ioLogik R1200 Series
Using ioSearch
3-14
Users can define burnout values (BO, default 2 mA) for selected ranges. When input values are in the burnout
range, raw data will register as 0000h to indicate analog input burnout. The definition of raw data is as follows:
Burnout Value (BO)
0.0 < BO < 4.0
User defined (default 2 mA)
Burnout State
0 ≤ AI < BO mA
S/W output 0000h
Under Range
BO ≤ AI < 4 mA
S/W output raw data
Normal Range
4 ≤AI ≤ 20.00 mA
S/W output raw data until FFFEh
Over Range
XX > 20.00 mA
S/W output FFFFh
ATTENTION
When configuring the jumpers to select voltage or current measurement for the AI channels, open the cover by
first removing the screw on the back panel. Details on jumper settings can be found in the Jumper Settings
(DIO and AI) section.
Configuring Analog Output Channels
The current status of each AO (analog output) channel can be viewed on the I/O Setting: