LED Indicators
There are 7 LED indicators on the front panel of the ICF-1280I series
converter.
LED
Color
Description
Relay
Status
PWR1/PWR2
Solid
green
Power is on
Closed
Off
Power is off, or power error
condition exists
Open
Ready
Solid
green
Baud rate is detected, converter
is ready for communication
Closed
Flashing
green*
Fiber diagnosis is finished
Closed
Flashing
red*
Detecting baudrate.
Closed
Flashing
red and
green*
Slotting time setting error
Closed
Off
System power is off
Closed
P1/P2
(Fiber)
Flashing
/solid
green
Fiber port is receiving data
Closed
Solid
red*
Fiber cable linking to Tx is
abnormal
Open
Flashing
red*
Fiber cable linking to Rx is
abnormal
Open
Off
Fiber in idle state
Closed
P3
(PROFIBUS)
Flashing
green
PROFIBUS port is
communicating
Closed
Flashing
red
Inner transceiver IC defective;
PROFIBUS port Data
communication error;
Insufficient shielding of the bus
cable;
Echo package timeout
Open
Solid red Echo package timeout,
PROFIBUS UART character error
Open
Off
PROFIBUS in idle state
Closed
Fault
Solid
green
Fiber connections are working
normally in Fiber Diagnosis
mode
Closed
Flashing
red*
Fiber abnormality occurred in
another segment
Closed
Solid
red*
Fiber abnormality occurred on
this converter
Closed
If both power inputs experience an outage, the relay will become an
open circuit for alarm purposes.
*Refer to the following table for troubleshooting.
*Refer to the
Remote Fiber Diagnosis
section for instructions.
If an ICF-1280I converter is deployed at the beginning or at the end of the
topology in Linear mode or Star mode, the unused port should be
disabled. In such cases, it is recommended to use an ICF-1180I series
converter. Please use the ICF-1180I series with Rev. 1.3, or higher
versions, to connect with the ICF-1280I series.