5
DUCT FITTINGS
This Hood Must Use an
6
″
Round Duct. It Can
Transition to 3-1/4
″
x 10
″
or 3-1/4
″
x 12
″
Duct.
Use this chart to compute
maximum permissible lengths
for duct runs to outdoors.
NOTE:
Do not exceed maximum
permissible equivalent lengths!
Maximum duct length:
100 foot for range hoods.
Flexible ducting:
If flexible metal ducting is used,
all the equivalent feet values in
the table should be doubled.
The flexible metal duct should
be straight and smooth and
extended as much as possible.
DO NOT use flexible plastic
ducting.
NOTE:
Any home ventilation
system, such as a ventilation hood,
may interrupt the proper flow of
combustion air and exhaust
required by fireplaces, gas
furnaces, gas water heaters and
other naturally vented systems.
To minimize the chance of
interruption of such naturally
vented systems, follow the
heating equipment manufacturer’s
guidelines and safety standards
such as those published by NFPA
and ASHRAE.
Installation Preparation
Total Duct Run
*Actual length of straight duct plus duct fitting
equivalent. Equivalent length of duct pieces are
based on actual tests conducted by GE Evaluation
Engineering and reflect requirements for good
venting performance with any ventilation hood.
Total
Equivalent
Quantity Equivalent
Duct Piece
Dimensions
Length*
Used
Length
Round,
1 ft. (per
straight
foot length)
3-1/4
″
x 10
″
1 ft. (per
straight
foot length)
90° elbow
12 ft.
45° elbow
7 ft.
3-1/4
″
x 10
″
14 ft.
3-1/4
″
x 12
″
10 ft.
90° elbow
3-1/4
″
x 10
″
8 ft.
3-1/4
″
x 12
″
6 ft.
45° elbow
3-1/4
″
x 10
″
33 ft.
3-1/4
″
x 12
″
24 ft.
90° flat elbow
6
″
round to
2 ft.
rectangular
Rectangular to 8
″
2 ft.
round
3-1/4
″
x 10
″
4 ft.
3-1/4
″
x 12
″
4 ft.
6
″
round to rectangular
transition 90° elbow
3-1/4
″
x 10
″
4 ft.
3-1/4
″
x 12
″
4 ft.
Rectangular to 6
″
round
transition 90° elbow
Round wall cap
24 ft.
with damper
3-1/4
″
x 10
″
24 ft.
3-1/4
″
x 12
″
18 ft.
Rectangular wall cap
with damper
Round roof cap
33 ft.
Содержание ZV850
Страница 42: ...Notes 42 ...
Страница 63: ...63 Notas ...