- 5 -
must be purchased separately. Refer to the detailed specifications
below:
Head Type:
flat
Head Diameter
>5.2 mm
Length
>6 mm
Thread Size:
M3 x 0.5 mm
Connector Description
Power Terminal Block
A person trained for the job should install the wiring for the input
terminal block. The wire type should be copper (Cu) and only 28-18
AWG wire size and torque value 0.5 N-m should be used.
Power Jack
Connect the power jack (in the package) to the AIG-100’s DC terminal
block (on the bottom panel), and then connect the power adapter. It
takes several seconds for the system to boot up. Once the system is
ready, the SYS LED will light up.
NOTE
The product is intended to be supplied by a UL Listed Power
Unit marked "L.P.S." (or "Limited Power Source") and is rated
9-36 VDC, 0.8 A min., Tma = 70°C (min). If you need further
help with purchasing the power source, please contact Moxa for
further information.
Grounding
Grounding and wire routing help limit the effects of noise because of
electromagnetic interference (EMI). There are two ways to connect the
AIG-100 grounding wire to the ground.
1.
Through the SG (Shielded Ground):
The SG contact is the left-most contact in the
3-pin power terminal block connector when
viewed from the angle shown here. When you
connect to the SG contact, the noise will be
routed through the PCB and the PCB copper
pillar to the metal chassis.
2.
Through the GS (Grounding Screw):
The GS is next to the power connector. When
you connect to the GS wire, the noise is
routed directly through the metal chassis.
NOTE
The grounding wire should have a minimum diameter of
3.31 mm
2
.