background image

MORTEX

 

PRODUCTS

 

INC

 

FORT

 

WORTH,

 

TX

 

76106

 

Page

 

9

 

13.

 

Check the evaporator condensate drain pan for any debris 
and ensure the pan is properly draining by pouring water 
into the drain to check it. 

14.

 

Remove any excess water that may have spilled from 
checking the evaporator condensate drain. 

15.

 

Reinstall the blower assembly and secure the assembly 
using the screws that was removed in step 5. 

16.

 

Reinstall the control box cover and secure it to the control 
box with the screw that was removed in step 4. 

17.

 

Reinstall the lower access door on the furnace. 

18.

 

Reinstall the upper access door on the front of the 
evaporator coil compartment. 

19.

 

Follow the instructions exactly as shown in Startup and 
Shutdown Section in this manual to properly startup this 
appliance. 

 

SECTION III: FURNACE CONTROLS  

 

This section discusses the furnace controls and how they 
operate. Refer to Figure 10 for component locations. 
1.

 

The Limit Controls

 – Each electric heater element has a 

limit control directly in front of it to sense overheating of 
the element and open if the temperature gets above the set 
point of the limit control. 

2.

 

The Heater Relays

 – The electric heater relays simply 

turn the heater elements on and off. The relays are 
controlled by the thermostat. On a call for heat 24 VAC is 
sent to the relay(s) 24 VAC coil energizing the relay. 
When the call for heat has been satisfied the 24 VAC is 
removed from the relays 24 VAC coil de-energizing the 
relay(s). 

3.

 

Cooling Time Delay Relay (TDR)

 – The cooling relay is 

used only when 24 VAC is on the “G” terminal from the 
thermostat. The relay controls the blower on time delay 
and is adjustable from 0 – 30 seconds. The factory setting 
is approximately 13 seconds. 

4.

 

Circuit breakers

 – The circuit breakers are designed as 

over-current protection for the electric heaters only. The 
circuit breakers MUST NEVER be used for over-current 
protection for the transformer, 24 VAC circuit, or the 
blower motor. 

5.

 

3 Amp Fuse

 – This fuse is used for over-current 

protection of the 24 VAC circuit. 

6.

 

Transformer

 – The transformer is used to step down 

voltage from 240 VAC to 24 VAC. The transformer 
provides the required 24 VAC for the system control 
circuit. 

7.

 

Blower Motor Isolation Relay

 - This relay is used to 

load the TDR when using an X-13 motor or for isolation 
between the high and low speeds of a PSC motor. The 
wiring has been designed so that the normally closed 
contacts are used for heating and the normally open 
contacts are used for cooling. The relay coil is energized 
after the thermostat has a call from the “G” terminal 
starting the time delay cycle on the time delay relay. Once 
the time delay relay has reached the delay setting the relay 
contacts close energizing the isolation relay coil. The 
normally closed contacts on the isolation relay open and 

the normally open contacts close, energizing the motor on 
the selected cooling speed. 

X-13Motor Isolation Relay

 - This relay is used on the X-13 

motor as a load for the time delay relay so the relay will 
operate properly. The wiring has been designed so that the 
normally closed contacts are used for heating and the normally 
open contacts are used for cooling. The relay coil is energized 
after the thermostat has a call from the “G” terminal starting 
the time delay cycle on the time delay relay. Once the time 
delay relay has reached the delay setting the relay contacts 
close energizing the isolation relay coil. The normally closed 
contacts on the isolation relay open and the normally open 
contacts close, energizing the motor on the selected cooling 
speed. 

SECTION IV: SEQUENCE OF OPERATION  

 

Continuous Blower 

The thermostat has a manual fan switch that can be moved to 
the “

On” 

position or it can be programmed for 

continuous

 fan 

operation. This setting causes the thermostat to complete the 
circuit between “R” and “G” terminals causing the time delay 
relay to start the time delay cycle. Once the time delay relay 
has completed the on-delay cycle the contacts will close 
sending voltage to the isolation relay coil. The isolation relay 
will close the normally open contacts (Terminals #2 and #4) 
sending voltage to selected indoor blower motor speed tap 
connected to terminal #4. The normally closed contacts 
(Terminals #5 and #6) will open. 
The indoor blower will operate continuously until the fan 
switch on the thermostat has been switched from on to auto. 

 

Figure 9: Component Locations 

 

Intermittent Blower - Cooling 

The thermostat has a manual fan switch that can be moved to 
the “

Auto”

 position or it can be programmed for 

auto 

fan 

operation. When the thermostat calls for cooling, a circuit is 
completed between the “R”, “Y” and “G” Terminals. The 
indoor fan motor is energized from the “G” terminal on the 
thermostat causing the time delay relay to start the on-time 

Содержание E30A2D0008ABA

Страница 1: ...21 2 Factory Speed Tap Settings 13 9 Accessory Parts List 22 3 Blower Performance 1 3 HP PSC Motor 14 10 Replacement Parts List 1 3 HP PSC Motor 23 4 Blower Performance 1 3 HP X 13 Motor 15 11 Replacement Parts List 1 3 HP X 13 Motor 24 5 1 Blower Performance 1 2 HP X 13 Motor 16 12 Replacement Parts List 1 2 HP X 13 Motor 25 5 2 Blower Performance 1 2 HP X 13 Motor 17 13 Replacement Parts List 3 ...

Страница 2: ...ow of air is required for safe and proper operation Never block or obstruct air openings used for ventilation and cooling of the furnace electrical components 8 Refer to the furnace rating plate for the furnace model number for the operating specifications for safe operation 9 Provide clearances for servicing ensuring service access is allowed for the control box electric elements and the blower 1...

Страница 3: ...hnician The furnace s best friend is a qualified service technician If the unit gives any indication of improper operation call the service technician The service technician is allowed to perform the normal routine care of your furnace He can detect potential problems and make corrections before trouble develops Preventative maintenance of this type will allow the furnace to operate with minimal c...

Страница 4: ...area If you smell vapors of any kind DO NOT turn on the power to the furnace until vapors have been ventilated and removed from the area of the furnace B CHECK THE FURNACE visually check the furnace for loose screws and or panels that may be missing or have fallen off C CHECK DUCT CONNECTIONS visually check the connections of the ducts to the furnace to make sure there are no gaps or holes and duc...

Страница 5: ...efer to Figure 5 11 Follow the instructions to Turn On Start the Appliance in the Startup and Shutdown section of these instructions 12 Follow the instructions to Turn On Start the Appliance in the Startup and Shutdown section of these instructions Coil Cabinet Top Air Filters Follow these easy steps to replace the filters located in the top of the coil compartment 1 Follow the procedure To Turn O...

Страница 6: ...instructed as to how to clean and reinstall filters washable or replaceable filters for good preventive maintenance Care must be taken that the edges of the washable or replaceable filter are resting on the protruding edges of the metal plates at each end of the aluminum fins This allows a gap between the filter and the coil surface to prevent dirt from wicking from the filter to the coil Make sur...

Страница 7: ...serious injury if clothing or body parts get caught in the moving part The manufacturer or distributer will not be responsible for any repairs due to improper parts changes improper maintenance improper furnace adjustments or improper modifications made by the homeowner and or the appliance user The manufacturer will not be responsible if the homeowner and or appliance user use this section of the...

Страница 8: ... dirt or debris from around the heater elements Be careful not to damage the heater elements with the vacuum hose or the brush Figure 7 Control Box Cover Figure 8 Blower Assembly and Mounting Screw Location 8 Check the blower wheel for dust and debris Use the brush and the vacuum cleaner to remove any dust or debris from the wheel Be careful not the move or accidentally remove the blower wheel bal...

Страница 9: ...or isolation between the high and low speeds of a PSC motor The wiring has been designed so that the normally closed contacts are used for heating and the normally open contacts are used for cooling The relay coil is energized after the thermostat has a call from the G terminal starting the time delay cycle on the time delay relay Once the time delay relay has reached the delay setting the relay c...

Страница 10: ...ing Cycle When the thermostat calls for cooling The thermostat closes the circuit between the R Y and G terminals 24 VAC is sent from the Y terminal through the yellow thermostat wire to the 24 VAC coil terminal on the condenser contactor energizing the contactor and starting the compressor and outdoor fan motor At the same time the G terminal is sending 24 VAC through the green pigtail wire to th...

Страница 11: ...240 VAC and 24 VAC at the motor terminals A If the 240 VAC and 24 VAC is present at the motor terminals but the motor is not operating then replace the motor Refer to Figure 12 and Table 1 for terminal locations and definitions B If 240 VAC is not present at the motor check for a broken wire between the circuit breaker number one and the motor C If 240 VAC is present at the motor terminals continu...

Страница 12: ... to OFF 3 Disconnect the plastic wire plug that has the wires that goes to the motor terminals from the top right side of the control box 4 Remove the two screws on the right side of the blower mounting plate 5 Slide the blower out of the blower compartment and set on the floor 6 Remove the wires from the terminals Be sure to write down the motor terminal identifier and wire color so the wires do ...

Страница 13: ... 8 R M Z 2 3 4 5 G 8 W 11 14 P 330 1680 7 56 223 98 8 R M Z 2 3 4 5 G 8 W 12 15 P 330 1680 8 00 210 98 8 R M Z 2 3 4 5 G 8 W 13 17 P See Example 330 CFM kW x 3412 x Voltage Correction Less Than 240V x 1 08 TR E30B3DxxxAAA Electric Furnace temperature rise TR can be used to determine air flow delivered This result can then be used to determine FPMvelocityacross the coil face area using the chart be...

Страница 14: ...5 952 949 946 928 890 724 648 532 364 with Cabinet97 FLSB 27 MEDIUM 1175 1170 1164 1143 1100 1025 964 716 558 405 or 97 FLSF 27 HI 1536 1463 1403 1328 1249 1155 1075 900 716 493 CFMwith Coil 98 8G7W OP LO 1010 1013 1001 975 930 874 688 587 463 363 with Cabinet97 FSOB 27 MEDIUM 1205 1184 1153 1110 1048 975 751 640 496 367 HI 1553 1482 1407 1328 1244 1154 1039 747 608 438 CFMwith Coil 96 8G4W OP LO ...

Страница 15: ...6 LO 764 689 586 507 460 399 332 MED LO 855 807 733 632 571 521 478 416 367 MEDIUM 990 923 878 825 741 672 628 574 520 440 MED HI 1085 1031 988 929 878 789 725 663 603 474 HI 1291 1247 1202 1160 1117 1073 1020 821 665 524 CFM with Coil LO 721 655 566 507 451 374 315 98 8G7W OP MED LO 828 756 705 623 561 529 462 404 359 with Cabinet MEDIUM 948 898 845 778 705 641 595 553 502 406 97 FSOB 27 MED HI 1...

Страница 16: ...656 630 494 with Cabinet MEDIUM 1251 1216 1170 1134 1079 1045 1009 860 685 570 97 FLSB 27 MED HI 1450 1410 1380 1335 1303 1221 1139 1056 737 580 or 97 FLSF 27 HI 1549 1506 1457 1410 1335 1246 1165 1056 741 648 CFM with Coil LO 878 811 771 714 625 558 536 478 417 377 98 8W7W OP MED LO 1035 981 943 891 852 797 702 652 609 474 with Cabinet MEDIUM 1223 1190 1151 1111 1072 1018 940 842 647 523 97 FSOB ...

Страница 17: ...1316 1245 1137 1012 679 551 or 97 FLSF 39 HI 1570 1531 1488 1415 1344 1279 1170 1070 736 562 CFMwith Coil LO 851 813 759 708 618 555 523 458 394 362 98 8Z12W OP MED LO 1021 982 934 884 837 740 684 636 573 452 with Cabinet MEDIUM 1210 1170 1138 1092 1052 999 922 751 613 469 97 FSOB 39 MED HI 1419 1385 1344 1279 1210 1083 1010 774 621 480 HI 1503 1458 1393 1312 1230 1103 1019 785 629 486 CFMwith Coi...

Страница 18: ...126 1104 1065 874 711 561 with Cabinet MEDIUM 1404 1350 1327 1294 1251 1211 1145 1005 718 535 97 FSOB 39 MED HI 1601 1538 1468 1400 1327 1241 1148 888 719 541 HI 1725 1613 1530 1442 1360 1283 1190 1088 739 576 CFM with Coil LO 1111 1072 1019 976 931 877 781 712 680 548 98 8G12W OP MED LO 1289 1255 1226 1185 1143 1105 1066 938 732 556 with Cabinet MEDIUM 1415 1367 1345 1308 1270 1226 1170 1072 751 ...

Страница 19: ...97 641 608 521 393 98 8W7W OP MEDIUM 1271 1222 1166 1117 1055 983 796 721 634 565 with Cabinet HI 1438 1369 1304 1232 1166 1090 1008 811 705 615 97 FSOB 27 CFM with Coil LO 932 919 913 893 860 808 752 674 555 450 98 8W12W OP MEDIUM 1336 1303 1279 1234 1172 1111 1030 948 793 678 with Cabinet HI 1683 1615 1552 1465 1386 1303 1208 1100 987 771 97 FLSB 39 or 97 FLSF 39 CFM with Coil LO 961 934 902 863...

Страница 20: ...4 637 553 with Cabinet HI 1448 1387 1314 1242 1175 1094 1006 916 732 578 97 FSOB 39 CFMwith Coil LO 946 940 913 890 850 807 701 613 555 445 96 8W4W OP MEDIUM 1319 1279 1229 1192 1155 1080 991 897 711 552 with Cabinet HI 1590 1534 1467 1396 1313 1223 1127 1028 904 731 97 FLSB 21 or 97 FLSF 21 CFMwith Coil LO 942 920 885 835 789 708 630 573 494 364 96 8W4W OP MEDIUM 1264 1203 1150 1090 1025 950 883 ...

Страница 21: ...862 622 474 98 8W12W OP MEDIUM 1502 1440 1370 1302 1240 1153 1059 950 823 523 with Cabinet HI 1599 1530 1457 1388 1314 1244 1355 1039 762 566 97 FSOB 39 CFM with Coil LO 1412 1372 1326 1278 1214 1145 1067 951 713 504 98 8G12W OP MEDIUM 1643 1577 1505 1438 1358 1288 1203 1107 983 684 with Cabinet HI 1747 1672 1605 1529 1443 1358 1275 1176 1056 688 FLSB 39 or 97 FLSF 39 CFM with Coil LO 1352 1301 12...

Страница 22: ...C 5 TON ACCESSORY BLOWER 86MH0026 3 4 HP X 13 5 TON ACCESSORY BLOWER 86MH0027 21 1200 CFM BROKE DOWN COOLING COIL CABINET 97 FLSB 21 21 1600 CFM BROKE DOWN COOLING COIL CABINET 97 FSOB 21 21 1800 CFM BROKE DOWN COOLING COIL CABINET 97 FLOB 21 31 1600 CFM BROKE DOWN COOLING COIL CABINET 97 FLSB 27 31 1600 CFM BROKE DOWN COOLING COIL CABINET 97 FSOB 27 31 1800 CFM BROKE DOWN COOLING COIL CABINET 97 ...

Страница 23: ...17 R68BAD018 R68BAD014 R68BAD018 R68BAD018 6 CIRCUIT BREAKER 2 R68BAD013 R68BAD013 R68BAD017 7 HEATER CONTACTOR 1 R68AB0019 R68AB0019 R68AB0019 R68AB0019 R68AB0019 R68AB0019 8 HEATER CONTACTOR 2 R68AB0019 R68AB0019 R68AB0019 9 TIME DELAY RELAY R68AC0009 R68AC0009 R68AC0009 R68AC0009 R68AC0009 R68AC0009 10 LIMIT 155 F R68CA0008 R68CA0008 R68CA0008 R68CA0008 R68CA0008 R68CA0008 11 GROUND LUG R68GF00...

Страница 24: ...IRCUIT BREAKER 1 R68BAD014 R68BAD017 R68BAD018 R68BAD014 R68BAD018 R68BAD018 7 CIRCUIT BREAKER 2 R68BAD013 R68BAD013 R68BAD017 8 HEATER CONTACTOR 1 R68AB0019 R68AB0019 R68AB0019 R68AB0019 R68AB0019 R68AB0019 9 HEATER CONTACTOR 2 R68AB0019 R68AB0019 R68AB0019 10 TIME DELAY RELAY R68AC0009 R68AC0009 R68AC0009 R68AC0009 R68AC0009 R68AC0009 11 LIMIT 155 F R68CA0008 R68CA0008 R68CA0008 R68CA0008 R68CA0...

Страница 25: ... BREAKER 1 R68BAD014 R68BAD017 R68BAD018 R68BAD014 R68BAD018 R68BAD018 7 CIRCUIT BREAKER 2 R68BAD013 R68BAD013 R68BAD017 8 HEATER CONTACTOR 1 R68AB0019 R68AB0019 R68AB0019 R68AB0019 R68AB0019 R68AB0019 9 HEATER CONTACTOR 2 R68AB0019 R68AB0019 R68AB0019 10 TIME DELAY RELAY R68AC0009 R68AC0009 R68AC0009 R68AC0009 R68AC0009 R68AC0009 11 LIMIT 155 F R68CA0008 R68CA0008 R68CA0008 R68CA0008 R68CA0008 R6...

Страница 26: ... BREAKER 1 R68BAD014 R68BAD017 R68BAD018 R68BAD014 R68BAD018 R68BAD018 7 CIRCUIT BREAKER 2 R68BAD013 R68BAD013 R68BAD017 8 HEATER CONTACTOR 1 R68AB0019 R68AB0019 R68AB0019 R68AB0019 R68AB0019 R68AB0019 9 HEATER CONTACTOR 2 R68AB0019 R68AB0019 R68AB0019 10 TIME DELAY RELAY R68AC0009 R68AC0009 R68AC0009 R68AC0009 R68AC0009 R68AC0009 11 LIMIT 155 F R68CA0008 R68CA0008 R68CA0008 R68CA0008 R68CA0008 R6...

Страница 27: ...68BAD014 R68BAD018 R68BAD018 6 CIRCUIT BREAKER 2 R68BAD013 R68BAD013 R68BAD017 7 HEATER CONTACTOR 1 R68AB0019 R68AB0019 R68AB0019 R68AB0019 R68AB0019 R68AB0019 8 HEATER CONTACTOR 2 R68AB0019 R68AB0019 R68AB0019 9 TIME DELAY RELAY R68AC0009 R68AC0009 R68AC0009 R68AC0009 R68AC0009 R68AC0009 10 LIMIT 155 F R68CA0008 R68CA0008 R68CA0008 R68CA0008 R68CA0008 R68CA0008 11 GROUND LUG R68GF0022 R68GF0022 R...

Страница 28: ...1 R68BAD014 R68BAD017 R68BAD018 R68BAD014 R68BAD018 R68BAD018 8 CIRCUIT BREAKER 2 R68BAD013 R68BAD013 R68BAD017 9 HEATER CONTACTOR 1 R68AB0019 R68AB0019 R68AB0019 R68AB0019 R68AB0019 R68AB0019 10 HEATER CONTACTOR 2 R68AB0019 R68AB0019 R68AB0019 11 TIME DELAY RELAY R68AC0009 R68AC0009 R68AC0009 R68AC0009 R68AC0009 R68AC0009 12 LIMIT 155 F R68CA0008 R68CA0008 R68CA0008 R68CA0008 R68CA0008 R68CA0008 ...

Отзывы: