background image

Page 5 of 6: C70861 Rev A – 01.09

18 Specifications

Function:

P, 

I

, or P & 

I

, switch selectable

Input 1:

Scaled to 95V max with switch
selectable lag of 55mS.

Input 2:

Switch selectable.
4-20mA 240R load, for 0 to +10V on R34.
Or 0 to ±10V direct onto R34.
R34 is plug-in, 100K nominal.

Input 3:

R33 plug-in. ±10V gives ±100% valve
drive when R33 = 10k Ohm, ±10% when
R33 = 100k Ohm.

Feedback input:

Differential 4-20mA or ±10V, switch
selectable
±15V max.
R in 100k –  ±10V
R in 240R – 4-20mA

Feedback amp:

Zero, ±10V.
Gain, 1 to 10.
Derivative (velocity) feedback via
plug-in resistor R16 and fixed capacitor.

Transducer excitation:

+10V @ 10mA max. 

Error amp:

Unity gain.
Bias ±1.5V. 

Proportional amp gain:

1 to 20.

Integrator gain:

1 to 45 per second.

Integrator input:

Switch selectable from output of unity
gain error amp or proportional gain amp

Enable: 

Relay, +24V @ 8mA, 17 to 32V.

Output amp:

Switch selectable voltage or current, single
ended output, return to ground.
V.  ±10V, minimum load = 200 Ohm

I

.  ±5, 10, 20, 30, 50mA to a maximum

of ±100mA

max load =

11V    – 39   Ohm

I

(Amp)

Step push button:

-50% valve drive disturbance.

Valve supply:

Terminal 23, 300mA max.

In position:

±10% of valve drive. 20mA and 40V max
output to PLC.

Front panel

Vs, internal supply – green

indicators:

Valve drive positive – red

negative – green

Enable – yellow
In position – green

Front panel

Valve ±10V (regardless of output

test points:

signal selection)
Feedback amplifier output
signal 0V

Front panel

Input 1 scale

trimpots:

Error amp bias

(15 turns)

P gain

I

gain

Dither level
Feedback amp gain
Feedback amp zero

(

)

Dither:

200 Hz fixed frequency.
±10% valve drive. Switch selectable
on/off

Supply:

Terminal 1,
24V nominal, 22 to 28V
75mA @ 24V, no valve current,
200mA @ 100mA valve current

±15V output:

Terminals 14 and 15,
± (110mA – max valve current)

Wire size range:

0.2mm

2

to 2.5mm

2

(24AWG to 12AWG)

Recommended

M205, 250mA T (slow blow) fuse

supply protection:

compliant to IEC127-2 sheet 3

Mounting:

DIN rail
IP 20

Temperature:

0 to +40ºC

Dimensions:

100W x 108H x 45D

Weight:

180g

CE mark:

EN50081.1 emission
EN61000-6-2 immunity

C tick:

AS4251.1 emission

19 Internet

www.moog.com/dinmodules

Отзывы: