Dimensions 

Unit: mm (inch) 

 

Reset Button 

Restore the MGate to factory default settings by using a pointed object 
(such as a straightened paper clip) to hold the reset button down until the 
Ready LED stops blinking (approximately five seconds). 

Pull-up, Pull-down, and Terminator for RS-485 

Beneath the MGate 5103’s top cover, you will find DIP switches to adjust 
each serial port’s pull-up resistor, pull-down resistor, and terminator. 

 

SW 

Pull-up 

  resistor 

Pull-down 

resistor 

Terminator 

ON 

1 k

 

1 k

 

120 

 

OFF 

150 k

150 k

–* 

*Default 

Hardware Installation Procedure 

1.

 

Connect the power adapter. Connect the 12-48 VDC power line or 
DIN-rail power supply to the MGate 5103’s terminal block. 

2.

 

Use a serial cable to connect the MGate to the Modbus device. 

3.

 

Use an Ethernet cable to connect the MGate to the PROFINET IO 
controller. 

4.

 

The MGate 5103 is designed to be attached to a DIN rail or mounted 
on a wall. For DIN-rail mounting, push down the spring and properly 
attach it to the DIN rail until it “snaps” into place. For wall mounting, 
install the wall-mounting kit (optional) first and then screw the device 
onto the wall.   
 
 
 

 
The following figure illustrates the two mounting options: 

Содержание MGate 5103

Страница 1: ...ricas Toll free 1 888 669 2872 Tel 1 714 528 6777 Fax 1 714 528 6778 Moxa China Shanghai office Toll free 800 820 5036 Tel 86 21 5258 9955 Fax 86 21 5258 5505 Moxa Europe Tel 49 89 3 70 03 99 0 Fax 49...

Страница 2: ...ck installation guide printed Warranty card Please notify your sales representative if any of the above items is missing or damaged Optional Accessories can be purchased separately CBL F9M9 150 DB9 fe...

Страница 3: ...ing Red Blinking Communication error When MGate 5103 acts as Modbus Client Master 1 Slave device returned an error exception 2 Received a frame error parity error checksum error 3 Timeout slave device...

Страница 4: ...ON 1 k 1 k 120 OFF 150 k 150 k Default Hardware Installation Procedure 1 Connect the power adapter Connect the 12 48 VDC power line or DIN rail power supply to the MGate 5103 s terminal block 2 Use a...

Страница 5: ...Default account admin Default password moxa Pin Assignments Modbus Serial Port Male DB9 Pin RS 232 RS 422 RS 485 4W RS 485 2W 1 DCD TxD A 2 RXD TxD B 3 TXD RxD B Data B 4 DTR RxD A Data A 5 GND GND G...

Страница 6: ...4 Standards Covered EN 60079 0 2013 A11 2013 IEC 60079 0 6th Ed AND EN 60079 15 2010 IEC 60079 15 4th Ed 5 The conditions of safe use a Ethernet Communications Devices are intended for mounting in a t...

Страница 7: ...locations only WARNING EXPLOSION HAZARD Do not disconnect the equipment unless the power has been switched off or the area is known to be nonhazardous WARNING EXPLOSION HAZARD The substitution of any...

Отзывы: