68P80801E30-A 5/1/2002
3-35
Gen 3 Site Controller System Manual
Chapter 3 Pre-Installation
Recommended Tools, Equipment, and Parts
Recommended parts
Table 3-10 lists the recommended parts for installation. These are not
included as part of the system shipment and must be procured locally. All
model numbers are Motorola part numbers, unless noted otherwise.
Table 3-10
Recommended parts for installation
Part
Type/size
Supplier
Where used
anchor kit
#02100-13
Hendry
cabinet floor anchors
bolts
3/8x16x3/4”
locally
procured
Breaker Panel on
Power Supply Rack
1/4x20x1/2”
locally
procured
DC return bus,
Power Supply Rack
colored
vinyl tape
red, black, green,
brown, yellow, and
white
locally
procured
wire identification
grease
anti-oxidant
locally
procured
battery terminal
corrosion control
lockwashers
split - 3/8”
locally
procured
Breaker Panel,
Power Supply Rack
split - 1/4”
locally
procured
DC return bus,
Power Supply Rack
lugs
2 hole 1” center
various sizes
locally
procured
battery connection;
3/8” bolt, 4/0 Cu
lugs
2 hole 1” center
locally
procured
DC return
connection; 1/4”
bolt, #6 Cu
power
cables
#6 AWG stranded Cu
(red and black)
locally
procured
Power Supply wiring
4/0 stranded Cu (red
and black)
locally
procured
Power Supply wiring
ground
cables
#2 AWG stranded Cu
(green)
locally
procured
cabinet grounding
#6 AWG stranded Cu
(green)
locally
procured
cabinet grounding
NOTE:
Refer to the Parts and Suppliers appendix for other cable sizes needed where
equipment cabinets are not next to each other.