13
Installation
XG0231 - 061120
H2
H1
V
D
H
V
This section applies to installations where the shortest possible vent
run is through the wall. Refer to Appendix A - Power Vent locations,
to ensure the planned Power vent location is acceptable. Refer to the
table below for vent run requirements. Please note, images are shown
without screens for clarity purposes. However, your fireplace should
not be operated without proper installation of screens.
Figure 6.d
Straight Horizontal, Top Vent, Wall mounted power vent.
Figure 6.f
Multi-Elbow, Top Vent, Wall mounted power vent.
Figure 6.g
Multi-Elbow with downward vent run, Top Vent, Wall mounted power vent.
Multi-Elbow Installations
Downward Vertical Venting
V1
V1
V1
D = 6' Max
V2
H1
H1
H1
H2
H2
V3
Section 3-3: Installing a Wall Mounted Vent System
Selection of components and details of venting lay out should
adhere to the following guidelines:
Ensure the maximum vent run does not exceed 100’
Ensure the number of 90° elbows does not exceed 6
Ensure the number of 45° elbows does not exceed 12
One Elbow Layout
MAX V1+H1+
V2+H2+V3+H3
Max. #
Elbows
R320ST, R420ST
100'
6
R520ST, R620ST
100'
6
MAX V1+H1+
D+H2+V3
Max. #
Elbows
R320ST, R420ST
40'
6
R520ST, R620ST
40'
6
MAX V1+H1
Max. #
Elbows
R320ST, R420ST
100'
6
R520ST, R620ST
100'
6