2

2/08

6. Energize the load to be monitored. Verify normal running amps have been

achieved. The LED will be lit under normal operating conditions (the current
sensed is at an acceptable level) indicating the output contacts are energized
(NO is closed and NC is open). If the current drops to zero, the LSRU
will recognize a normal stop, and will not de-energize its relay.

NOTE: The standard LSRU is a fail-safe design, meaning the NO (normally

open contact) will be open if the LSRU fails or control power is
interrupted.

7. The installation is now complete.

LSRU

L3

L2

M

L1

L2

START

0L

STOP

OL

OL

L1

OL

MOTOR

M

MAGNE

TIC

CON

T

AC

T

OR

THREE 

PHAS

E PO

WER

CONTRO

L

 P

OWER

FIGURE 1: TYPICAL WIRING DIAGRAM

Unit  Description

Model 

Voltage 

Range

Options

Current Range

LSRU

024 – 18 to 30 VAC

O – Overcurrent

1.5 – 0 to 10 Amps

115 

– 

90 

to 135 

VAC 

– 

Undercurrent

2 – 5 to 25 Amps

T – Trip Delay

3 – 25 to 100 Amps

R – Restart Delay (seconds)

E – Extended Restart Delay (minutes)

Any questions or comments call SymCom at 1-800-843-8848 or 1-605-348-5580.

SymCom warrants its microcontroller based products against defects in material or workmanship
for a period of five (5) years from the date of manufacture. All other products manufactured by
SymCom shall be warranted against defects in material and workmanship for a period of two (2)
years from the date of manufacture.  For complete information on warranty, liability, terms, and
conditions, please refer to the SymCom Terms and Conditions of Sale document.