TROUBLE SHOOTING 

Problem 

LCD/LED/Buzzer 

Explanation / Possible cause 

What to do 

Unit shuts down 
automatically 
during startup 

process. 

LCD/LEDs and buzzer 
will be active for 3 
seconds and then 

complete off. 

The battery voltage is too low 
(<1.91V/Cell)

 

1. Re-charge battery. 
2. Replace battery. 

No response after 

power on. 

No indication. 

1. The battery voltage is far too 
low. (<1.4V/Cell) 

2. Battery polarity is connected 
reversed. 

1. Check if batteries and the 
wiring are connected well. 

2. Re-charge battery. 
3. Replace battery. 

Mains exist but the 
unit works in 
battery mode. 

Input voltage is 

displayed as 0 on the 
LCD and green LED is 

flashing. 

Input protector is tripped 

Check if AC breaker is tripped 

and AC wiring is connected 
well. 

Green LED is flashing. 

Insufficient quality of AC power. 
(Shore or Generator) 

1. Check if AC wires are too 
thin and/or too long. 

2. Check if generator (if 
applied) is working well or if 
input voltage range setting is 

correct. (UPS

Appliance) 

Green LED is flashing.  Set “Solar First” as the priority of 

output source. 

Change output source priority 
to Utility first. 

When the unit is 
turned on, internal 
relay is switched on 

and off repeatedly. 

LCD display and LEDs 
are flashing 

Battery is disconnected. 

Check if battery wires are 
connected well.   

Buzzer beeps 
continuously and 

red LED is on. 

Fault code 07 

Overload error. The inverter is 
overload 110% and time is up. 

Reduce the connected load by 
switching off some 

equipment. 

Fault code 05 

Output short circuited. 

Check if wiring is connected 

well and remove abnormal 
load.   

Temperature of internal converter 

component is over 120°C. (Only 
available for 1-3KVA models.) 

Check whether the air flow of 
the unit is blocked or whether 

the ambient temperature is 
too high. 

Fault code 02 

Internal temperature of inverter 

component is over 100°C. 

Fault code 03 

Battery is over-charged.   

Return to repair center. 

The battery voltage is too high. 

Check if spec and quantity of 

batteries are meet 
requirements. 

Fault code 01 

Fan fault 

Replace the fan. 

Fault code 06/58 

Output abnormal (Inverter voltage 
below than 190Vac or is higher 
than 260Vac) 

1. Reduce the connected 
load. 
2. Return to repair center 

Fault code 
08/09/53/57 

Internal components failed. 

Return to repair center. 

Fault code 51 

Over current or surge. 

Restart the unit, if the error 

happens again, please return 
to repair center. 

Fault code 52 

Bus voltage is too low. 

Fault code 55 

Output voltage is unbalanced. 

Fault code 56 

Battery is not connected well or 
fuse is burnt. 

If the battery is connected 
well, please return to repair 

center. 

Содержание 1KVA-5KVA

Страница 1: ...1KVA 5KVA INVERTER CHARGER Version 1 7 User Manual...

Страница 2: ...n 8 Final Assembly 9 Communication Connection 10 Dry Contact Signal 10 OPERATION 11 Power ON OFF 11 Operation and Display Panel 11 LCD Display Icons 12 LCD Setting 14 Display Setting 21 Operating Mode...

Страница 3: ...nnel can install this device with battery 6 NEVER charge a frozen battery 7 For optimum operation of this inverter charger please follow required spec to select appropriate cable size It s very import...

Страница 4: ...lications via LCD setting Configurable AC Solar Charger priority via LCD setting Compatible to mains voltage or generator power Auto restart while AC is recovering Overload Over temperature short circ...

Страница 5: ...ator 3 Charging indicator 4 Fault indicator 5 Function buttons 6 Power on off switch 7 AC input 8 AC output 9 PV input 10 Battery input 11 Circuit breaker 12 RS232 communication port 13 Parallel commu...

Страница 6: ...ng points before selecting where to install Do not mount the inverter on flammable construction materials Mount on a solid surface Install this inverter at eye level in order to allow the LCD display...

Страница 7: ...a qualified personnel WARNING It s very important for system safety and efficient operation to use appropriate cable for battery connection To reduce risk of injury please use the proper recommended c...

Страница 8: ...f 2 3 Nm Make sure polarity at both the battery and the inverter charge is correctly connected and ring terminals are tightly screwed to the battery terminals WARNING Shock Hazard Installation must be...

Страница 9: ...ted cable requirement for AC wires Model Gauge Torque Value 1KVA 16 AWG 0 5 0 6 Nm 2KVA 230VAC 14 AWG 0 8 1 0 Nm 2KVA 120VAC 3KVA 12 AWG 1 2 1 6 Nm 4KVA 10 AWG 1 4 1 6Nm 5KVA 8 AWG 1 4 1 6Nm Please fo...

Страница 10: ...us 4KVA 5KVA 60A 8 AWG 1 4 1 6 Nm CAUTION Important Be sure to connect AC wires with correct polarity If L and N wires are connected reversely it may cause utility short circuited when these inverters...

Страница 11: ...MPPT Voltage Range 30 66Vdc 60 88Vdc 30 115Vdc 60 115Vdc Min battery voltage for PV charge 17Vdc 34Vdc 17Vdc 34Vdc Please follow below steps to implement PV module connection 1 Remove insulation sleev...

Страница 12: ...device when battery voltage reaches warning level Unit Status Condition Dry contact port NC C NO C Power Off Unit is off and no output is powered Close Open Power On Output is powered from Utility Clo...

Страница 13: ...ng status and input output power information LED Indicator LED Indicator Messages Green Solid On Output is powered by utility in Line mode Flashing Output is powered by battery or PV in battery mode G...

Страница 14: ...ad percent load in VA load in Watt and discharging current Battery Information Indicates battery level by 0 24 25 49 50 74 and 75 100 in battery mode and charging status in line mode In AC mode it wil...

Страница 15: ...1 867V cell 1 95V cell 1 95 2 033V cell 2 033 Load Information Indicates overload Indicates the load level by 0 24 25 50 50 74 and 75 100 0 25 25 50 50 75 75 100 Mode Operation Information Indicates u...

Страница 16: ...level warning voltage or the setting point in program 12 Utility first default Utility will provide power to the loads as first priority Solar and battery energy will provide power to the loads only w...

Страница 17: ...oltage range will be within 90 280VAC UPS If selected acceptable AC input voltage range will be within 170 280VAC 04 Power saving mode enable disable Saving mode disable default If disabled no matter...

Страница 18: ...put voltage only available for 120Vac models 110V 120V default 09 Output frequency 50Hz default 60Hz 11 Maximum utility charging current Available options in 1KVA 24V and 2KVA 24V Plus 120Vac model 10...

Страница 19: ...options in 24V models 22 0V 22 5V 23 0V default 23 5V 24 0V 24 5V 25 0V 25 5V Available options in 48V models 44V 45V 46V default 47V 48V 49V 50V 51V 13 Setting voltage point back to battery mode whe...

Страница 20: ...4V default 55V 56V 57V 58V 16 Charger source priority To configure charger source priority If this inverter charger is working in Line Standby or Fault mode charger source can be programmed as below S...

Страница 21: ...off 19 Auto return to default display screen Return to default display screen default If selected no matter how users switch display screen it will automatically return to default display screen Inpu...

Страница 22: ...p Setting range is from 20 0V to 24 0V for 24V model 40 0V to 48 0V for 48V model Increment of each click is 0 1V Low DC cut off voltage will be fixed to setting value no matter what percentage of loa...

Страница 23: ...er battery voltage output voltage output frequency load percentage load in VA load in Watt DC discharging current main CPU Version and second CPU Version Selectable information LCD display Input volta...

Страница 24: ...arging current 1A Output frequency Output frequency 50Hz Load percentage Load percent 70 Load in VA When connected load is lower than 1kVA load in VA will present xxxVA like below chart When load is l...

Страница 25: ...kW load in W will present xxxW like below chart When load is larger than 1kW 1KW load in W will present x xkW like below chart Main CPU version checking Main CPU version 00014 04 Secondary CPU version...

Страница 26: ...e Errors are caused by inside circuit error or external reasons such as over temperature output short circuited and so on PV energy and utility can charge batteries Charging by utility Only available...

Страница 27: ...ted or over temperature is detected by internal converter components 06 Output voltage is abnormal For 1K 2K 3K model Output voltage is too high For 4K 5K model 07 Overload time out 08 Bus voltage is...

Страница 28: ...times every second 03 Battery is over charged Beep once every second 04 Low battery Beep once every second 07 Overload Beep once every 0 5 second 10 Output power derating Beep twice every 3 seconds 12...

Страница 29: ...5Vac 7V or 270Vac 7V Max AC Input Voltage 150Vac or 300Vac Nominal Input Frequency 50Hz 60Hz Auto detection Low Loss Frequency 40 1Hz Low Loss Return Frequency 42 1Hz High Loss Frequency 65 1Hz High L...

Страница 30: ...150 load 10s 110 150 load Surge Capacity 2 rated power for 5 seconds Nominal DC Input Voltage 24Vdc 48Vdc Cold Start Voltage 23 0Vdc 46 0Vdc Low DC Warning Voltage load 20 22 0Vdc 44 0Vdc 20 load 50 2...

Страница 31: ...Voltage per cell Charging Current 100 50 Bulk Constant Current Absorption Constant Voltage Maintenance Floating Current Voltage T1 T1 10 T0 minimum 10mins maximum 8hrs T0 2 43Vdc 2 35Vdc 2 25Vdc Solar...

Страница 32: ...eneral Specifications INVERTER MODEL 1KVA 24V 1KVA 48V 2KVA 24V 3KVA 24V 3KVA 48V 2KVA 24V Plus 3KVA 24V Plus 2KVA 48V Plus 3KVA 48V Plus 4KVA 5KVA Safety Certification CE Operating Temperature Range...

Страница 33: ...nd LEDs are flashing Battery is disconnected Check if battery wires are connected well Buzzer beeps continuously and red LED is on Fault code 07 Overload error The inverter is overload 110 and time is...

Страница 34: ...8 503 800 139 339 1000 112 269 1200 95 227 1400 81 176 1600 62 140 1800 55 125 2000 50 112 3KVA 300 449 1100 600 222 525 900 124 303 1200 95 227 1500 68 164 1800 56 126 2100 48 108 2400 35 94 2700 31...

Страница 35: ...00 123 301 2100 105 253 2400 91 219 2700 71 174 3000 63 155 4KVA 400 766 1610 800 335 766 1200 198 503 1600 139 339 2000 112 269 2400 95 227 2800 81 176 3200 62 140 3600 55 125 4000 50 112 5KVA 500 61...

Отзывы: