background image

PVHEX58-300 & PVHEX510-300 Horizontal Power Vent

Appendix B: State of Massachusetts

Amendment

 (Gas Fireplace / Equipment sold in the State of Massachusetts)

 5.08: Modifications to NFPA-54, Chapter 10

 

(1) Revise NFPA-54 section 10.5.4.2

 

by adding a second exception as follows:

Existing chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manually reset device 

that will automatically shut off the gas to the burner in the event of a sustained back-draft

.

 

(2) Revise 10.8.3

 by 

adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, 

including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in 

the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 

 

1. INSTALLATION OF CARBON MONOXIDE DETECTORS.

 

At the time of installation of the side wall horizontal vented gas fueled equip-

ment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor 

level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon 

monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled 

equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon 

monoxide detectors

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with 

alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days 

to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm 

shall be installed.

 

2. APPROVED CARBON MONOXIDE DETECTORS.

 

Each carbon monoxide detector as required in accordance with the above provisions 

shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified. 

 

3. SIGNAGE.

 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet 

above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print 

size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

 

4. INSPECTION.

 The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, 

upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. 

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 

 

1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the 

Board; and 

 

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or struc-

ture used in whole or in part for residential purposes.  

 

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED

. When the manufacturer of Product 

Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions 

provided by the manufacturer for installation of the equipment and the venting system shall include:

 

1. Detailed instructions for the installation of the venting system design or the venting system components; and

 

2. A complete parts list for the venting system design or venting system. 

 

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED

. When the manufacturer of a Prod-

uct Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, 

the following requirements shall be satisfied by the manufacturer:

 

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and 

 

2. The “special venting systems”

 shall be Product Approved by the Board, and the instructions for that system shall include a parts list and 

detailed installation instructions. 

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for 

venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

 

(3) After NFPA-54 section 10.10.4.2

 add a new section 10.10.4.3 as follows:

When more than four gas appliances are to be vented through a common gas vent or common horizontal vent manifold, a plan of the proposed vent installation 

shall be submitted to the Inspector and the serving gas supplier for review and approval.

Extraction from: Massachusetts Rules and Regulations

5.00: Amendments To 2002 Edition Of ANSI Z223.1-NFPA-54

Appendix

Page 19

XG0517 - 070714

Содержание PVHEX510-300

Страница 1: ...rrosive Fork lift trucks Danger overhead crane Explosion risk Oxidising Danger of death Biohazard Laser Radiation Danger of entrapment Hot surface General Warning Blank Gas bottles Watch for falling objects Electricity Danger for cutter Entrapment hazard Battery hazard Rotating parts Low temperature Strong magnetic field Optical radiation Non ionizing radiation Radiation Hazardous to the Environme...

Страница 2: ...tenance manual as it must also be adhered to Power Cord Harnesses EPVH10 10 foot power cord and harness EPVH20 20 foot power cord and harness EPVH30 30 foot power cord and harness EPVH40 40 foot power cord and harness EPVH50 50 foot power cord and harness EPVH60 60 foot power cord and harness EPVH70 70 foot power cord and harness EPVH80 80 foot power cord and harness EPVH90 90 foot power cord and ...

Страница 3: ...1 2 241 6 1 8 156 15 7 8 403 13 330 13 330 5 127 8 203 18 1 4 465 22 1 4 566 17 1 4 439 21 1 4 541 2 51 13 330 4 1 2 114 19 7 8 505 9 1 2 241 6 1 8 156 15 7 8 403 13 330 5 127 8 203 Top View Rear View 18 1 4 465 22 1 4 566 17 1 4 439 21 1 4 541 19 7 8 505 9 1 2 241 6 1 8 156 15 7 8 403 13 330 13 330 Power Head Framing Kit Vent Retainer Electrical Box 14 1 2 368 5 127 PVHEX58 300 PVHEX10 300 10 254...

Страница 4: ...s combustible material construction Installation Step 1 Unscrew Power Head from rough in Box by unscrewing four screws Figure 2a Unscrewing four screws Step 2 Remove Power head from rough in box Figure 2c Unpacking the Power vent Figure 2b PVHEX58 300 PVHEX510 300 Horizontal Power Vent Page 4 XG0517 070714 ...

Страница 5: ...gure 2e Step 4 Remove six screws securing the electrical cover Figure 2f Step 5 Remove electrical cover Figure 2g Step 6 Remove two screws securing the strain relief plate Figure 2h Step 7 Remove Strain Relief Plate PVHEX58 300 PVHEX510 300 Horizontal Power Vent Figure 2d ...

Страница 6: ...nector through the hole in the electrical cover until it clicks into place Figure 2l Step 11 Secure the electrical cover back down with the six screws making sure the control cable curls up safely Figure 2m Step 12 Pass the vent pipe through the rough in box so it extends 6 1 2 inches into the rough in box Step 9 Reinstall the strain relief plate underneath the strain relief nut and screw the stra...

Страница 7: ...le for the power head does not get pinched or caught Figure 2r PVHEX58 300 PVHEX510 300 Horizontal Power Vent Figure 2o Figure 2p Step 14 Plug the power cable from the power vent head into the control cable Step 13 Slip the Vent Support Band over the vent so that it sits flush against the back of the rough in box Tighten the band around the vent so the vent cannot be pushed back through the hole i...

Страница 8: ...utlined Connect the wiring to the fireplace as oulined in the schematic shown in figure 4 Ensure that the proper clearances are maintained for the wiring and conduit When installing the wiring it must never run above the vent run and it must be at least 1 clear of all venting 1 Clearance Wire Figure 3a Conduit and Wiring Wiring Installation Page 8 XG0517 070714 PVHEX58 300 PVHEX510 300 Horizontal ...

Страница 9: ...the combustion air inlet to any other appliance 6in 15 cm for appliances 10 000 Btuh 3 kW 12 in 30 cm for appliances 10 000 Btuh 3 kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW Canadian Installations US Installations 1 2 6in 15 cm for appliances 10 000 Btuh 3 kW 9 in 23 cm for appliances 10 000 Btuh 3 kW and 50 000 Btuh 15 kW 12 in 30 cm for appliances 50 000 Btuh 15 kW K...

Страница 10: ...3 Cut 3 zap straps securing wiring Figure 5d Step 4 Cut Brown Wire From Motor Capacitor Replacement REC1254 Step 5 Cut white fiber wire from power cable black wire from motor and black wire from capacitor Figure 5e 8 fasteners 4 oposite side Outer Cover Page 10 XG0517 070714 4 on opposite side PVHEX58 300 PVHEX510 300 Horizontal Power Vent ...

Страница 11: ...all bell connector connect the brown wire from the motor to the black wire from the capacitor Figure 5g Step 7 Strip all the wires for connection Using old ground screw secure the ground wire and new capacitor to the motor Figure 5f Step 6 Remove ground screw that secures the ground wire and capacitor bracket to the motor Note Keep this screw for later use Dispose of old capacitor PVHEX58 300 PVHE...

Страница 12: ...motor or pinched Figure 5j Figure 5k Figure 5l Step 12 Secure outer cover with supplied 8 screws Step 11 Check operation and rotation Motor should spin counter clockwise Service 8 fasteners 4 oposite side Outer Cover Page 12 XG0517 070714 4 on opposite side PVHEX58 300 PVHEX510 300 Horizontal Power Vent ...

Страница 13: ...om motor Figure 6d Step 5 Cut white fiber wire from power cable black wire from motor and black wire from capacitor Step 2 Remove 8 screws securing the outer cover of the power head Figure 6b Figure 6c 8 fasteners 4 oposite side Outer Cover Step 3 Cut 3 zap straps securing wiring 4 on opposite side PVHEX58 300 PVHEX510 300 Horizontal Power Vent ...

Страница 14: ... to power head Figure 6f Figure 6g Image 40 Step 8 Lift motor assembly out Service Step 9 Put new motor assembly in Figure 6h Figure 6e Step 6 Cut the black fiber wire from power cable Page 14 XG0517 070714 PVHEX58 300 PVHEX510 300 Horizontal Power Vent ...

Страница 15: ...13 Using the supplied large bell connector connect the white fiber wire from the power cable to the black wire from the motor and the black wire from the capacitor Figure 6j Step 11 Attach new capacitor and the ground wire to the ground on the motor Strip all the wire ends Figure 6i Step 10 Secure motor plate with supplied eight screws PVHEX58 300 PVHEX510 300 Horizontal Power Vent ...

Страница 16: ...n counter clockwise Figure 6n Figure 6m Step 14 Using the other supplied small bell connector connect the brown wire from the motor to the black wire from the capacitor Step 15 Using three supplied zap straps neatly secure wiring Make sure no wires can get caught in the motor or pinched Page 16 XG0517 070714 4 on opposite side PVHEX58 300 PVHEX510 300 Horizontal Power Vent ...

Страница 17: ...Page 17 XG0518 070714 Notes PVHEX58 300 PVHEX510 300 Horizontal Power Vent ...

Страница 18: ...Gas Appliance must be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability It is expressly agreed and understood that The Companies sole obligation and purchaser s excl...

Страница 19: ...ve grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless...

Страница 20: ...Ferndale Washington TF 1 800 789 6236 FX 1 866 3000 0927 XG0517 050514 Langley British Columbia TF 1 800 378 3115 FX 1 604 607 6462 PVHEX58 300 PVHEX510 300 Power Vent Termination ...

Отзывы: