
M200-01-00
2
CAUTION
Dust covers provide limited protection against airborne dust
particles during shipping. Dust covers must be removed
before the sensors can sense smoke. Remove sensors prior
to heavy remodeling or construction.
Testing
Before testing, notify the proper authorities that the system
is undergoing maintenance, and will temporarily be out of
service. Disable the system to prevent unwanted alarms.
All sensors must be tested after installation and periodi-
cally thereafter. Testing methods must satisfy the Authority
Having Jurisdiction (AHJ). Sensors offer maximum perfor-
mance when tested and maintained in compliance with
EN54 and applicable local codes.
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
This sensor can be functionally tested with a test mag-
net. The test magnet electronically simulates smoke in
the sensing chamber, testing the sensor electronics and
connections to the control panel.
1. Hold the test magnet in the magnet test area as shown
in Figure 3.
2. The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel
to indicate sensor status. Coded signals, transmitted
from the panel, can cause the LEDs to blink, latch
on, or latch off. Refer to the control panel technical
documentation for sensor LED status operation and
expected delay to alarm.
C0100-00
3
2
1
3
2
1
+
–
–
+
OPTIONAL RETURN LOOP
REMOTE ANNUNCIATOR
+
–
B. Smoke Entry: Aerosol Generator (Gemini 501)
The GEMINI model 501 aerosol generator can be used
for smoke entry testing. Set the generator to represent
4%/ft. to 5%/ft. obstruction as described in the GEMINI
501 manual. Using the bowl shaped applicator, apply
aerosol until the panel alarms.
A sensor that fails any of these tests should be cleaned
as described under
CLEANING
, and retested. If the
sensor fails after cleaning, it must be replaced and returned
for repair.
When testing is complete, restore the system to nor-
mal operation and notify the proper authorities that the
system is back in operation.
Figure 1. Wiring diagram:
3
I56-2155-003R
C0169-00
C0170-00
Cleaning
It is recommended that the detector be removed from
its mounting base to facilitate cleaning. The detector is
cleaned as follows:
NOTE:
Before removing the detector, notify the proper
authorities that the smoke detector system is
undergoing maintenance and will be temporarily
out of service. Disable the zone or system undergo-
ing maintenance to prevent unwanted alarms.
1. Remove the detector cover by prying away the four
side tabs with a small-bladed screwdriver, and then
pulling the cover from the base.
2. Vacuum the screen carefully without removing it. If
further cleaning is required continue with Step 3, oth-
erwise skip to Step 7.
3. Remove the screen/chamber cover assembly by pull-
ing it straight out (see Figure 4).
4. Clean the chamber by vacuuming or blowing out dust
and particles.
5. Replace the sensing chamber cover, aligning the arrow
on the top with arrow on the printed circuit board.
6. To replace the screen, place it over the chamber
assembly, turning it until it snaps into place.
7. Replace the cover using the LEDs to align the cover
and then gently pushing it until it locks into place.
8. Reinstall the detector.
9. Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back
on line.
C0146-00
Figure 2. Rotary decade address switches:
Figure 3. Test magnet position:
tenS
oneS
9
8
7
6
5
4
3
2
1 0
9
8
7
6
5
4
3
2
1 0
D
N
T
N
I
A P
T
O
O
LED STATUS
INDICATORS
TES
T
MAGNET
PAINTED
SURFACE
PAINTED
SURFACE
TEST
MAGNET
MAGNET TEST
MARKER
Figure 4. Sensor assembly:
CAUTION
Do not loop wire under terminal 1 or 2. Break
wire run to provide supervision of connection.
SenSInG
cHaMBer
Screen
aSSeMBlY
SenSor
coVer
coVer reMoVal
taBS
control
p
anel