![Morso DB15 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/morso/db15/db15_installation-and-operating-instructions-manual_1836680005.webp)
DB15
INSTALLATION AND OPERATING INSTRUCTIONS
8
9
DB15
INSTALLATION AND OPERATING INSTRUCTIONS
PARTS AND ACCESSORIES
Standard Spare Parts for Morso DB15 Central Heating Stove
to be emitted from the chimney, especially when the fire is cold.
Use only VERY dry wood or smokeless fuels. Is the chimney high
enough and hot enough to generate the necessary 12Pa draught?
POOR HEAT OUTPUT:
This appliance is
very easily
capable of
producing the quoted heat outputs given suitable fuels and a
chimney capable of developing sufficient draught. Is the chimney
too short or becoming cool or damp? Is the fuel completely dry?
Have the central controls been set correctly? Is the building
sufficiently well insulated?
CONDENSATION
onto cool surfaces inside the stove can be
severe if fuel is in any way damp.
Use only very dry fuel.
It is vital
that the heating circuit is fitted with a device, such as a low-limit
thermostat, to minimise cold water circulating through the boiler.
SMOKE COMING INTO ROOM
A little smoke leaking into the
room during refuelling is normal, but fumes are poisonous and
recurrent smoke emission must NEVER be tolerated, causes
might be:
NEW STOVE: There is often a smell and sometimes visible fumes
as the paint cures. This normally stops after an hour or so.
INADEQUATE SEALS: Are all flue pipes and connectors
absolutely
gas-tight? Even the tiniest crack or gap can spoil the
draught. Does an inset appliances fully seal against the fireplace?
BLOCKED FLUEWAYS: Has soot and ash collected above the
inner back part of the firebox?
UNSUITABLE, BLOCKED OR UN-SWEPT CHIMNEY: The first
requirement for correct operation is a sound chimney. Check the
requirements earlier in this document and in any case of doubt
engage a professional sweep or chimney engineer.
POOR AIR SUPPLY: Lack of air to the fire is a common cause of
smoking and poor performance. Air supply problems may be
worse in certain wind conditions (often incorrectly ascribed to
'downdraught', which is in fact very rare), where air can be sucked
out of the room. The answer is to fit an air vent, as near to the fire
as possible, facing into the usual wind direction.
DOWNDRAUGHT: Wind can blow
down
a chimney if there is
something higher nearby such as a tree, hill or high building.
Fitting an anti-downdraught cowl to the chimney top can cure this.
Types which cannot be swept through are not recommended.
POOR CHIMNEY DRAUGHT- Chimney draught in use MUST be
at least 12Pa.
CHIMNEY FIRE:
In the rare event of deposits inside the chimney
igniting (roaring sound + dense smoke and sparks from the
chimney) immediately close the door, shut all air controls and call
the fire brigade. Prevent fires by using
very dry fuel
and having
your chimney swept regularly.
MAINTENANCE
MONTHLY
- Open the fire door and inspect the top flue passages.
Gain access for cleaning by using the tool to lift off the lid (B on the
diagram).
ANNUALLY- SWEEP THE CHIMNEY
The entire length of the
chimney from stove to outlet should be swept annually, more often
if smoky fuels are used.
NEW PARTS
Your stove has been extensively tested for safety -
please don't try to modify it and always obtain genuine spare parts
.
SURFACE FINISH
Wipe the stove body with a slightly damp cloth
when cool. NEVER use aerosol spray or wax near the hot fire –
they can ignite. Painted steel parts can be refurbished using
special spray paint.
Your stove generates
VERY
high temperatures. Eventually the
internal parts will require replacement . Help parts to last by:
●Using only recommend, very dry, fuels.
●Emptying the ash very regularly when using mineral fuel -never
allow it to touch the underside of the grate.
●Cleaning the flueways regularly.
●Avoiding 'over-firing'
PARTS AND ACCESSORIES
Standard Spare Parts for Morso DB15 Central Heating Stove
Part Number
a
Window
MOR0029
b
Front firebar
MOR0030
c
Riddling bar
MOR0031
d
Thermostat assembly
MOR0032
e
Roof brick, pair, with seals
MOR0033
f
Side Brick, pair, with seals
MOR0034
g
Mid Brick, with seals
MOR0035
h
Firebar, upper
MOR0036
k
Firebar, lower
MOR0037
m
Ashpan
MOR0038
Touch-up paint
MOR0039
Operating tool
MOR0040
Rope Seal kit
MOR0041
Mineral fibre seals between bricks
MOR0042
Morso UK Ltd, Unit 7, The I O Centre, Valley Drive, Rugby, Warwickshire, CV21 1TW UK
4
These stove designs are registered at the UK Patent Office, Design No 4030575 and others, and are protected by Copyright © and UK Design Right, Glyn Hughes 2006-2013.
Certain parts are UK Patent Applied For. This document printed 10/09/2013. We are always striving to improve these products and may change their specification without notice.
KEY
SPARE PART
PART NUMBER
A
WINDOW
MOR0029
B
FRONT FIREBAR
MOR0032
C
RIDDLING BAR
MOR0031
D
THERMOSTAT ASSEMBLY
MOR0032
E
ROOF BRICK, PAIR, WITH SEALS
MOR0033
F
SIDE BRICK, PAIR, WITH SEALS
MOR0034
G
MID BRICK, WITH SEALS
MOR0035
H
FIREBAR, UPPER
MOR0036
K
FIREBAR, LOWER
MOR0037
M
ASHPAN
MOR0038
TOUCH-UP PAINT
MOR0039
OPERATING TOOL
MOR0040
ROPE SEAL KIT
MOR0041
MINERAL FIBRE SEALS BETWEEN BRICKS
MOR0042
1. CONTROL THE
HEATING SYSTEM
Stove boilers control their
own water temperature
by an internal thermostat,
so controls such as time
clocks and thermostats
regulate flow through the
heating circuit, not
the boiler.
2. GUARD AGAINST
CONDENSATION!
Solid fuels contain water
which can condense on
cool boiler faces to cause
VERY rapid corrosion and
failure. Use very dry fuel
and always fit a device such
BOILER STOVE CENTRAL HEATING SYSTEMS
This is a rough guide to specifying and fitting central heating using a solid fuel boiler stove with
thermostatic control. It doesn’t cover every detail, which will need to be determined on-site by
a skilled heating engineer.
‘Wet’ solid fuel central heating systems use the same types of pipework (including microbore,
plastic) and heat emitters (radiators, underfloor, etc), as other fuels and they can likewise
come on in the morning, go off at night and regulate themselves. Systems must...
HEAT REQUIREMENT
CONTROLS
GET THE RIGHT SIZE HEATERS
Guesswork won’t do.
A preliminary estimate of heat
requirement for each room
can be got from the table here.
Example: A room 6m x 5m x
2.8m has volume of 84m³.
If it was a ground floor room
in the corner of a two-storey
house, in which the adjacent
rooms and the one above were
also heated, then 2 unheated
outsid 1 outside floor =
3 unheated faces.
If moderately insulated then
Your stove has a built-in
mechanical thermostat
to regulate its water
temperature. A tiny vial of
oil is fitted in the boiler.
As the boiler water gets
hotter, the oil expands
along a fine tube, moves
a bellow outward,moving
an arm, which closes off
air to the fuel and so slows
combustion. So, if the time
clock or room thermostat
determines that no heat
is needed, it stops the
circulating pump; without
BOILER STOVE CENTRAL HEATING SYSTEMS
This is a rough guide to specifying and fitting central heating using a solid fuel boiler stove with thermostatic control. It doesn't cover
every detail, which will need to be determined on-site by a skilled heating engineer.
'Wet' solid fuel central heating systems use the same types of pipework (including microbore, plastic) and heat emitters (radiators,
underfloor, etc), as other fuels and they can likewise come on in the morning, go off at night and regulate themselves. Systems must...
1: CONTROL THE HEATING SYSTEM.
Stove boilers control their own water temperature by an internal thermostat, so controls
such as time clocks and thermostats regulate flow through the heating circuit, not the boiler.
2: GUARD AGAINST CONDENSATION!
Solid fuels contain water which can condense on cool boiler faces to cause VERY rapid corrosion
and failure. Use
very
dry fuel and
always
fit a device such as a low-level thermostat to minimise cool water circulating through the boiler.
2: ALLOW FOR EXCESS HEAT.
The fire can close down automatically, but it can't
completely
stop combustion and output will vary
considerably during a fuelling cycle. There must be some infallible means of dissipating, and preferably storing, surplus heat, for instance a
hot water cylinder or a thermal store and always a system to run the central-heating pump if there is risk of boiling. Should thermostat and
pump fail together, there must be infallible provision to cool the system, or allow it to boil, for instance through an open vent. (The old-
fashioned idea of deliberately wasting heat through a permanent "heat leak" radiator not only throws heat away, it just will not suffice with
powerful modern stoves.)
HEAT REQUIREMENT
GET THE RIGHT SIZE HEATERS.
Guesswork won't do. A preliminary estimate of heat
requirement for each room can be got from the table here.
Example
: A room 6m x 5m x 2.8m
has volume of 84m³. If it was a ground floor room in the corner of a two-storey house, in
which the adjacent rooms and the one above were also heated, then 2 unheated outside
walls + 1 outside floor = 3 unheated faces. If moderately insulated then the factor in the table
is 40 Watts per m³, so 84m³ x 40 = 3360 Watts, or 3.36kW. A radiator, or radiators, emitting
at least 3.36kW should be specified.
Don't forget that, with boiler stoves, the room output and water output go up and down
together - turn the central heating down, and the whole stove goes cooler. It is usually wise to
fit a radiator (with thermostatic valve) in the fireplace room.
The actual value varies with the shape, exposure, draughtiness and temperatures. For larger
installations or whole-house heating, use the more accurate 'U-Value method - an online
heat-need calculator is available at
www.soliftec.com
.
APPROXIMATE HEAT REQUIREMENT OF ROOMS
Watts
per
Cubic Metre
Number of unheated faces
1
2
3
4
5
6
No effective insulation
eg: all-glass rooms with single glazing, barns, workshops, tents
120
132
145 158 170 183
Poor insulation
eg; single glazing, little loft insulation, uninsulated cavity walls, draughts
62
70
78
86
94 102
Moderate insulation
eg: thick solid walls, some loft insulation, some draught-proofing
31
35
40
44
48
53
Good Insulation
eg: some wall insulation, thick loft insulation, double glazing, draught-proofing
21
24
27
31
34
37
Best insulation
eg: properties built to 2008 UK standards
16
18
20
22
24
26
Watts (W) per cubic metre
CONTROLS
Your stove has a built-in
mechanical thermostat to
regulate
its
water
temperature. A tiny vial of oil
is fitted in the boiler. As the
boiler water gets hotter, the
oil expands along a fine tube,
moves a bellow outward,
moving an arm, which closes
off air to the fuel and so
slows combustion. So, if the timeclock or room thermostat determines
that no heat is needed, it stops the circulating pump; without water
circulation the boiler begins to get too hot, the oil expands, shuts off
air and the fire dies down. If there is demand for heat, for instance in
the morning, the pump comes on, colder water enters the boiler, the
air-flap opens and the fire blazes up.
The control dial on the stove does not directly turn the stove up and
down, it sets the water temperature at which the thermostat will begin
to shut the fire down.
We recommend a control system regulating the central-heating pump through (1) a single-channel time clock, (2) a centrally-located
room thermostat (not in the stove room) and (3) thermostatic radiator valves on all but one radiator. A low-level (about 50°C) pipe
thermostat to prevent pumped circulation of cool water (which can cause condensation, rust, and deplete stored hot water) and a high
level one (about 90°C) to override controls and run the heating circuit to dissipate heat if there is a risk of boiling. Stored hot water for
taps is not controlled, but accumulates during normal operation, especially during periods while central heating is not required.
1
Copyright © and UK Design Right, Glyn Hughes 2006-2013.
'Teddington' thermostat
(Normal cold '0' setting - about 7mm open)
Typical wiring layout through connector block (return dotted)
Room and boiler outputs vary together
the factor in the table is 40 Watts
per m³, so 84m³ x 40 = 3360 Watts,
or 3.36kW. A radiator, or
radiators, emitting at least
3.36kW should be specified.
Don’t forget that, with boiler
stoves, the room output and
water output go up and down
together - turn the central
heating down, and the whole
stove goes cooler.
It is usually wise to fit a
radiator (with thermostatic
valve) in the fireplace room.
The actual value varies
as a low-level thermostat
to minimise cool water
circulating through the boiler.
3. ALLOW FOR
EXCESS HEAT
The fire can close down
automatically, but it can’t
completely stop combustion
and output will vary considerably
during a fuelling cycle.
There must be some infallible
means of dissipating, and
preferably storing, surplus
heat, for instance a hot
water cylinder or a thermal
store and always a system
to run the central-heating
pump if there is risk of
boiling. Should thermostat
and pump fail together,
there must be infallible
provision to cool the system,
or allow it to boil, for
instance through an open
vent.
(The old-fashioned idea of
deliberately wasting heat
through a permanent “heat
leak” radiator not only
throws heat away, it just
will not suffice with powerful
modern stoves.)
APPROXIMATE HEAT REQUIREMENT OF ROOMS
Watts per Cubic Metre
NUMBER OF UNHEATED FACES
1
2
3
4
5
6
INSULA
TION
No effective insulation eg: all-glass rooms with single
glazing, barns, workshops, tents
120
132
145
158
170
183
Poor insulation eg; single glazing, little loft insulation,
uninsulated cavity walls, draughts
62
70
78
86
94
102
Moderate insulation eg: thick solid walls, some loft insulation,
some draught-proofing
31
35
40
44
48
53
Good Insulation eg: some wall insulation, thick loft insulation,
double glazing, draught-proofing
21
24
27
31
34
37
Best insulation eg: properties built to 2008 UK standards
16
18
20
22
24
26
WATTS (W) PER CUBIC METRE
water circulation the boiler
begins to get too hot, the oil
expands, shuts off air and
the fire dies down. If there
is demand for heat, for instance
in the morning, the pump
comes on, colder water
enters the boiler, the air-flap
opens and the fire blazes up.
The control dial on the stove
does not directly turn the
stove up and down, it sets
the water temperature at
which the thermostat will
begin to shut the fire down.
We recommend a control
system regulating the
central-heating pump
through (1) a single-channel
time clock, (2) a centrally-
located room thermostat
(not in the stove room) and
(3) thermostatic radiator
valves on all but one
radiator. A low-level (about
50°C) pipe thermostat to
prevent pumped circulation
of cool water (which can
cause condensation, rust,
and deplete stored hot
water) and a high level one
with the shape, exposure,
draughtiness and temperatures.
For larger installations or
whole-house heating, use
the more accurate ‘U-Value
method - an online heat-need
calculator is available at
www.soliftec.com.