TROUBLESHOOTING AND CORRECTIVE MEASURES FOR THE SENSOR FUNCTION

Sensor function 

gives no water

Transformer fault set, AC not 
selected and activated on the 
circuit board.  

The water is shut off
Poor or batteries turned the 
wrong way

Sensor distance too short 
The solenoid valve is not 
working

Dirt in the solenoid valve

Inlet filter clogged

Fault in the electronics

Check that the transformer is set to 12V. And 
that the circuit board has AC selected.

Check the water connection
Check the batteries, 4 ea R6 á 1.5 volt, which 
must be mounted according to the instructions 
in the battery compartment
Try moving your hand closer to the sensor eyes
Activate the sensor eyes and listen for a click-
ing sound

see above

Examine the inlet filter mounted between the 
solenoid valve and valve block
Conduct a ”self-test” as described above

Set the Transformer to 12V. Select AC. 
Press RESET.

Open any shut offs
Replace batteries, or correct the position 
of the battery. NOTE: Use alkaline bat-
teries!
Adjust the sensor gap
If you hear no sound: Replace the 
solenoid coil or if necessary the entire 
solenoid valve
If you hear a clicking sound - clean the 
solenoid valve or replace the membrane 
disk, see figure below
Clean the inlet filter

Replace the sensor eyes or circuit board

POSSIBLE CAUSE

TROUBLESHOOTING

CORRECTIVE MEASURE

PROBLEMS

The tap will not 

turn off

Before additional tests can be made, establish whether the fault is electrical or mechanical by disconnecting the batteries. 
If the tap shuts off with disconnected current, the fault is electrical. If the tap continues to run there is a mechanical fault.
Mechanical fault - dirt in the 
solenoid valve

Electrical fault - the elec-
tronics prevent the solenoid 
valve from shutting off

-

Conduct a ”self-test” as described above

Dismantle the solenoid valve for clea-
ning, see figure below

Replace the sensor eyes or circuit board

Dirt in the solenoid valve, or 
leaky membrane disk

Screw apart the solenoid valve and look for dirt 
and check the membrane disk

Clean and where necessary replace the 
membrane disk, see figure below

The tap is dripping

The sensor distance is too far -

Adjust the sensor distance to about 5 
cm in front of the sensor eyes

The tap opens/

shuts off con-

stantly

The sensor eyes are defective The sensor distance setting is not reacting

Replace the sensor eyes

Normal function

When activating the sensor function, a red flashing light is to be visible on the indication lamp (under the sensor eyes) just when the flow 
starts.

Test:

MoraTemp Duo has a built-in function for self-testing in the electronics unit. This is what you do: Open the control box cover and pull out the 
circuit board. Press the ”RESET” button briefly. The result should then be a red flashing light both from the indication lamp on the tap and from 
the circuit board, a clicking sound from the solenoid valve and the tap should open. Then a green flashing light on the circuit board, clicking 
from the solenoid valve, the tap shuts off, then two red flashes from the indication lamp and on the circuit board. This test confirms that the 
electronics are OK.

Clean the 
holes when 
necessary

Membrane 
disk

Maintenance and cleaning

The maintenance normally required involves, for the most part, keeping the sensor 
eyes clean. Use no abrasive cleaning agent or strong substances that might 
damage the lenses. If the water contains a lot of particles and dirt, you might 
sometimes need to remove and clean the solenoid valve’s water affected parts, 
and the dirt filter that is fitted between the valve block and solenoid valve. Be 
particularly careful with the small holes in the membrane disk and the surfaces 
to which they seal.
Strong sunlight aimed directly at the sensor eyes may also disturb the function. 
The interval between battery replacement varies a lot, but for normal use working 
life should be year or so. 
Always use alkaline batteries for best performance.

When assem-
bling check 
that this hole is 
correctly aligned 
with the cor-
responding hole 
on the solenoid 
valve.

Reset to AC but 

nothing is working 

4

  07.04. MA nr 1001032 

INSTRUCTION

Содержание Temp Duo 72 20 00

Страница 1: ...cuit board and put back the cover On AC operation select AC instead of DC on the circuit board reset the transformer to 12V operation Connect to circuit board Press RESET 3 Connect the valve block to the mixer s connection pipe remember the sup port sleeves in the connection pipe and to incoming hot and cold water If the mixer has an outlet for connecting a dishwasher connect the dishwasher s conn...

Страница 2: ... tap sensor eyes Contact for connection to solenoid valve blue orange cable Indicationlamp green Indicationlamp red Change over switch between battery and mains Mode DC battery operation Name MA nr Control box 72 93 43 Circuit board 72 93 42 Sensor eyes with cable 72 93 18 Valve block 72 93 24 Solenoid coil 72 93 46 Connection hose 70 97 17 Membrane disk 72 92 27 Transformer for mains 72 92 30 Cab...

Страница 3: ...from the hot water side On the hot water side the cold water plug must be fitted included To do this you only need a 3mm Allen key When the plug has been fitted the tap will always give 100 cold water during sensor operation The function of the mixer valve has been totally blocked and the water that the tap now produces during sensor operation can be used as drinking water and for food preparation...

Страница 4: ...ew apart the solenoid valve and look for dirt and check the membrane disk Clean and where necessary replace the membrane disk see figure below The tap is dripping The sensor distance is too far Adjust the sensor distance to about 5 cm in front of the sensor eyes The tap opens shuts off con stantly The sensor eyes are defective The sensor distance setting is not reacting Replace the sensor eyes Nor...

Отзывы: