SYSTEM

SPECIFICATIONS

Rain Sensor Input (Required) - (7.1)

Smoke Vent Input (Optional) - (7.4)

External Temperature Input (Required) - (7.5)

Heating Interlock Input (Optional) - (7.2)

Fire Alarm Input (Optional) - (7.3)

The Rain Sensor Input requires a normally open volt-free contact wired 

between the “COM” and “NO” “Rain” terminals of J28 (upper level).

When the contact is closed the system will close the active louvres and 

windows, but leave internal dampers on X-AIR systems and wall louvres in 

their position based on the temperature/CO

2

 to allow continued ventilation 

in the space. If the ventilation system is a WINDCATCHER Classic or SOLA-

BOOST system, then the dampers will fully close on rain.

The Smoke Vent input requires a normally open volt-free contact wired between 

the “COM” and “NO” terminals of the J33 “Smoke” terminals (upper level).

When the contact is closed all dampers, louvres, wall louvres and windows 

will open to allow the escape of smoke.

The external temperature input requires a weather-proof temperature sensor 

with a 0-10V output that maps to -10°C to +40°C, powered by 24V DC, connected 

to J34. One such suitable sensor is the Titan Products part ref: TPVOS.

This should be located out of direct sunlight and away from any heat sources 

that could affect the air temperature measurement (such as plant exhaust). 

It is recommended that it is installed on a north facing façade of the building. 

If it is located on any other façade it will require shielding by building soffits 

or by a type of solar shielding.

It is used to adjust the seasonal strategy and protect ventilation systems 

against snow/frost.

The Heating Interlock input requires a normally open volt-free contact wired 

between the “COM” and “NO” terminals of the J28 “Heat” terminals (lower level).

When the contact is closed the system will limit all dampers, wall louvres 

and windows to a maximum of 10% open as default. This may be altered 

to anything in the range of 5% to 20% in 5% increments via the iNVent  2 

configurator software.

The Fire Alarm input requires a normally open volt-free contact wired between 

the “COM” and “NO” terminals of the J33 “Fire” terminals (lower level).
When the contact is closed all dampers, louvres, wall louvres and windows 

will fully close.

Fault Output (Optional) - (7.6)

The fault output is a volt-free contact which when open indicates a fault has 

occurred. Max rated voltage: 24V DC.

Master Controls

Содержание INVENT 2

Страница 1: ...INVENT 2 Operational Manual...

Страница 2: ...inal J3 Master Controls BMS I O General Features Damper Louvre Connection USB Fault Output Optional Night time cooling LEDs Smoke Vent Input Optional Control Strategy RS485 Competition Key Switch Inpu...

Страница 3: ...SENSOR 2 RS485 DMP LVR DAMPER LOUVRE 0V 24V DMP LVR WALL ACTUATOR 0V 24V Zone 0V 24V 0V 24V SENSOR 1 SENSOR 2 RS485 DMP LVR DAMPER LOUVRE 0V 24V DMP DMP LVR WALL ACTUATOR 0V 24V Zone 0V 24V 0V 24V SE...

Страница 4: ...Jack J2 is used to connect power to the panel from the external power supply and is centre positive The Power Terminal J3 is for future use when the power supply will be integrated within a new desig...

Страница 5: ...panel in order to see the status and configuration of the panel via the iNVent Configurator software This enables the iNVent 2 panel to be reconfigured to operate in more advanced and custom configura...

Страница 6: ...t uses for various functions such as time stamping data logs calculating the current season and providing out of hours closure of automated windows It uses a CR2032 battery in order to maintain the ti...

Страница 7: ...y24VDC connected to J34 One such suitable sensor is the Titan Products part ref TPVOS This should be located out of direct sunlight and away from any heat sources that could affect the air temperature...

Страница 8: ...se contact is closed all dampers louvres wall louvres and windows will close If both the Open and Close inputs are activated at the same time by an external system then the Close setting will take pri...

Страница 9: ...contact rated at 24V 1A maximum The iNVent 2 panel has four solid state relays Upper terminals of J15 J18 J22 J26 for controlling a cooling system per zone This is not currently supported but will be...

Страница 10: ...e set to close when the internal temperature is at least 25 C and the external temperature is at least 5 C above the internal temperature This feature is designed to prevent a space from heating up du...

Страница 11: ...e level drops below 1300 ppm Note If the dampers are already at 100 they do not open any further Input Priority 1 Fire Key Switch Highest 2 Fire Alarm 3 Competition Switch 4 Override Open 5 Override C...

Страница 12: ...Halifax House High Wycombe Buckinghamshire HP12 3SE 44 0 1494 897700 www monodraught com info monodraught com Follow us on...

Отзывы: