Dx350_06d_oi_e.docx / Jul-20
page 23 / 67
General Menu
OPERATIONAL MODE
This parameter specifies the selected measuring function.
0 SPEED
Speed indicator (RPM), tachometer or frequency counter
1 PROCESS TIME
Operation as baking time or processing time indicator (reciprocal speed)
2 TIMER
Operation as stopwatch
3 COUNTER
Operation as position indicator, event-, sum-, differential- or up-down counter
4 VELOCITY
Runtime measurement as speed indicator
ENCODER PROPERTIES
(for DX350)
This parameter determines the characteristics of the pulse input for DX350.
0 PNP
PNP (switch to +)
1 NPN
NPN (switch to -)
2 NAMUR
Connect sensor (–) to GND and sensor (+) to input (A or B)
3 TRI-STATE
Tri-State for push-pull encoders/ sensors
ENCODER PROPERTIES
(for DX355)
This parameter determines the characteristics of the pulse input for DX355.
0 RS422
RS422 standard
1 HTL DIFFERENTIAL
HTL differential
2 HTL PNP
HTL PNP single ended (switch to +)
3 HTL NPN
HTL NPN single ended (switch to -)
ENCODER SUPPLY
(only for DX355 available)
This parameter defines the voltage of the auxiliary supply output (Aux-Out).
0 24VDC SUPPLY
24 VDC encoder supply
1 5VDC SUPPLY
5 VDC encoder supply
COUNTING DIRECTION
This parameter determines the direction of counting. (Only in mode COUNTER)
0 FORWARD
forward
1 REVERSE
reverse