Analog Menu
This menu defines the basic settings of the analog output.
This function is only available for devices with option AO.
ANALOG SOURCE
This parameter defines the reference source for analog output
0 MEASUREM. RESULT
Reference source is the measurement result of the selected operating mode.
1 COUNTER A
Reference source is the counter reading of channel A.
(only visible in mode COUNTER
COUNT MODE: A+B or A-B)
2 COUNTER B
Reference source is the counter reading of channel B.
(only visible in mode COUNTER
COUNT MODE: A+B or A-B)
3 BATCH COUNTER
Reference source is the batch counter.
(only visible in mode COUNTER
BATCH / TOTAL MODE:
INCREMENT BATCH, DECREMENT BATCH or USE INPUTS ONLY)
4 TOTAL COUNTER
Reference source is total counter.
(only visible in mode COUNTER
BATCH / TOTAL MODE: TOTAL COUNTER)
5 TOTAL TIMER
Reference source is the total timer.
(only visible in mode TIMER
TOTAL TIME MODE: YES)
ANALOG FORMAT
This parameter defines the output characteristics. The analogue output is proportional to the display value.
With setting ANALOG FORMAT (-10 … +10 V) in MODE COUNTER the polarity of the analog output depends on the
polarity of the display value.
0
-10…10V
-10 … +10 V
1
0…20M
0 … 20 mA
2
4…20MA
4 … 20 mA
ANALOG START
This parameter defines the start value of the analog conversion. This start value is corresponding to the display value
for an analog output of 0 V or 0/4 mA.
-99999999
Smallest start value
0
Default value
+99999999
Highest start value
ANALOG END
This parameter defines the end value of the analog conversion. This end value is corresponding to the display value
for an analog output of (+/-) 10 V or 20mA.
-99999999
Smallest end value
10000
Default Wert
+99999999
Highest end value
ANALOG GAIN (%)
This parameter specifies the maximum conversion of the analog output in %.
e. g. 102.00 corresponds to a conversion of 10.2 V or 20.4 mA, when the ANALOG END value is reached.
e. g. 95.00 corresponds to a conversion of 9.5 V or 18 mA, when the ANALOG END value is reached.
0
Smallest gain
100
Default value
110
Highest gain