11.6.33 Error 34: Powerfail funkction error
11.6.33.1 Error 34-0 (emergency code 3220h)
Cause: Power fail detected and reaction active
Suggested steps:
Check net connection of servo
An under-voltage occurred
on the drive while this axis
was switched on.
l
Power supply was possibly switched off.
l
Please check if the actual grid voltage matches
the supply setting (parameter PST_
VoltageSupply)
l
Verify that the grid is stable under load
condition.
11.6.33.2 Error 34-1 (emergency code 3220h)
Cause: Returning DC-link voltage detected
Suggested steps:
Restart Device
An under-voltage occurred
on the drive while this axis
was switched on.
l
Power supply was possibly switched off.
l
Please check if the actual grid voltage matches
the supply setting (parameter PST_
VoltageSupply)
l
Verify that the grid is stable under load
condition.
MOOG
ID No.: CB40859-001 Date: 11/2020
MSD Servo Drive - Device Help
406
11 Alarms & warnings
11.6.33.3 Error 34-2 (emergency code 3220h)
Cause: Power fail initialization failed
Suggested steps:
Check power fail parameter settings
This issue is probably
caused by an unsuitable
parameter setting.
l
Save your parameter set for a later restore.
l
See 'history of parameter changes' and undo
the latest changes.
l
Please check your parameter set for
implausible settings.
l
Please set device to factory setting, restart, and
see if the error occurs again.
l
When reporting this error to your service
partner, please include your device's
parameter setting.