H*38DF-CLCR Corner Gas Fireplace
Installation
Section 3-3-1: Venting Layout
Selection of components and details of venting layout should adhere
to the following guidelines:
Vent terminations must
not
be recessed in walls or siding.
For Heat Shield requirements see
page 16
.
Once the proposed venting layout has been determined refer to
either
Figure 12, 12a, 14, or 14a
to ensure the layout is acceptable.
Wall Mounted Terminations: TOP VENT
All dimension lengths for vertical or horizontal runs are measured
from center of the vent pipe.
Venting runs
must
fall within the limits set by the venting graphs,
see
Figure 12 or 12a
.
The Venting Graph
Measure the vertical height from the fireplace hearth to the centre of
the termination and the horizontal run from the fireplace flue collar to
the wall flange of the termination. Plot on the Venting Graph
Figure 12
or 12a
with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 126" and the horizontal
run to the wall flange of the vent termination is 138", this would be
an acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 36" and the horizontal
run to the wall flange of the vent termination is 84",
this would
NOT be an acceptable installation�
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 60" and
the horizontal run to the wall flange of the vent termination is 144",
this would NOT be an acceptable installation�
Figure 12�
H38C* or HL38C*
Top Vent Venting Graph for wall mounted
terminations.
Figure 13a
.
H38C* or HL38C*
Top Vented, wall mounted installation
with one 90° bend. The vent run must comply with Venting Graph for
Top vent, wall mounted terminations,
Figure 12
.
Figure 13
�
HP38C*
Top Vent Venting Graph for wall mounted
terminations.
Figure 12a�
HP38C* Top Vented,
wall mounted installation with one
90° bend.
The vent run must comply with Venting Graph for
Top vent, wall mounted
terminations,
Figure 12a.
46”
A
C
B
.
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
18”
If your installation does not
fall within the venting graph
parameters, please contact a
local Montigo dealer for Power
Venting options.
59”
A
C
B
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
18”
If your installation does not
fall within the venting graph
parameters, please contact a
local Montigo dealer for Power
Venting options.
Heat
Shield
Termination
Hearth
Exterior
Wall
59” Min.
18” Max
Flex of Rigid
section
Heat
Shield
Termination
Hearth
Exterior
Wall
46” Min.
18” Max
Flex section