Part Number: 000016427 Rev 00 08/2020 103
Compressor Electrical Diagnostics
The compressor does not start or will trip repeatedly on overload.
Check Resistance (Ohm) Values
NOTE: Compressor windings can have very low ohm values. Use a properly calibrated
meter.
Perform the resistance test after the compressor cools. The compressor dome should be
cool enough to touch (below 120°F/49°C) to ensure that the overload is closed and the
resistance readings will be accurate.
Single Phase Compressors
1. Disconnect power and remove the wires from the compressor terminals.
2. The resistance values between C and S and between C and R, when added together
should equal the resistance value between S and R.
3. If the overload is open, there will be a resistance reading between S and R, and open
readings between C and S and between C and R. Allow the compressor to cool, then
check the readings again.
Check Motor Windings to Ground
Check continuity between all three terminals and the compressor shell or copper
refrigeration line. Scrape metal surface to get good contact. If continuity is present, the
compressor windings are grounded and the compressor should be replaced.
To determine if the compressor is seized, check the amp draw while the compressor is
trying to start.
Содержание PKM0335
Страница 2: ......
Страница 8: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 64: ...64 Part Number 000016427 Rev 00 08 2020 Troubleshooting THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 98: ...98 Part Number 000016427 Rev 00 08 2020 Troubleshooting THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 130: ...130 Part Number 000016427 Rev 00 08 2020 Specifications THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 131: ......
Страница 132: ...Katom 305 Katom Drive Kodak Tennessee 37764 Part Number 000016427 Rev 00 08 2020 ...