms. See Ventilation 

Air From Inside Building (Figure 2).

B. Vent room directly to the outdoors. See Ventilation 

Air From Outdoors (Figure 3). 

C. Install a lower Btu/hr heater if lower Btu/hr size 

makes room unconfined. 

If actual Btu/hr used is less than the maximum Btu/

hr the space can support, the space is an uncon

-

fined space. You will need no additional fresh air 

ventilation.

VENTILATION AIR
Ventilation from Inside Building

This fresh air would come from an adjoining unconfined 

space. When ventilation to an adjoining unconfined 

space, you must provide two permanent openings: 

one within 12” of the ceiling and one within 12” of 

the floor on the wall connecting the two spaces (see 

options 1 & 2 of fig. 2). You can also remove door into 

adjoining room (see option3, fig 2). Follow the National 

Fuel Gas Code NFPA 54/ ANSI Z223.1, Section 5.3, 

Air for Combustion and Ventilation for required size of 

ventilation grills or ducts.

Figure 2.

Figure 3.

Ventilation 

Gills into 

Adjoining 

Room - 

Option 1

Ventilation Gills into 

Adjoining Room - Option 2

12”

12”

Or remove 

door into 

Adjoining 

Room - 

Option 3

INLET 

AIR

OUTLET 

AIR

VENTILATION CRAWL SPACE

TO CRAWL 

SPACE

TO ATTIC

VENTILATION AIR

VENTILATED 

ATTIC

OUTLET AIR

Содержание MHVFBF20LPBT

Страница 1: ...oper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual for correct installation and operational procedures For assistance or additional information consult a qualified installer service agency or gas supplier 2018 CB UNVENTED LP GAS FIRED ROOM HEATER OPERATING INSTRUCTIONS AND OWNER S MANUAL READ INSTRUCTIONS CAREFULLY Read and follo...

Страница 2: ...be SOCIAL MEDIA WARNINGS IMPORTANT Read this owner s manual carefully and completely before trying to assemble operate or service this heater Improper use of this heater can cause serious injury or death from burns fire explosion electrical shock and carbon monoxide poisoning WARNING This appliance is equipped for propane gas Field conversion is not permitted WARNING Do not use any accessory not a...

Страница 3: ...hr 2 931W shall not be installed in a bedroom or bathroom 3 Keep all air openings in heater clear free of debris or any blockage This will insure that enough air for proper combustion enters the heater 4 If heater shuts off do not relight until you provide fresh outside air If heater keeps shutting off it requires servicing 5 Turn off and unplug heater and let cool before servicing Only a qualifie...

Страница 4: ... The following are excerpts from National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Combustion and Ventilation All spaces in homes fall into one of the three following ventilation classifications 1 Unusually Tight Construction 2 Unconfined Space 3 Confined Space This heater must not be installed in a confined space or unusually tight construction unless provisions are provided for adeq...

Страница 5: ...r Vent Free Heater 20 000 Btu hr Total 60 000 Btu hr 4 Compare the maximum Btu hr the space can support with the actual amount of Btu hr used Example 51 800 Btu hr maximum Btu hr the space can support 60 000 Btu hr Actual amount of Btu hr used The space in the above example is a confined space because the actual Btu hr used is more than the maximum Btu hr the space can support You must provide add...

Страница 6: ...earances from the floor ceiling and joining walls WARNING Rework worksheet adding the space of the adjoining unconfined space The combined space must have enough fresh air to supply all ap pliance in both spaces Ventilation from Outdoors If necessary provide extra fresh air by using ventilation grills or ducts Connect these items directly to the outdoors or spaces open to the outdoors These includ...

Страница 7: ...g bracket is level For wall stud mounting locate one end of the mounting bracket over a wall stud WARNING Maintain minimum clearances shown in figure 7 If you can provide greater clearances from the floor and joining wall 2 Mark screw locations on wall see figure 7 3 Remove tape and mount bracket from wall Figure 7 Attaching to Wall Stud For attaching mounting bracket to wall studs 1 Drill holes a...

Страница 8: ...ottom mounting holes and wall anchor or drilled hole 7 Hold spacer in place with one hand With the other hand insert mounting screw through bottom mounting hole and spacer Place tip of screw in opening of wall anchor or drilled hole 8 Tighten both screws until heater is firmly secured to wall Do not over tighten Note Do not re place front panel at this time Replace front panel after making gas con...

Страница 9: ... heater If sediment trap is not installed or is installed improperly heater may not run correctly IMPORTANT Hold pressure regulator with wrench when connecting it to gas piping and or fittings CHECKING GAS CONNECTIONS WARNING Test all gas piping and connections for leaks after installing or servicing Correct all leaks at once WARNING Never use an open flame to check for a gas leak Apply a mixture ...

Страница 10: ...call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If knob will not push in or turn by hand don t try to repair it call a quali fied service technician or gas supplier Force or attempted repair may result in a fire or explosion Pressure Testing Heater Gas Connections 1 The appliance and its appliance main gas valve must be disconnected from the ga...

Страница 11: ... for repairs If control knob does not pop up when released contact a qualified service person or gas supplier for repairs 8 When the pilot is lit turn control knob counterclockwise to heating level The main burner should light 9 To select the desired heat level turn the temperature setting knob counterclockwise to between 1 5 THERMOSTAT CONTROL OPERATION FOR IR20LPT IR30LPT The thermostatic contro...

Страница 12: ...ilot assembly clean and free of dust and dirt To clean these parts we recommend using compressed air no greater than 30 psig This can be done by using a vacuum cleaner in the blow position or using compressed air in a can If using canned air please follow the directions on the can If you don t follow directions on the can you could damage the burner or pilot assembly In addition the directions bel...

Страница 13: ...regulator 6 Turn Control knob to pilot position When ignitor button is pressed in there is a spark at the ODS pilot but no ignition 1 Control knob not fully pressed in 2 Control knob not pressed in long enough 3 Equipment shutoff valve not fully open 4 Thermocouple damaged 5 Control valve damaged 1 Press in control knob fully 2 After ODS pilot lights keep control knob pressed in for 30 seconds 3 F...

Страница 14: ...ee Figure 4 page 7 4 Clean burner orifice see Cleaning and Maintenance on pages 11 and 12 or replace burner orifice White powder residue forming within burner box or on adjacent walls or furni ture 1 When heated vapors from furniture polish wax carpet cleaners etc turn into white powder residue 1 Turn heater off when using furniture polish wax carpet cleaner or similar products Heater produces unw...

Страница 15: ...Installation Instructions and Owner s Manual Unvented LP Gas Vent Free Room Heaters 15 This page intentionally left blank ...

Страница 16: ...ocouple LP 1 22 F299201 Fan Assembly 1 9 80009 05 Orifice 1 23 80049 Fan Switch 1 10 80073 Orifice Adapter 1 24 80011 Igniter Module Mounting Bracket 1 11 80055 Regulator Mounting Bracket 1 25 80019 Igniter Module 1 12 80020 Regulator Connection 1 26 80014 Ignitor Wire 1 13 80106 Regulator 1 27 N A Burner Left Bracket 1 14 N A Burner Right Bracket 1 28 80013 High Limit Switch FAN 1 70342 Hardware ...

Страница 17: ...22 F299201 Fan Assembly 1 9 80009 03 Orifice 1 23 80049 Fan Switch 1 10 80073 Orifice Adapter 1 24 80011 Igniter Module Mounting Bracket 1 11 80055 Regulator Mounting Bracket 1 25 80019 Igniter Module 1 12 80020 Regulator Connection 1 26 80014 Igniter Wire 1 13 80082 Regulator 1 27 N A Burner Left Bracket 1 14 N A Burner Right Bracket 1 28 80013 High Limit Switch FAN 1 70342 Hardware Kit not shown...

Страница 18: ...80106 Regulator 1 19 F299201 Fan Assembly 1 8 80020 Regulator Connection 1 20 80011 Igniter Module Mounting Bracket 1 9 80055 Regulator Mounting Bracket 1 21 80019 Igniter Module 1 10 80009 04 Orifice 1 22 80014 Igniter Wire 1 11 N A Bracket Plenum Assembly 1 23 80013 High Limit Switch Fan 1 12 80081 Thermostat Valve 1 24 80049 Fan Switch 1 70342 Hardware Kit not shown 1 Blower not included on all...

Страница 19: ...2 Regulator 1 19 F299201 Fan Assembly 1 8 80020 Regulator Connection 1 20 80011 Igniter Module Mounting Bracket 1 9 80055 Regulator Mounting Bracket 1 21 80019 Igniter Module 1 10 80009 03 Orifice 1 22 80014 Igniter Wire 1 11 N A Bracket Plenum Assembly 1 23 80013 High Limit Switch Fan 1 12 80081 Thermostat Valve 1 24 80049 Fan Switch 1 70342 Hardware Kit not shown 1 Blower not included on all uni...

Страница 20: ... be purchased at any Mr Heater local dealer or direct from the factory FOR INFORMATION REGARDING SERVICE Please call Toll Free 800 251 0001 www mrheater com Our office hours are 8 00 AM 5 00 PM EST Monday through Friday Please include the model number date of purchase and description of problem in all communication LIMITED WARRANTY Mr Heater Inc warrants its heaters and accessories to be free from...

Отзывы: