ioLogik E1200H Series
Modbus/TCP Default Address Mappings
A-14
Reference
Address
Data Type
Description
30564
0x0233
1 word
Read AI 3 Current Mode Status
0: Normal
1: Burn Out
2: Over Range
30565
0x0234
1 word
Read AI 4 Current Mode Status
0: Normal
1: Burn Out
2: Over Range
30566
0x0235
1 word
Read AI 5Current Mode Status
0: Normal
1: Burn Out
2: Over Range
30567
0x0236
1 word
Read AI 6 Current Mode Status
0: Normal
1: Burn Out
2: Over Range
30568
0x0237
1 word
Read AI 7 Current Mode Status
0: Normal
1: Burn Out
2: Over Range
30569
0x0238
1 word
Read AI 8 Current Mode Status
0: Normal
1: Burn Out
2: Over Range
30570
0x0239
1 word
Read AI 9 Current Mode Status
0: Normal
1: Burn Out
2: Over Range
RTD Channel
31537
0x0600
1 word
CH0 RTD Value
<R> 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31538
0x0601
1 word
CH1 RTD Value
<R> 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31539
0x0602
1 word
CH2 RTD Value
<R> 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
4xxxx Read/Write Registers (Support function 3, 6, 16)
Reference
Address
Data Type
Description
DO Channel
40001
0x0000
1 word
CH0 DO Value 0: Off 1: On
40002
0x0001
1 word
CH1 DO Value 0: Off 1: On
40003
0x0002
1 word
CH2 DO Value 0: Off 1: On
40004
0x0003
1 word
CH3 DO Value 0: Off 1: On
40005
0x0004
1 word
CH4 DO Value 0: Off 1: On
40006
0x0005
1 word
CH5 DO Value 0: Off 1: On
40007
0x0006
1 word
CH6 DO Value 0: Off 1: On
40008
0x0007
1 word
CH7 DO Value 0: Off 1: On
40009
0x0008
1 word
CH8 DO Value 0: Off 1: On
40010
0x0009
1 word
CH9 DO Value 0: Off 1: On
40011
0x000A
1 word
CH10 DO Value 0: Off 1: On
40012
0x000B
1 word
CH11 DO Value 0: Off 1: On