61
MPSYSTEMS-M-001/06
9.6.7.
Alarms ‘RC’
RC unit uses one alarm output to interface with R Series. If a fault occurs, a signal is sent
to the alarm circuit on R Series, which, typically, will put machine tool into a feed hold. The
units PLC will display fault type.
Alarm will not clear off PLC display until fault has been rectified. Once fault has been
remedied, press
[ 1 ]
to clear alarm.
ALARM DISPLAY
SYMPTOM(S)
CAUSE
LOW FLOW
Less than 5GPM through heat
exchanger
Heat exchanger
clogged.
Circulation pump
rotation reversed.
OVERLOAD
Motor overload tripped
Electric motor short
cycle.
Electric motor shorting.
Load on motor to great.
Electric motor over load
set to low.
Electrical short in system
causing overload to trip.
INLET OUT OF RANGE
Sensor fault
Inlet temperature out of
range.
OUTLET OUT OF RANGE
Sensor fault
Outlet temperature out
of range.
HP PUMP FAULT
R Series high pressure system
fault
R Series Fault.
Содержание AK CB20
Страница 15: ...9 MPSYSTEMS M 001 06 4 2 1 Floor Layout R VR SERIES 28 36 15 24 ...
Страница 16: ...10 MPSYSTEMS M 001 06 RF16 RT VR16 VRT SERIES 15 24 38 42 ...
Страница 25: ...19 MPSYSTEMS M 001 06 6 3 3 1 R RA11 Series Control Signal Explanation ...
Страница 26: ...20 MPSYSTEMS M 001 06 6 3 3 1 1 Variable Adaptive Series Control Signal Explanation VR ...
Страница 33: ...27 MPSYSTEMS M 001 06 6 5 3 8JIC to 6JIS Fitting Explanation ...
Страница 72: ...66 MPSYSTEMS M 001 06 10 2 Relief Valve Identifier ...
Страница 76: ...70 MPSYSTEMS M 001 06 JIS JIC Fittings Example 6 3 8 JIS 6 3 8 JIC 8 1 2 JIS 8 1 2 JIC ...
Страница 77: ...71 MPSYSTEMS M 001 06 RF8 Series Flow Diagram ...
Страница 78: ...72 MPSYSTEMS M 001 06 RFC Series Flow Diagram ...
Страница 79: ...73 MPSYSTEMS M 001 06 RA11 Series Flow Diagram ...
Страница 80: ...74 MPSYSTEMS M 001 06 RT Series Flow Diagram ...
Страница 81: ...75 MPSYSTEMS M 001 06 RF16 Series Flow Diagram ...