  •  For the best shielding, the shield should be run all   
     the way from the signal source to the receiving  
     device.  (see Note below)

  •  The maximum length of unshielded input and   
     output signal wiring should be 2 inches.

Note: 

Some of Moore Industries’ instruments can be 

classifi ed as receivers (IPT

2

, IPX

2

, etc.) and some can 

be classifi ed as transmitters (TRX, TRY, etc.) while 

some are both a receiver and a transmitter (SPA

2

HIM, etc).  Hence, your shield ground connections 

should be appropriate for the type of signal line being 

shielded.  The shield should be grounded at the 

receiver and not at the signal source.

CE Conformity

Installation of any Moore Industries’ products that
carry the CE marking must adhere to the
guidelines in the Recommended Ground Wiring
Practices section in order to meet the EN 61326
requirements set forth in the applicable EMC 
directive.

19mm

(0.78 in)

FRONT VIEW

13mm

(0.54 in)

96mm

(3.80 in)

85mm

(3.375 in) 

8mm 

(0.32 in)

SIDE VIEW

10mm

(0.395 in)

Rear Access Location for 

Pneumatic Connections, 
1/8 NPT Used in options:

-FA2, -FA4, -FA6, and -FA12 

123mm

(4.83 in)

12mm

(0.45 in)

Bottom Access Location for 

Pneumatic Connections, 
1/8 NPT Used in options:

-FA1, -FA3, -FA5, and -FA11 

Red LED "ON" 

When Input 

Current is Present

Electrical Test Jack & LED

for 2mm (0.8 in) Dia. 

Phone Tip Plug Used in:

-FA3, -FA4, -FA8, -FA10,

-FA11 and -FA12

IPT

CURRENT/PRE

SS

URE

TRAN

S

MITTER

 +IN      –IN 

SPAN

ZERO

39mm

(1.54 in)

2

Zero Adj.

Span Adj.

+T

–T

Pneumatic Test Jack
Used in options:
-FA3, -FA4, -FA8, 
-FA10, -FA11 
and -FA12 

Mounting Block

Used in options:

-FA7, -FA8, -FA9, and -FA10 

LED & Current 

Test Jacks 

Yes 

Yes 
Yes 
Yes 

None 
None 

Yes 
Yes 

None 
None 
None 
None

Electrical Input 

Location  

Front 

Front 
Front 
Front 
Front 
Front 
Front 
Front 
Front 
Front 
Front 
Front

Pneumatic Output 

Supply Location 

Bottom 

Rear 

Bottom 

Rear 

Bottom 

Rear 

No mounting block 
No mounting block 
No mounting block 
No mounting block 

Bottom 

Rear

Pneumatic Test 

Jack Location

 

None 

None

Front 
Front 

None
None 
None 

Front 

None 

Front 
Front 
Front

 

Option

 

  

–FA1 
–FA2 
–FA3 
–FA4 
–FA5 
–FA6 
–FA7 
–FA8 
–FA9 

–FA10 
–FA11 
–FA12

Pneumatic Connections

Supply air must be clean, dry instrument air.  It is 
recommended that all particles larger than 1 micron 
be removed.  Use of ¼-inch tubing allows suffi  cient 
air for one unit.  When using RIR or SIR headers, 
up to 30 IPT

2

s may be run from a ¾-inch NPT pipe 

without degrading performance, provided the air 
supply pressure is suffi  cient.  Output tubing should 
be ¼-inch, though larger tubing may be desirable for 
exceptionally long runs.  Purge the output tubing and 
the controlled device before connecting to the IPT

2

 or 

RIR/SIR.

Caution:

Output air cycles back through the IPT 

2

.  

Contamination in the output line or controlled 

device may easily enter and damage the IPT 

2

.

Figure 4.  

Mounting Dimensions

Содержание IPT2

Страница 1: ...IPT2 IPT 2 July 2016 170 730 00G Current to Pressure I P Transmitter All product names are registered trademarks of their respective companies Current to Pressure I P Transmitter...

Страница 2: ...Information 5 Application Information 6 Calibration 7 Adjustments 7 Calibration Equipment 7 Test Jacks 8 Calibration Setup 8 Calibration Procedure 8 Installation 9 Mounting 9 Installation in Hazardou...

Страница 3: ...r documentation is missing this number is used to identify equipment characteristics The model number for the IPT2 is located on a label on the side of the unit Serial Number Moore Industries maintain...

Страница 4: ...FA11 FA12 See Table 1 for more information Housing DIN Aluminum DIN style housing assembly WTI Rain proof as de ned by NEMA 3R FA7 or FA8 required WTIP Rain proof as de ned by NEMA 3R with plate and...

Страница 5: ...on temperature pressure and the relative humidity of the air Su cient water must be removed to lower the dew point of the air to a temperature below ambient The dew point at line pressure is expressed...

Страница 6: ...on to prevent oil contamination of the desiccant as well as downstream ltration to prevent desiccant nes from introducing new contamination The service life of an IPT2 is directly proportional to the...

Страница 7: ...he wiper stop Usually a slight change can be felt when the clutch is at the end of a range i e it is slipping However if this change is not felt either end can be reached by turning the shaft 15 turns...

Страница 8: ...illustration of a typical calibration setup including optional equipment To check or calibrate the IPT2 connect the unit as shown in this illustration Calibration Procedure There are two options show...

Страница 9: ...the unit into place until the retaining lever snaps up ush be neath the handle To remove an IPT2 press down on the retaining lever and lift the unit out by the handle Note Check valves in the headers...

Страница 10: ...be used when the IPT2 is installed in a Class I Division 2 location Australia New Zealand ANZEx Installations Certi cate No ANZEx 09 3000X Nonincendive Type n application Ex n Marking Code Ex n IIC T6...

Страница 11: ...D for 2mm 0 8 in Dia Phone Tip Plug Used in FA3 FA4 FA8 FA10 FA11 and FA12 IPT CURRENT PRESSURE TRANSMITTER IN IN SPAN ZERO 39mm 1 54 in 2 Zero Adj Span Adj T T Pneumatic Test Jack Used in options FA3...

Страница 12: ...ibed in the Maintenance section Operation Reverse output operation Once adjusted and installed the IPT2 operates unattended except for occasional cleaning of the air supply lters If a malfunction is i...

Страница 13: ...ly and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall no...

Отзывы: