Installation Instructions and Owner’s Manual

Unvented Natural Gas Fired Room Heater

c.  Caulking or sealants are applied to areas such as joints 

around windows and door frames, between wall-

ceiling joints, between wall panels, at penetrations 
for plumbing, electrical, and gas lines, and at other 
openings. 

If you home does not meet all of the three criteria above, 
see Determining the Type of Heater Location Space, below.

Confined Space and Unconfined Space

The National Fuel Gas Code, NFPA 54/ ANSI Z223.1

 

defines a confined space as a space whose volume is less 

than 50 cubic feet per 1,000 Btu per hour (4.8 m

3

 per kW) 

of the aggregate input rating of all appliances installed in 
that space, and an unconfined space as a space whose 
volume is not less than 50 cubic feet per 1,000 Btu per 

hour (4.8 m

3

 per kW) of the aggregate input rating of all 

appliances installed in that space. Rooms communicating 
directly with the space in which the appliances are 
installed*, through openings not furnished with doors, are 
considered a part of the unconfined space.

*Adjoining rooms are communication only if there are 
doorless passageways or ventilation grills between 
them.

DETERMINING THE TYPE OF HEATER LOCATION 
SPACE:

Use this method to determine if you have a confined or 
unconfined space.

Note:

 the space includes the room in which you 

install heater plus any adjoining rooms with doorless 
passageways or ventilation grills between the rooms.

1.  Find the volume of the space by multiplying room length 

x width x height.

Example: Space size 18ft (length) x 18ft. (width) x 8ft.  
 

(height) = 2592

If additional ventilation to adjoining room is supplied with 
grills or openings, add the volume of these rooms to the 
total volume of the space.

2.  Divide the space volume by 50 cubic feet to determine 

the maximum Btu/hr the space can support.

Example:   2592 cu.ft. (volume of space) / 50 cu.ft. =  
 

51.8 or 51,800 (maximum Btu/hr the space  

 

can support)

 WARNING:

 This heater shall not be installed in a 

room or space unless the required volume of indoor 
combustion air is provided by the method described 

in the National Fuel Gas Code, ANSI Z223.1/NFPA 

54, the International Fuel Gas Code, or applicable 
local codes

SAFETY DEVICE

This heater has a pilot with an Oxygen Depletion Sensor 

(ODS) safety shut off system. The ODS/pilot shuts off the 

heater if there is not enough fresh air.

IGNITION SYSTEM

PIEZO: 

The heater is equipped with a piezo manual ignitor. 

This system requires no matches, batteries, or other source 
to light heater.

LOCAL CODES

Install and use heater with care. 
Installation must conform to local codes or in the absences 
of local codes, use the latest edition of National Fuel Gas 

Code, ANSI Z223.1/NFPA 54.

UNPACKING

1.  Remove heater from carton.

2.  Remove all protective packaging applied to heater 

for shipment.

3.  Check heater for any shipping damage. If heater 

is damaged, promptly inform dealer where you 
bought heater.

FRESH AIR FOR COMBUSTION AND VENTILATION

WARNING: 

This heater shall not be installed in a confined 

space or unusually tight construction unless provisions are 
provided for adequate combustion and ventilation air. Read 
the following instructions to insure proper fresh air for this 

and other fuel-burning appliances in your home. 

ESTABLISHING ADEQUATE VENTILATION

The following are excerpts from National Fuel Gas Code, 

NFPA 54/ ANSI Z223.1, Section 5.3, Air for Combustion 

and Ventilation. All spaces in homes fall into one of the 
three following ventilation classifications:

1.  Unusually Tight Construction

2.  Unconfined Space

3.  Confined Space

This heater must not be installed in a confined space 
or unusually tight construction unless provisions are 
provided for adequate combustion and ventilation air. The 
information on pages 4 and 5 will help you classify your 
space and provide adequate ventilation.

Unusually Tight Construction 

If your home meets all of the three following criteria you 
must provide additional fresh air. See Ventilation from 
Outdoors, page 5.
Unusually tight construction is defined as construction 
where:
a.  Walls and ceilings exposed to the outside atmosphere 

have a continuous water vapor retarder with a rating 
of one perm (6 x 10

-11

 kg per pa-sec-m

2

) or less with 

openings gasketed or sealed and

b.  Weather stripping has been added on operable windows 

and doors, and 

Содержание F299811

Страница 1: ...Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electr...

Страница 2: ...d of high surface temperature and should stay away to avoid burns or clothing ignition Young children should be carefully supervised when they are in the same room with heater A barrier designed to re...

Страница 3: ...ou provide fresh outside air If heater keeps shutting off it requires servicing 5 Turn off and let cool before servicing Only a qualified service person should service and repair heater 6 Do not run h...

Страница 4: ...y the method described in the National Fuel Gas Code ANSI Z223 1 NFPA 54 the International Fuel Gas Code or applicable local codes SAFETY DEVICE This heater has a pilot with an Oxygen Depletion Sensor...

Страница 5: ...Follow the National Fuel Gas Code NFPA 54 ANSI Z223 1 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts WARNING Rework worksheet adding the space of the a...

Страница 6: ...e 4 For convenience and efficiency install the heater Where there is easy access for operation inspection and service In the coldest part of the room CAUTION If you install the heater in a home garage...

Страница 7: ...ocations using 9 64 drill bit 2 Place mounting bracket onto wall Line up holes on each end of bracket with hole drilled in wall 3 Insert mounting screws through bracket and into wall studs 4 Tighten s...

Страница 8: ...res a 3 8 NPT National Pipe Thread inlet connection to the pressure regulator Use of floor mounting feet will require you to use a 3 8 NPT street elbow to make gas connection CAUTION Never connect hea...

Страница 9: ...gas meter 4 Check all connections and joints in gas supply piping system Apply mixture of liquid soap and water to gas joints Bubbles forming show a leak 5 Correct all leaks at once 6 Depressurize an...

Страница 10: ...go to the next step 5 Push in gas control know slightly and turn counterclockwise to PILOT IGN and depress for five 5 seconds Note The first time that the heater is operated after connecting the gas s...

Страница 11: ...rvicing it must be replaced prior to operating the heater WARNING Failure to keep the primary air opening s of the burner s clean may result in sooting and property damage CLEANING ODS PILOT AND BURNE...

Страница 12: ...hutoff valve not fully open Fully open equipment shutoff valve Thermocouple connection loose at control valve Hand tighten thermocouple nut until snug and then tighten 1 4 turn more Pilot flame not to...

Страница 13: ...sing odor causing products while heater is running Gas leak See WARNING statement at top of page 12 Locate and correct all leaks see Checking Gas Connections page 9 Heater shuts off in use ODS operate...

Страница 14: ...r 1 ITEM P N PART DESCRIPTION QTY 10 80055 Regulator Mounting Bracket 1 1 1 80058 Floor Mounting Feet Beige 1 80214 Floor Mounting Feet White 1 12 NA Regulator Connection 1 13 80052 Back Panel Beige 1...

Страница 15: ...g Bracket 1 8 80058 Floor Mounting Feet Beige 1 80214 Floor Mounting Feet White 1 ITEM P N PART DESCRIPTION QTY 9 NA Regulator Connection 1 10 80036 Wall Mounting Bracket 1 1 1 80052 Back Panel Beige...

Страница 16: ...Y A QUALIFIED SERVICE AGENCY REPLACEMENT PARTS ORDERING INFORMATION PURCHASING Accessories may be purchased at any Mr Heater local dealer or direct from the factory FOR INFORMATION REGARDING SERVICE P...

Отзывы: