Configuration and Troubleshooting
2-8 Manual # 42-02-2P26
System Timers
-
Motor/Valve Time Limit
(Default 3 minutes)
Starts when the controller attempts to move the car in the up direction and
resets when the car reaches the destination floor. If the timer expires before
the car reaches its destination, the controller stops trying to move the car
up to protect the motor. The car will then lower to the bottom floor and shut
down.
-
Open Limit Time
(Default 10 seconds)
Determines how long the door operator should attempt to open the doors
before declaring an unsuccessful attempt (Door Open Fail 1 - 3). After 3
unsuccessful attempts, a Door Open Fault will be declared. This action pro-
tects the door motor.
-
Close Limit Time
(Default 10 seconds)
Determines how long the door operator should attempt to close the doors
before declaring an unsuccessful attempt (Door Close Fail 1 - 3). After 3
unsuccessful attempts, a Door Close Fault will be generated, followed by a
Door Fault Shutdown. This action protects the door motor.
-
Door Interlock Timer
(Default 100 mS)
Introduces a delay when closing or opening doors are abruptly reversed.
This may be required if the door operator is sensitive to such reversal due
to de-bounce capability. Set to 0.0 if not required.
-
Short Door Timer
(Default 1 second) Length of time doors will remain
open after being reopened by photo eye, safety edge, or door open button.
-
Car Call Timer
(Default 2 seconds)
Length of time doors will remain open to service a car call.
-
Hall Call Timer
(Default 4 seconds)
Length of time doors will remain open to service a hall call.
-
Lobby Call Timer
(Default 6 seconds)
Length of time doors will remain open to service a lobby call.
-
ADA Car Timer
(Default 3 seconds)
Length of time doors will remain open to service an ADA car call.
-
ADA Hall Timer
(Default 5 seconds)
Length of time doors will remain open to service an ADA hall call.
-
Stuck PHE Timer
(Default 10 seconds) Length of time the photo eye is
allowed to delay closing before it is bypassed and the doors begin to close.
-
Stuck SE Timer
(Default 20 seconds) Length of time the safety edge is
allowed to delay closing before it is bypassed and the doors begin to close.
-
Stuck DOB Timer
(Default 10 seconds) Length of time the door open but-
ton is allowed to delay closing before it is bypassed and the doors begin to
close.
-
Car Delayed Timer
(Default 30 seconds) Removes the car from hall call
demand if delayed beyond the timer setting.
-
COS Timer
(Default 5 minutes) If the car delayed condition persists for the
amount of time set here, the car will be removed from service for all calls.
-
FLO Timer
(Default 5 minutes) When a car is inactive for this amount of
time, the fan and light will automatically be turned off.
-
Door Hold Timer
(Default 20 seconds) Time to hold the doors open for a
momentary activation of the Door Hold input (button).
-
Parking Timer
(Default 2 seconds) If a car is idle in excess of the time set
here, it will move to its designated parking floor.
-
Sleep Mode Timer
(Default 10 minutes) The touch screen will enter sleep
mode when this timer expires if there has been no activity.
Table 2.1 Touchscreen Organization and Content
Tab
Subtab
Description
CONFIG
01