Setting
:
Disable/ Enable
Description
:
Disconnect starter motor by Genset voltage
13.
Esc. ACV Setpoint
Setting
:
44~100/48~108/76~172/84~188/88~198/152~342(V)
Default
:
72/72/124/124/132/228
Description
:
Disconnect starter motor when AC Voltage reaches disconnecting setting
11.
.......................................................................................................................
AC Ampere
1.
Current Ratio:
Range
:
1~31
5:5
10:5
15:5
20:5
30:5
40:5
50:5
60:5
75:5
80:5
100:5
150:5
200:5
250:5
300:5
400:5
500:5
600:5
700:5
800:5
900:5
1000:5
1200:5
1500:5
1600:5
2000:5
2500:5
3000:5
3200:5
4000:5
5000:5
Default
:
500:5
Description
:
Setup the current transformer ratio
2.
Over load Detect
:
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates overload protection
3.
Over load Protection
:
Setting
:
1.Warning 2.Alarm 3.Trip 4.Stop
Default
:
3
Description
:
Setup the action when overload occurs
4.
O. L. Set Point
:
Range
:
1~31
0.1~20.0(A)
0.1~30.0(A)
0.1~40.0(A)
0.1~50.0(A)
0.1~60.0(A)
0.1~75.0(A)
0.1~80.0(A)
0.2~100.0(A)
0.3~150.0(A)
0.4~200.0(A)
5.0~250.0(A)
6.0~300.0(A)
8.0~400.0(A)
10.0~500.0(A)
12.0~600.0(A)
14~700.0(A)
15.0~750.0(A)
16.0~800.0(A)
18.0~900.0(A)
20.0~1000.0(A)
24.0~1200.0(A)
30.0~1500.0(A)
32.0~1600.0(A)
40.0~2000.0(A)
50.0~2500.0(A)
60.0~3000.0(A)
64.0~3200.0(A)
80.0~4000.0(A)
100.0~5000.0(A)
120~6000(A)
Description
:
When current is above setting, the controller outputs trip signal, setup range is
related to the CT ratio.