MQ Power WhisperWatt 180 Скачать руководство пользователя страница 2

DCA180SSI

WhisperWatt

TM

 Generator

Generator Specifications

Design

Revolving field, Self-ventilated,

Drip-proof, Single bearing

No. of Poles

4-pole

Excitation

Brushless with AVR

Standby Output

158 KW (198 KVA)

Prime Output

144 KW (180 KVA)

Generator RPM

1800

Voltage - 3 phase

208, 220, 240, 415, 440, 480V Reconnectable

Voltage - single phase

120, 127, 139, 240, 254, 277V Adjustable

Armature Connection

Star with neutral

Voltage Regulation

(No load to full load)

±0.5%

Power Factor

0.8

Frequency

60 Hz

Frequency Regulation:

No Load to Full Load

Isochronous under varying loads from

no load to 100% rated load

Frequency Regulation:

Steady State

±0.25% of mean value for constant loads

from no load to full load

Insulation

Class F

Sound Level dB(A)
Full load at 23 feet

71

Engine  Specifications

Make/Model

Isuzu / 6HK1X

Emissions

EPA Tier 3 Certified

Starting System

Electric

Design

4-cycle, Watercooled, Direct injection,

Turbocharged, Charge air cooled

Displacement

7790 cc

No. cylinders

6

Bore x Stroke (mm)

115 x 125

Gross Engine Power Output

265 hp (197 kW)

BMEP

241 psi (1656 kPa)

Piston Speed

1480 ft/min (7.5 m/s)

Compression Ratio

17.5 : 1

Engine Speed

1800 rpm

Overspeed Limit

2070 rpm

Oil capacity gallons (liters)

10.6 (40.0)

Battery

12V 100 Ah x 2 (24V systems)

Fuel  System

Recommended Fuel

ASTM-D975-No.1 or No. 2-D

Maximum Fuel Flow (per hour)

31.7 gal. (120 L)

Maximum Inlet Restriction (Hg)

5.7 in. (150 mm)

Fuel Tank Capacity

100 gal. (380 L)

Fuel Consumption

gph

lph

full load

10.6

40.0

75% load

8.0

30.1

50% load

6.1

23.1

25% load

3.7

14.0

Cooling System

Fan Load

8.0 hp (6.0 kW)

Coolant Capacity (with radiator)

7.2 gal. (27.2 L)

Coolant Flow Rate (per minute)

43.0 gal. (160 L)

Heat Rejection to Coolant (per minute)

5699 Btu (6.0 MJ)

Maximum Coolant Friction Head

8.5 psi (59 kPa)

Maximum Coolant Static Head

29.5 ft. (9.0 m)

Ambient Temperature Rating

104°F (40°C)

Air

Combustion Air

435 cfm (12.3 m

3

/min)

Maximum Air Cleaner Restriction

13.6 in H

2

O (3.4 kPa)

Alternator Cooling Air

1459 cfm (41.3 m

3

/min)

Radiator Cooling Air

9182 cfm (260 m

3

/min)

Exhaust System

Gas Flow (full load)

1112 cfm (31.5 m3/min)

Gas Temperature

1022°F (550°C)

Maximum Back Pressure

53.2 in. H

2

O (13.3 kPa)

Amperage

Rated Voltage

Maximum Amps

1Ø 120 Volt

400 Amps (4 wire)

1Ø 240 Volt

200 Amps (4 wire)

3Ø 240 Volt

433 Amps

3Ø 480 Volt

216 Amps

Main Line Circuit Breaker Rating

500 Amps

Over Current Relay Trip Set Point

216 Amps

Generator is not intended for use in enclosed areas or where free flow of air is restricted.

Backfeed to a utility system can cause electrocution and/or property damage.  Do not
connect to any building’s electrical system except through an approved device.

                         

Specifications are subject to change without notice.

DCA180SSI  Rev 0

Warranty*

Isuzu Engine

12 months from date of purchase with unlimited hours or 24 months
from date of purchase with 2000 hours (whichever comes first).

Generator

24 months from date of purchase or 2000 hours (whichever occurs
first).

Trailer

12 months excluding normal wear items.

*Refer to the express written, one-year limited warranty sheet for additional
information.

Содержание WhisperWatt 180

Страница 1: ...nstrumentation includes DC ammeter oil pressure gauge water temp gauge fuel level gauge tachometer hour meter manual engine speed control and emergency shutdown monitors Complete generator analog instrumentation includes voltage regulator control ammeter phase selector switch voltmeter phase selector switch AC voltmeter AC ammeter frequency meter panel light and circuit breaker Automatic safety sh...

Страница 2: ...nsumption gph lph full load 10 6 40 0 75 load 8 0 30 1 50 load 6 1 23 1 25 load 3 7 14 0 Cooling System Fan Load 8 0 hp 6 0 kW Coolant Capacity with radiator 7 2 gal 27 2 L Coolant Flow Rate per minute 43 0 gal 160 L Heat Rejection to Coolant per minute 5699 Btu 6 0 MJ Maximum Coolant Friction Head 8 5 psi 59 kPa Maximum Coolant Static Head 29 5 ft 9 0 m Ambient Temperature Rating 104 F 40 C Air C...

Страница 3: ...lable Optional Fuel Cell Features Trailer fuel tank a second fuel cell located in the trailer allows for extended run time Sub base fuel cells double wall Additional fuel cell for extended runtime operation Contains a leak sensor low fuel level switch and a secondary containment tank UL142 listed 12 hours of minimum run time 24 hours of minimum run time Optional Control Features Audible alarm aler...

Страница 4: ... 10 08 DCA180SSI 180SSIU Manufactured by Denyo Co MQ POWER POST OFFICE BOX 6254 CARSON CA 90749 310 537 3700 800 883 2551 FAX 310 604 3831 E MAIL mqpower multiquip com WEBSITE www mqpower com Weight Dry Weight 6373 lbs 2890 kg Wet Weight 7211 lbs 3270 kg Max Lifting Point Capacity 14050 lbs 6373 kg ...