Mooney Flowgrid Скачать руководство пользователя страница 13

Flowgrid Regulator |  13

Standby Monitor

Working Monitor

 

1.   Purge station and open outlet valve or vent to allow flow 

through the station. 

2.   Set pilot (#3) to a high setting above desired setpoint.

3.   Set pilot (#1) to a high setting above desired setpoint.

4.   Set the Monitor pilot (#2) at a zero setting.

5.   Set restrictor on Pilot (#1) at an intermediate opening (a 

“4” setting on the Mooney Type 24 Restrictor).

6.   Slowly open the inlet block valve to station. The 1st Stage 

Regulator should remain closed as a result of the Monitor 
Pilot (#2) being set to zero.

7.   Increase the setting of the Monitor Pilot (#2) to the 

desired pressure setting. If the valve is unstable, increase 
the restrictor opening until it becomes stable

 8.   Lower the setpoint of the 2nd stage regulator (Pilot #3) to 

the desired outlet pressure setting. Tune the restrictor on 
Pilot (#3) at this time. The 1st stage regulator should open 
or begin to control the interstage pressure at the setpoint 
of Pilot (#1).

9.   Adjust the setpoint of Pilot (#1) to achieve the desired 

Interstage pressure. Tune the restrictor on Pilot (#1) at this 
time.

10.  Raise the setpoint of Pilot (#3) to verify the setpoint of the 

Monitor Pilot (#2). Adjust if necessary. Check for system 
stability and adjust the restrictor on Pilot (#1) if required.

11.  Return setpoint of Pilot (#3) to maintain the desired outlet 

pressure.. 

 Figure 10. Working Monitor Schematic

 NOTE: In a working Monitor system with less than 25 psig differential across the second stage 
regulator the pilot supply may be connected to the piping upstream of the first stage regulator. 
This will improve the shutoff of the second stage regulator.

 Maintenance

 Regulator parts are subject to normal wear and must be 
inspected and replaced as necessary. The frequency of 
inspection and replacement of parts depends on severity 
of service conditions or the requirements of local, state, 
and federal regulations. Be certain that the name plates are 
updated to accurately indicate any field changes in equipment, 
materials, service conditions, or pressure settings.

 Before disassembly make sure the regulator has been isolated 
from the process by closing block valves on the inlet and outlet 
sides of the regulator. Safely release pressure and process 
fluid from body and pilot system. Failure to complete these 
steps can result in personal injury and property damage.

Содержание Flowgrid

Страница 1: ...y or redundancy Non stretching fabric reinforced diaphragm for stability and fast response at all temperatures Positive spring shutoff Two stage pressure drop to minimize noise and provide cavitation...

Страница 2: ...ng spring case Table 1 Table 2 Figure 1 The throttle plate 2 supports the diaphragm and provides a machined surface that the diaphragm seals against for bubble tight shutoff Restricted capacity plates...

Страница 3: ...et side of the valve 8 The Capacity tag indicates the capacity of the throttle plate 100 75 50 35 in the valve NOTE On all 1 valves and 2 standard valves the throttle plate itself is stamped Item Defi...

Страница 4: ...ng the pressure above the diaphragm allows the inlet pressure to progressively lift the diaphragm off the throttle plate opening the valve and satisfying the demand for flow in the downstream system R...

Страница 5: ...MSS SP 61 standards If it is necessary to retest the valve follow one of the procedures listed below to prevent damage to the diaphragm OPTION 1 1 Disconnect and remove all control line s and the pil...

Страница 6: ...alled in confined or enclosed spaces should be provided with adequate ventilation to prevent the possibility of gas buildup or accumulation from leaks and venting Leaks or vented gas may accumulate ca...

Страница 7: ...ent valves and gauge connections are recommended in the inlet and outlet piping to the Flowgrid valve A gauge connection may be installed on the loading pressure connection to the Spring Case of the F...

Страница 8: ...outlet connection on Type 30 Filter to Type 24 Restrictor inlet 3 Type 24 Restrictor mounted to Tee connection 3A Type 24 Restrictor mounted to Inlet port of Series 20 Pilot 4 Tee mounted to Inlet Por...

Страница 9: ...alve 5 Sense line connecting Sense port on Series 20 Pilot to downstream piping 6 Outlet port of Series 20 Pilot connected to Outlet connection of Flowgrid valve 6A Outlet port of Series 20 Pilot conn...

Страница 10: ...2 is plugged 10 Pilot cartridges in PRV mode 2nd Stage Regulator 11 Filter supply connected from inlet connection on valve body to Type 30 Filter inlet 12 Pilot supply from outlet connection on Type 3...

Страница 11: ...d 9 Slowly close the downstream block valve or vent to check the Flowgrid valve for lockup shut off 10 Slowly open the downstream block valve Back Pressure Regulator or Relief Valve 1 Adjust the pilot...

Страница 12: ...n the set point of the Operating Regulator becomes less than the set point of the Monitor regula tor the interstage pressure will drop from approximately full inlet pressure to 5 10 PSI above the outl...

Страница 13: ...t this time 10 Raise the setpoint of Pilot 3 to verify the setpoint of the Monitor Pilot 2 Adjust if necessary Check for system stability and adjust the restrictor on Pilot 1 if required 11 Return set...

Страница 14: ...sharp metal tools The bottom of the groove must have a smooth finish to prevent leakage The mating surface of adjacent parts must also be smooth to prevent leakage Assembly NOTE Do not lubricate diap...

Страница 15: ...e sense line to a new location often solves control problems 4 Check to make sure needle valves are not used on any pilot system connections Full opening type valves are recommended 5 Check for pilot...

Страница 16: ...O REPRE SENTATION OR WARRANTY OF ANY KIND EXPRESS OR IMPLIED AS TO MERCHANTABILITY FITNESS FOR PARTICULAR PURPOSE OR ANY OTHER MATTER WITH RESPECT TO ANY OF THE PRODUCTS While the information in this...

Отзывы: