background image

MORTEX

 

PRODUCTS

 

INC

 

FORT

 

WORTH,

 

TX

 

76106

 

Page

 

8

 

 

 
 
 
 
 
 
 
 
 
 
 

 

SECTION II: FURNACE MAINTENANCE  

 

The interior sections of the furnace must be cleaned and 
adjusted by a qualified service contractor once a year or before 
the start of each heating season. The following items must be 
checked: 
1.

 

The blower wheel and motor for excessive dirt. 

2.

 

The electric heaters for wear, damage or corrosion. 

3.

 

The electrical components for excessive dust, dirt, wear, 
or deterioration. 

4.

 

The supply air duct system for excessive dust, dirt or 
debris 

5.

 

The return air duct system for excessive dust, dirt or 
debris 

6.

 

All electrical wiring for wear, insulation cracks and/or 
damage. 

7.

 

Check the air conditioning evaporator coil for dust, debris 
or damage. 

8.

 

Check the evaporator coil drain pan for proper drainage to 
prevent water backup into the furnace. 

9.

 

The furnace casing and all interior sheet metal panels or 
dividers. 

 

Furnace Cleaning Procedure 

1.

 

Follow the instructions exactly as shown in Start Up and 
Shutdown Section in this manual to properly shutdown 
this appliance. 

2.

 

Remove the lower access door on the front of the furnace. 

3.

 

Remove the upper access door on the front of the 
evaporator coil compartment. 

4.

 

Remove all 6 screws on the control box cover and remove 
both covers. Refer to Figure 7. 

5.

 

Remove the two screws on the right side of the blower 
mounting plate and slide the blower out of the furnace. 
Refer to Figure 8. 

6.

 

Use a vacuum cleaner and a small brush to remove any 
dirt and debris from the blower compartment. 

7.

 

Check in the area below the blower compartment where 
the heater elements are located and remove any dust, dirt 
or debris from around the heater elements. Be careful not 
to damage the heater elements with the vacuum hose or 
the brush. 

 

Figure 7: Control Box Cover 

 

 

Figure 8: Blower Assembly and Mounting Screw Location 

 

8.

 

Check the blower wheel for dust and debris. Use the 
brush and the vacuum cleaner to remove any dust or 
debris from the wheel. Be careful not to move or 
accidentally remove the blower wheel balance weight 
located on the wheel blades. If the wheel weight is moved 
or removed, it will cause the blower wheel to vibrate. If 
the wheel is vibrating, you must replace it. 

9.

 

Check the blower motor for dust and debris. Be sure to 
clean the openings on the motor housing as these 
openings are used to cool the motor. If the dust, dirt or 
debris has not been removed from these openings it will 
cause the motor to run hotter than normal and will shorten 
the life of the motor. 

10.

 

Check and clean with the brush and vacuum cleaner any 
dust in the supply and return ducts as far as you can reach. 
If these ducts look like they have an excessive amount of 
dust, dirt or debris you should recommend to the home 
owner or user to call a professional to properly clean the 
duct system. 

11.

 

Check and clean any dust, dirt, or debris from all of the 
controls and all of the surfaces in the control box. If dust 
or dirt is left on the components they will operate at a 
much hotter temperature causing premature component 
failure. 

12.

 

Check the evaporator coil compartment for dirt, dust or 
debris and remove any that exists. 

13.

 

Check the evaporator condensate drain pan for any debris 
and ensure the pan is properly draining by pouring water 
into the drain to check it. 

14.

 

Remove any excess water that may have spilled from 
checking the evaporator condensate drain. 

FIRE HAZARD 

NEVER PLACE A JUMPER BETWEEN “R” & “W”  

 

Placing jumper wire between the RED and WHITE 
thermostat wires at the furnace in order to override the 
thermostat and energize the heater elements is an extremely 
dangerous practice that can result in damage to the 
thermostat, dangerous operation, serious injury, property 
damage and/or death. 

Содержание E30 SERIES

Страница 1: ...Torque Motor 14 9 Replacement Parts List 3 4 HP Constant Torque Motor 19 5 Blower Performance 3 4 HP Constant Torque Motor 15 CONTACT INFORMATION Contact us by mail Manufactured and Distributed by Mo...

Страница 2: ...block or obstruct air openings used for ventilation and cooling of the furnace electrical components 8 Refer to the furnace rating plate for the furnace model number for the operating specifications...

Страница 3: ...an The furnace s best friend is a qualified service technician If the unit gives any indication of improper operation call the service technician The service technician is allowed to perform the norma...

Страница 4: ...of the furnace to make sure there are no flammable materials in the area If you smell vapors of any kind DO NOT turn on the power to the furnace until vapors have been ventilated and removed from the...

Страница 5: ...s on the center shelf Refer to Figure 6 10 Push the upper door forward and tighten with the thumb screw until the door is secured to the cabinet Refer to Figure 6 11 Follow the instructions to Turn On...

Страница 6: ...ted as to how to clean and reinstall filters washable or replaceable filters for good preventive maintenance Care must be taken that the edges of the washable or replaceable filter are resting on the...

Страница 7: ...cause serious injury if clothing or body parts get caught in the moving part The manufacturer or distributer will not be responsible for any repairs due to improper parts changes improper maintenance...

Страница 8: ...trol Box Cover Figure 8 Blower Assembly and Mounting Screw Location 8 Check the blower wheel for dust and debris Use the brush and the vacuum cleaner to remove any dust or debris from the wheel Be car...

Страница 9: ...heating or cooling operation 9 Thermostat Y Circuit The thermostat Y circuit is used for cooling or high speed indoor fan operation When 24 VAC is placed on the thermostat Y circuit the 24 vac is sen...

Страница 10: ...heck all wiring connections especially on any of the components to ensure they are securely fastened If you have 240 VAC coming out of the control box circuit breakers and you have 24 VAC between the...

Страница 11: ...tactor check for 24 VAC between the A1 and A2 terminals If 24 VAC is present then replace the heater contactor L1 L2 T1 T2 A 1 A 2 Figure 11 Heater Contactor Terminal Designations Blower Motor FLA 1 3...

Страница 12: ...2 741 615 466 LO 764 689 586 507 460 399 332 MED LO 855 807 733 632 571 521 478 416 367 MEDIUM 990 923 878 825 741 672 628 574 520 440 MED HI 1085 1031 988 929 878 789 725 663 603 474 HI 1291 1247 120...

Страница 13: ...56 630 494 with Cabinet MEDIUM 1251 1216 1170 1134 1079 1045 1009 860 685 570 97 FLSB 27 MED HI 1450 1410 1380 1335 1303 1221 1139 1056 737 580 or 97 FLSF 27 HI 1549 1506 1457 1410 1335 1246 1165 1056...

Страница 14: ...1245 1137 1012 679 551 or 97 FLSF 39 HI 1570 1531 1488 1415 1344 1279 1170 1070 736 562 CFMwith Coil LO 851 813 759 708 618 555 523 458 394 362 98 8Z12W OP MED LO 1021 982 934 884 837 740 684 636 573...

Страница 15: ...4 1065 874 711 561 with Cabinet MEDIUM 1404 1350 1327 1294 1251 1211 1145 1005 718 535 97 FSOB 39 MED HI 1601 1538 1468 1400 1327 1241 1148 888 719 541 HI 1725 1613 1530 1442 1360 1283 1190 1088 739 5...

Страница 16: ...TON ACCESSORY BLOWER 86MH0025 3 4 HP PSC 5 TON ACCESSORY BLOWER 86MH0026 3 4 HP CONSTANT TORQUE 5 TON ACCESSORY BLOWER 86MH0027 21 1200 CFM BROKE DOWN COOLING COIL CABINET 97 FLSB 21 21 1600 CFM BROK...

Страница 17: ...019P R68AB0019P 6 HEATER CONTACTOR 2 R68AB0019P R68AB0019P R68AB0019P 7 TRANSFORMER R68AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 8 CIRCUIT BREAKER 1 R68BAD014 R68BAD016 R68BAD018 R68BAD...

Страница 18: ...HEATER CONTACTOR 2 R68AB0019P R68AB0019P R68AB0019P 7 TRANSFORMER R68AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 8 CIRCUIT BREAKER 1 R68BAD015 R68BAD017 R68BAD018 R68BAD015 R68BAD018 R68B...

Страница 19: ...AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 8 CIRCUIT BREAKER 1 R68BAD015 R68BAD017 R68BAD018 R68BAD015 R68BAD018 R68BAD018 9 CIRCUIT BREAKER 2 R68BAD014 R68BAD013 R68BAD017 10 LOW VOLTAGE TERMINAL...

Отзывы: