PT-G7828/G7728
Featured Functions
3-19
System Events
Description
LLDP Table Change
Nearly connected devices are changed and shown in the LLDP table
Login Failure Lockout
The attempt to log in exceeds the threshold
Account Info Changed
The account information has been changed
Configuration is Imported
When the configuration is successfully imported
SSL Certification is Imported
When SSL Certification is successfully imported
Fiber Check Warning
If the corresponding value of the fiber port status exceeds the threshold
defined by the Fiber Check function
MAC Sticky Violation Port Disable
Any port with MAC sticky function is disabled because of a rule violation
Port module inserted
The module is inserted to the system
Port module removed
The module is removed from the system
Port module unrecognized
The module inserted is not recognized by the system
Dual image fail
One of the image has failed
Tracking Status Changed
The tracking status has changed
Port Enable Tracking Changed
The tracking status has changed and reacts on Port Enable
Static Route Tracking Changed
The tracking status has changed and reacts on Static Route
VRRP Tracking Changed
The tracking status has changed and reacts on VRRP priority
EPS Off->On
The external power supply for PoE is on
EPS On->Off
The external power supply for PoE is off
GOOSE Check Event
The GOOSE check status has changed
Dying Gasp
When power input of power module is lower the system uptime threshold
the dying gasp function will be activated. This event will only activate
before the whole system powers off.
Four response actions are available when events are triggered.
Action
Description
Trap
A notification will be sent to the trap server when an event is triggered.
A notification will be sent to the email server defined in the Email Setting.
Syslog
A notification will be sent to the syslog server defined in Syslog Server Setting.
Relay
Supports digital inputs to integrate sensors. When an event is triggered, the device will
automate alarms through the relay output.
Severity
Severity
Description
Emergency
System is unusable
Alert
Action must be taken immediately
Critical
Critical conditions
Error
Error conditions
Warning
Warning conditions
Notice
Normal but significant condition
Information
Informational messages
Debug
Debug-level messages