PROGRAMMING MENU - 04

PROGRAMMING MENU - 04

06. DESCRIPTIONS

06. DESCRIPTIONS

Parameter

Function

Settings

Factory Setting

04.00

OPEN SPEED

Allows set door opening speed.

00.00 to 70.00 Hz

50.00 to 70.00 Hz

04.01

CLOSE SPEED

Allows set door closing speed.

00.00 to 60.00 Hz

30.00 to 40.00 Hz

04.02

OPENING DECELERATION SPEED 

Allows you to select the deceleration speed on the ascent.

NOTE

 

• 

The changes on deceleration opening or closing speed will 

change the length of the deceleration.

00.00 to 40.00 Hz

25.00 Hz

04.03

CLOSING DECELERATION SPEED

Allows you to select the deceleration speed on the descent. 

NOTE

 

• 

If change the door speed it is necessary adjust this parameter.

00.00 to 40.00 Hz

25.00 Hz

04.50

LENGHT OPENING DECELERATION 

Allows to set the lenght of deceleration. The lenght can be set in 

course programming or in the menu diretly.

0 to 1000

150

(250mm)

04.51

LENGHT CLOSING DECELERATION 

Allows to set the lenght of deceleration. The lenght can be set in 

course programming or in the menu diretly.

0 to 1000

150

(250mm)

04.52

PAUSE TIME  

Allow to set the time the door is paused when it is open. 

NOTE

 

• 

By set 0 seconds, the door has no pause time.

0 = OFF

0 to 99

(ex: 99=99 sec.)

5s

04.53

HUMAN PRESENCE

This menu allows the door to open with an impulse until it reaches 

the limit switch.

In order to close the door the user must be permanently pressing the 

door down button.

In this function the pedestrian button will be descent.

0 = Disabled

1 = Enabled

0 = Disabled

04.54

OP-CH/PED BUTTON LOGIC 

This menu allows to add 3 working modes each with their 

specifications.

0 = Step by step

1 = Condominium

2 = Inversion

1 = Step by step

04.55

ACCELERATION RAMP AT OPENING

This menu allows you to adjust the opening acceleration ramp time 

to allow a smoother start of the door.

0 to 30

(ex: 10=1 sec.)

15

04.56

ACCELERATION RAMP AT CLOSING

This menu allows you to adjust the closing acceleration ramp time to 

allow a smoother start of the door.

0 to 30

(ex: 10=1 sec.)

15

Parameter

Function

Settings

Factory Setting

04.57

PEDESTRIAN OPENING TIME

This menu can select the lenght of the pedestrian opening. Knowing 

that 100 means 8M if put 12 means opening of a meter. If the Human 

presence is active this menu doesn't work. If set to 0 the CH/PED 

button will only be closed.

0 to 100

15

(aprox. 1.5m)

04.58

DECELERATION RAMP AT INVERSION

Allows to set the deceleration time at inversion. Steeper or smoother 

stop.

0 to 20

(ex: 10=1 sec.)

10

(1 s)

04.59

04.60

MANEUVERS COUNT 

This function allows to view all complete maneuvers performed by 

the automation.

The menu 04.60 show the number of maneuvers performed to the 

thousands while the menu 04.59 show up to hundreds of thousands 

(see example).

04.61

FLASHING LIGHT OUTPUT 

Allows to change the operating logic of flashing light. If it is set to 0 the 

flashing light will be active only when the motor is working. If select 

1 the flashing light is active as long as it exits the closing limit switch, 

when it reaches the closing limit switch it will remain ON for the time 

set in menu 04.63.

0 = connected 

in opening and 

closing

1 = courtesy light

0 = opening and 

closing

04.62

RESET MANEUVER COUNT

This menu allows to reset the maneuvers of menus 04.59 and 

04.60. In order to be able to reset, will need to enter the password 

available only to the Motorline technical department.

Password must be entered

04.63

COURTESY LIGHT TIME

This menu allows adjust the time when the light is on, since 

reaching the limit switch if selected in menu 04.61.

0 to 50 Min

0

04.64

PROGRAMMING MENU

This menu has the function of placing the control board in course 

programming.

0 to 1

1 = control board 

in programming

04.65

REVERSE SLOWDOWN ADJUSTMENT

 This menu allows you to adjust the inversion slowdown. When the 

door movement is reversed, the slowdown may be higher or lower 

than the reference value. Therefore, with this menu you can adjust 

to the desired value.

0 to 1000

150

Menu 04.59

Total maneuvers = 20502

Notes: 

1 maneuver = 1 opening 

and closing cycle.

Example:

Menu 04.60

If the values are incorrectly adjusted, there is a risk of damage to the motor and inverter.

Содержание MC115

Страница 1: ...V1 0 REV 08 2022 MC115 EN USER S AND INSTALLER S MANUAL...

Страница 2: ...ironmentally safe recycling Business users should contact their vendor and check the terms and conditions of the purchase agreement This product and its electronic accessories should not be mixed with...

Страница 3: ...enced in terms of usage of the product in a safe manner and who understands the risks and dangers involved Children shouldn t play with the product or opening devices to avoid the motorized door or ga...

Страница 4: ...and do not use it until all safety conditions have been met In the event of tripping of circuits breakers of fuse failure locate the malfunction and solve it before resetting the circuit breaker or r...

Страница 5: ...losing speed as well as the adjustment of the slowdown speed both in opening and in closing This control board allows easy and intuitive operation of various parameters and menus through a display It...

Страница 6: ...g the operation LEDs LED 1 ON Indicates that it is being powered at 230Vac OFF No power LED 2 ON SEC contact closed OFF SEC contact open LED 3 ON STR contact closed OFF STR contact open LED 4 Programm...

Страница 7: ...ocking or pre flashing light relay Programmable at parameter 04 61 MI1 Opening button MI2 Closing button MI3 Limit switch MI4 Limit switch MI5 Photocells MI6 STOP button MI7 Not used 24V Photocells an...

Страница 8: ...24V 4 24V 12 DCM 12 DCM DFM 16 10V 13 ACM 14 AVI 15 ACI 17 AFM 14 M01 15 M02 24V 9 S1 9 S2 15 DCM SG SG SGND 13 MCM BR1 N N L L L L L L M1 M2 M3 OP C P COM FAP FCH COM DS BL GND 24V BR2 E1 E1 R G B 1...

Страница 9: ...MI7 4 24V 4 24V 12 DCM 12 DCM DFM 16 10V 13 ACM 14 AVI 15 ACI 17 AFM 14 M01 15 M02 24V 9 S1 9 S2 15 DCM SG SG SGND 13 MCM BR1 N N L L L L L L M1 M2 M3 OP C P COM FAP FCH COM DS BL GND 24V BR2 E1 E1 R...

Страница 10: ...S2 15 DCM SG SG SGND 13 MCM BR1 N N L L L L L L M1 M2 M3 OP C P COM FAP FCH COM DS BL GND 24V BR2 E1 E1 R G B 12V LOOP 2 LOOP 2 LOOP 1 LOOP 1 5 6 3 4 EN 05 CONNECTIONS SQUEME OTHER CONNECTIONS MAGNETI...

Страница 11: ...M 14 AVI 15 ACI 17 AFM 14 M01 15 M02 24V 9 S1 9 S2 15 DCM SG SG SGND 13 MCM BR1 N N L L L L L L M1 M2 M3 OP C P COM FAP FCH COM DS BL GND 24V BR2 E1 E1 R G B 12V NO COM 4 15 EN 05 CONNECTIONS SQUEME C...

Страница 12: ...FCH COM DS BL GND 24V BR2 E1 E1 N L N L A1 A2 NC COM IN 230V OUT 230V EN 05 CONNECTIONS SQUEME UPS UNIT CONNECTION UPS UNIT POWER SUPPLY UPS POWER SUPPLY INPUT UPS POWER SUPPLY OUTPUT COM Common NC Re...

Страница 13: ...10V 13 ACM 14 AVI 15 ACI 17 AFM 14 M01 15 M02 24V 9 S1 9 S2 15 DCM SG SG SGND 13 MCM BR1 N N L L L L L L M1 M2 M3 OP C P COM FAP FCH COM DS BL GND 24V BR2 E1 E1 R G B 12V A B NC COM B A ON 1 2 ANT ST...

Страница 14: ...0 11 12 13 14 15 16 17 18 19 20 21 22 23 24 BL GND COM COM NO AC DC 12 24V LED COM NO AC DC 12 24V EN 05 CONNECTIONS SQUEME EXTERNAL COMPONENTS CONNECTIONS CONTROL BOARD CONNECTIONS MF2020 COLUMN PHOT...

Страница 15: ...fferent display modes 7 STOP RESET Restarts the device after a failure occurs 8 ENTER Used to enter change programming parameters 3 and 4 cannot be used Only the menus on page 16A can be set by the us...

Страница 16: ...Enter at parameter 00 07 and set password You will temporarily unlock the keyboard 2 Change the parameter you want The release will remain until the motor make a new operation WRONG PASSWORD 1 You hav...

Страница 17: ...r 0 to 30 ex 10 1 sec 15 Parameter Function Settings Factory Setting 04 57 PEDESTRIAN OPENING TIME This menu can select the lenght of the pedestrian opening Knowing that 100 means 8M if put 12 means o...

Страница 18: ...ton or a previously programmed remote control when you want the opening slowdown to start the speed automatically reduces Press the OP button or a previously programmed remote control when you want th...

Страница 19: ...tion time too short Increase the acceleration time OVERCURRENT DURING DECELERATION 01 Short circuit at the motor output Check that the isolation on the output lines is in good condition DETECTION OF E...

Отзывы: