Motorline professional MSC50 Скачать руководство пользователя страница 1

 

Rev. 1.0   07/05/2010 

MSC50

 

Easy  Light  twilight  switch,  makes  it  possible to carry out con-
trols without having light, there are various operational modes 
and types of power supply. 

- Mod.   

MSC50:

                     Power supply  

12-24 VAC-DC 

- Mod.   

MSC50 230V:

            Power supply            230VAC 

T

ECHNICAL 

D

ATA

 

- Power supply: 

See model 

- Max. consumption: 

2W 

- Relay Contact: 

30VDC 10A 

- Working temperature: 

-10÷55°C 

- Dimensions: 

80x54x38mm 

- Protection rating: 

IP 54 

 

 

C

ONNECTIONS OF THE 

CN1

 

T

ERMINAL BOARD

 

1:  Power supply 230VAC 
2:  Power supply 230VAC 

C

ONNECTIONS OF THE 

CN2

 

T

ERMINAL BOARD

 

1:  Power supply 24 VAC-DC 
2:  Power supply 0V 
3:  Power supply 12VAC-DC 
4:  Relay Contact Output 
5:  Relay Contact Output 
 

I

NITIAL 

F

UNCTIONING 

C

ONDITION

 

The device makes it possible to activate controls based on the 
light detected through the integrated sensor. Sensor sensitivity 
can  be  modified  using  the  VR1  trimmer  present  inside  of  the 
device.  By  using  the  SEL  and  SET  programming  keys  it  is 
possible  to  select  different  types  of  operation.  In  the  default 
configuration the device is set at an intermediate sensitivity to 
light through the VR1 trimmer and Monostable functioning with 
NO contact output. 

A

DJUSTING 

S

ENSITIVITY TO THE CAPTURED LIGHT

 

The device makes it possible to adjust Sensitivity of the light 
captured through the VR1 trimmer. The switching on of the 
LIGHT LED on the device indicates that the intensity of cap-
tured light exceeds the selected intervention threshold; in this 
way we will have a reference to the current light conditions to 
establish the desired one. 

 

 

P

ROGRAMMING 

K

EYS AND 

I

NDICATOR 

LED 

SEL Key

: selects the type of function to memorise, the choice 

is indicated by the flashing of the LED. By repeatedly pressing 
the  key,  it  is  possible  to  position  oneself  on  the  desired  func-
tion. The selection remains active for 15 seconds, displayed by 
the  flashing  LED,  after  which  the  control  unit  returns  to  the 
original status. 

SET Key

: carries out programming of the function chosen with 

the SEL key. 

Indicator LED

 

LED on: option memorised. 
LED off: option not memorised. 
Flashing LED: option selected. 

---------------------- MAIN MENU -----------------

 

LED Reference          LED Off                        LED On 

1) MONO                   Monostable                         Impulse 1 sec. 
2) TEMP.                    Timer = OFF                        Timer = ON 
3) I. CMD                    Relay Output NO                   Relay Output NC 

1)  MONO 

(Monostable Operation / Impulse 1 sec.)

 

The  control  unit  is  supplied  with  the  Monostable  operational 
mode  enabled  (MONO  LED  OFF),  meaning  that  the relay will 
activate every time that the sensor determines that there is no 
light, and will deactivate in the presence of light. When needing 
an  Impulse  type  of  functioning,  meaning  that the relay is only 
activated for one second each time that the sensor determines 
that  there  is  no  light,  programming  must  be  completed  in  the 
following  way:  position  the  SEL  key  on  the flashing of MONO 
LED  then  press  the  SET  key,  the  MONO  LED  will  simultane-
ously  switch  on  permanently  and  the  programming  is  com-
pleted. Repeat the procedure to restore the previous configura-
tion. 
 

2)  TEMP. 

(Timer Function enabled / disabled)

 

The control unit is supplied with the Timer functioning disabled 
(TIMER LED OFF). 
When  the  device  needs  to  be  used  with  the  timed  function, 
meaning  that  the  control  relay  is  active  for  the  programmed 
amount of time after the sensor has been activated. 
Proceed  as  follows:  position  the  SEL  key  on  TIMER LED and 
press the SET key to start programming, at the same time the 
TIMER LED will start to double flash; every double flash of the 
TIMER LED corresponds to an increase of 30 minutes up to a 
maximum of 12 hours  (24 double flashes), press the SET key 
until the desired time is reached; at the same time the selected 
value is saved and the TIMER LED will stay on.

 

It  is  possible  to  repeat  the  operation  in  case  of  an  incorrect 
programming. 

Displaying the programmed Time 

When verifying the previously programmed Time, it is possible 
to  display  it  in  the  following  way:  with  the  SEL  key  position 
yourself  on  TIMER  LED,  the  LED  will  start  to double flash for 
the  number  of  times  equal  to  the  Time  programmed  in  the 
memory (every double flash of the TIMER LED corresponds an 
increase  of  30  minutes),  (

example:  4  TIMER  LED  flashes  = 

120 minutes). 

 

3)  I. CMD 

( Inversion of NO / NC control functioning )

 

The  control  unit  is  with  a  Normally  Open  output  operational 
mode (LED I. CMD OFF).  
When needing an inverted mode of operation, with the control 
output set at Normally Closed, proceed as follows: position the 
SEL  key  on  the  flashing  of  LED  I.  CMD  then  press  the  SET 
key,  the  LED  I.  CMD  will  simultaneously  switch  on  perma-
nently  and  the  programming  is  completed.  Repeat  the  proce-
dure to restore the previous configuration. 