background image

VMX-synergy™ - Profibus DP Interface Quick Start Guide               

           1 | 

P a g e

 

 

 

 

Caution

 

This option module is specifically designed to be used with 
the VMX-synergy

TM

 range of soft-start products and is 

intended for professional incorporation into complete 
equipment or systems. If installed incorrectly it may present a 
safety hazard. Before commencing installation and 
commissioning, the user should ensure they are fully familiar 
with the VMX-synergy

TM

 unit, and in particular have read the 

important safety information and warnings contained in the 
VMX-synergy

TM

 User Guide.  

 

Overview

 

The Profibus DP Interface is intended to be installed in the 
VMX-synergy

TM

 option slot, and allows the VMX-synergy

TM

 to 

be connected to a Profibus DP network. The interface offers 
the following functionality:-  

 

 

Installation

 

 

Ensure all power is removed from the VMX-
synergy

TM

 unit prior to installing the option module 

 

Remove the blanking plate from the option module 
slot 

 

Carefully slide the option module into the slot, 
ensuring that the location tabs are correctly aligned. 
DO NOT USE EXCESSIVE FORCE 

 

Tighten the two screws on the option module to 
secure 

 

VMX-synergy configuration 

VMX-synergy

TM

 will automatically configure when the option 

module is installed. Correct installation can be confirmed 
from the touch screen interface: 

Device >> Networks >> Profibus 

 

 

 

 

 

Front panel 

 

 

 

 

 

 

 

 

  

Item 

  

Operation mode 

Status 

Profibus network 
connector 

 

 

Operation mode 

 

 

 

 

 

 

 

 

State 

Indication 

  

Off 

  

No power or not inserted 

Green 

Online data exchange 

Green, flashing 

Network OK, no data exchange 

Single Red flash 

Parameter error 

Double Red flash 

Network error 

  

Status 

 

 

 

 

State 

Indication 

  

Off 

  

No power  

  

  

Green 

Initialised 

  

Green, flashing 

Initialised, Self testing 

Red 

Error 

  

Profibus DP Connector Pinout 

 

 

 

 

 

 

 

 

Pin 

Function 

  

  

N/C 

  

N/C 

B line Positive RxD/TxD, 
RS485 

  

RTS 

Bus Ground (GND) 

  

+5V Bus output termination power 

 

N/C 

 

A Line negative RxD/TxD, RS485 

 

N/C 

 

Отзывы: