Moxa Technologies ICF-1280I Series Скачать руководство пользователя страница 9

 

- 9 - 

LED Indicators 

There are 7 LED indicators on the front panel of the ICF-1280I series 
converter. 

LED 

Color 

Description 

Relay 

Status 

PWR1/PWR2 

Solid 

green 

Power is on 

Closed 

Off 

Power is off, or power error 

condition exists 

Open 

Ready 

Solid 

green 

Baud rate is detected, converter 

is ready for communication 

Closed 

Flashing 

green* 

Fiber diagnosis is finished 

Closed 

Flashing 

red* 

Detecting baudrate. 

Closed 

Flashing 

red and 

green* 

Slotting time setting error 

Closed 

Off 

System power is off 

Closed 

P1/P2   

(Fiber) 

Flashing

/solid 

green 

Fiber port is receiving data 

Closed 

Solid 

red* 

Fiber cable linking to Tx is 

abnormal 

Open 

Flashing 

red* 

Fiber cable linking to Rx is 

abnormal 

Open 

Off 

Fiber in idle state 

Closed 

P3 

(PROFIBUS) 

Flashing 

green 

PROFIBUS port is 

communicating 

Closed 

Flashing 

red 

Inner transceiver IC defective; 

PROFIBUS port Data 

communication error; 

Insufficient shielding of the bus 

cable; 

Echo package timeout 

Open 

Solid red  Echo package timeout, 

PROFIBUS UART character error 

Open 

Off 

PROFIBUS in idle state 

Closed 

Fault 

Solid 

green 

Fiber connections are working 

normally in Fiber Diagnosis 

mode 

Closed 

Flashing 

red* 

Fiber abnormality occurred in 

another segment 

Closed 

Solid 

red* 

Fiber abnormality occurred on 

this converter 

Closed 

If both power inputs experience an outage, the relay will become an 
open circuit for alarm purposes. 
 
*Refer to the following table for troubleshooting. 

 
*Refer to the 

Remote Fiber Diagnosis 

section for instructions. 

 
If an ICF-1280I converter is deployed at the beginning or at the end of the 
topology in Linear mode or Star mode, the unused port should be 
disabled. In such cases, it is recommended to use an ICF-1180I series 
converter. Please use the ICF-1180I series with Rev. 1.3, or higher 
versions, to connect with the ICF-1280I series. 

Содержание ICF-1280I Series

Страница 1: ...2013 Moxa Inc All rights reserved P N 1802012800011 Moxa ICF 1280I Series Industrial PROFIBUS to Fiber Converter Hardware Installation Guide First Edition August 2013...

Страница 2: ...ence and radio frequency interference It provides a clean communication path and is immune to cross talk Insulation Optical fiber is an insulator interface the glass fiber eliminates the need for usin...

Страница 3: ...Protection feature protects against accidentally connecting the power cables to the wrong terminal The converter is designed to detect automatically which power wire is positive and which is negative...

Страница 4: ...o this converter are working properly the Fault LED will flash red As a result you should run Remote Fiber Diagnosis on every other second converter in the topology to recursively troubleshoot the pro...

Страница 5: ...F 1280I S models Up to 4 km with multi mode ICF 1280I M models Point to point linear bus star and redundant ring topologies Dual power input for redundancy Wide operating temperature from 40 to 75 C f...

Страница 6: ...ack panel of the ICF 1280I converter when you take it out of the box If you need to reattach the DIN rail attachment plate to the ICF 1280I converter make sure the stiff metal spring is situated towar...

Страница 7: ...nterference that may cause undesired operation Slot Time Settings Although ICF 1280I series converters can be connected in different topologies with a large number of units the total cable length and...

Страница 8: ...40 28 6000 951 120 24 3000 551 60 24 1500 351 30 24 500 251 10 24 187 5 171 3 75 24 93 75 171 1 875 24 45 45 851 0 909 24 19 2 171 0 384 24 9 6 171 0 192 24 Transmission Speed kbps SW1 SW2 SW3 SW4 Aut...

Страница 9: ...nner transceiver IC defective PROFIBUS port Data communication error Insufficient shielding of the bus cable Echo package timeout Open Solid red Echo package timeout PROFIBUS UART character error Open...

Страница 10: ...ity occurred on this converter Check P1 and P2 LEDs P1 P2 Flashing red Rx fiber cable abnormality Check the Rx fiber cable connecting to this port Tx and Rx cables crossed over Partner module is power...

Страница 11: ...Cable Single mode Multi mode 8 3 125 8 7 125 9 125 or 10 125 m 50 125 62 5 125 or 100 140 m Wavelength ICF 1280I S 1310 nm ICF 1280I M 820 nm Tx Output ICF 1280I S 7 dBm ICF 1280I M 14 dBm Rx Sensitiv...

Страница 12: ...latory Approvals Safety UL 508 EN 60950 1 EMC CE FCC Part 15 sub part B Class A EMI EN 55022 Class A EN 55024 EMS EN 61000 4 2 ESD Level 2 EN 61000 4 3 RS Level 3 EN 61000 4 4 EFT Level 4 EN 61000 4 5...

Отзывы: