10. Parameter Settings
Parameter
Description
„Register :8“ Setting:
Multiplier
Divisor
Offset
These operands allow to convert the result to the desired engineering
units.
The conversion affects the numeric value for serial read out from register
<:8> only, but not the scaling of the analogue output.
With the settings Multiplier
= 1,0000
Divisor
= 1,0000
Offset
= 0,0000
the readout from register < :8 > equals to the percentage result (xxx.xxx%)
, where 100,000% has been defined by the TEACH minimum and TEACH
maximum settings
+/-Operand
Readout from <:8>
=
Measuring result in % of full scale
x
xOperand
/Operand
+
With “Divisor” set to 0 the whole conversion will be skipped, resulting in
lower calculation time and the shortest possible conversion time.
The calculation result from [ Multiplier : Divisor ] must not exceed a value
of 15 000 !
Direction:
Can be used to invert the polarity of the analogue output signal when
converting quadrature A/B input signals or A=impulse and B=direction.
0 =
no inversion of the polarity
1 =
inversion of the polarity
A/B Mode:
Sets the counting mode with two independent single-channel inputs
0 = no combination
1 = sum A + B
2 = difference A – B
See DIL switch settings in chapter 5.1
.
Linearization
Mode:
Sets the mode of linearization.
0:
Linearization off, registers P1_x to P16_y do not affect the output
characteristics.
1:
Linearization in a range of 0 – 100%
2:
Linearization over full range –100% to +100%
See example in chapter „Linearization“