Morrison Bros. co. 918AC Series Скачать руководство пользователя страница 4

4

Morrison Bros. Co.  ‑  Dubuque, IA  ‑  800‑553‑4840

918AC‑0160 PP

Rev. 09-27-2022

5. Place the DIP switch Position Two in the “ON” position to configure the Motherboard to reset the channel 

2 relay output when the auto-timeout timer has expired. Place the DIP switch Position Two in the “OFF” 

position to prevent the auto-timeout timer from changing the state of the channel 2 relay output.

6. Place the DIP switch Position Three in the “ON” position to configure the Motherboard to reset the channel 

3 relay output when the auto-timeout timer has expired. Place the DIP switch Position Three in the “OFF” 

position to prevent the auto-timeout timer from changing the state of the channel 3 relay output.

7. Place the DIP switch Position Four in the “ON” position to configure the Motherboard to reset the channel 

4 relay output when the auto-timeout timer has expired. Place the DIP switch Position Four in the “OFF” 

position to prevent the auto-timeout timer from changing the state of the channel 4 relay output.

8. Locate the reset push button on the expansion board mezzanine.

9. Press and release the reset push button to complete the configuration of the Auto-Timeout relay output 

settings.

Latching Mode Output Function

The relay output Latching Mode allows the relay output to be latched during an active alarm and remain 

latched until a configurable reset condition occurs. The Latching Modes can only be configured for relay output 

channels 1 and 2. See the ‘Output Modules’ section on page 8 for details on configuring the outputs to be 

triggered by input channel alarms.

NOTE: 

The Latching Mode function takes precedence over the Non-Persistent and Auto-Timeout functions. 

Channel 1 Latching Mode Channel 2 Latching Mode

Disabled

Disabled

Reset by Input 2

Reset by Input 1

Reset by Input 3

Reset by Input 3

Reset by Input 4

Reset by Input 4

Содержание 918AC Series

Страница 1: ...cendie ou d explosion des blessures graves ou la mort Contents Installation 1 Steps to Configure the 918AC Series System Interface Motherboard 2 Non Persist Output Function 2 Auto Timeout Output Funct...

Страница 2: ...elay output when the triggering alarm condition s have been acknowledged Place the DIP switch Position One in the OFF position to prevent the alarm acknowledgement from changing the state of the chann...

Страница 3: ...re 3 Auto Timeout Relay Output Configuration 1 Locate the rotary switch Timeout Value SW 4 on the expansion board mezzanine see Figure 3 2 Use a small screwdriver to turn the rotary dial to the desire...

Страница 4: ...the auto timeout timer has expired Place the DIP switch Position Four in the OFF position to prevent the auto timeout timer from changing the state of the channel 4 relay output 8 Locate the reset pu...

Страница 5: ...and configure the channel 4 input as the reset condition place DIP switch Position One and Two the ON positions 3 Use DIP switch Positions Three and Four to set the Latching Mode for the channel 2 rel...

Страница 6: ...nel 2 3 Channel 3 Channel 3 4 Channel 4 Channel 4 Table 2 Expansion board SW2 Output Auto Timeout Position Setting ON This output channel relay will be reset to its normal condition when the auto time...

Страница 7: ...OFF Channel 1 Latching Mode Enabled Input 2 Reset OFF ON Channel 1 Latching Mode Enabled Input 3 Reset ON ON Channel 1 Latching Mode Enabled Input 4 Reset Position Setting 3 4 OFF OFF Channel 2 Latch...

Отзывы: