Configure Modbus Settings
The Serial tab is where Modbus serial port’s communication parameters are configured. You can configure Baud
Rate, Parity, Stop Bit, Flow Control, FIFO, and Interface Mode.
Mode
Description
RTU Master
Modbus RTU slave(s) will be connected to the serial port
RTU Slave
A Modbus RTU master will be connected to the serial port
ASCII Master
Modbus ASCII slave(s) will be connected to the serial port
ASCII Slave
A Modbus ASCII master will be connected to the serial port
Serial Port
Description
Baud Rate
50 bps to 921600 bps
Parity
None, Odd, Even, Mark, Space
Data Bits
8
Stop Bits
1, 2
Flow Control
None, DTR/DSR, RTS/CTS
FIFO
Enable, Disable
Interface
RS-232, RS-422, RS-485 2-wire, RS-485 4-wire