[1]
GTR-680
User Manual
T E L
:
0 4 - 2 2 3 8 - 0 6 9 8
F A X
0 4 - 2 2 3 8 - 0 8 9 1
W e b S i t e
h t t p : / / w w w . m o n i c o n . c o m . t w
E - m a i l
s a l e s @ m o n i c o n . c o m . t w
Страница 1: ...1 GTR 680 User Manual T E L 0 4 2 2 3 8 0 6 9 8 F A X 0 4 2 2 3 8 0 8 9 1 Web Site http www monicon com t w E m a i l s a l e s m o n i c o n c o m t w...
Страница 2: ...ER setting this keypad switches to previous parameter In CODE entry mode this keypad increases the value Under PARAMETER setting this keypad increases the setting value In CODE entry mode this keypad...
Страница 3: ...example if the conditions and parameter settings are given as follows 1 stop duration is 10 seconds crank attempt is 3 times The engine cranks for 10 seconds and then rest for 10 seconds after 3 attem...
Страница 4: ...O_STOP 8 Preheat output O_PREHEAT 9 Alarm output O_ALARM 10 AUX output 1 O_OUT1 N O 11 12 AUX output 0 O_OUT0 N O 13 18 AUX input 4 I N 4 19 AUX input 3 I N 3 20 AUX input 2 I N 2 21 AUX input 1 I N 1...
Страница 5: ...I 1 K 50 CT 2 input I 2 K 51 CT 3 input I 3 K 52 CT Common input Com 53 Sensor V output SENSOR V 54 Sensor Common GND input COMMON 55 Oil pressure sensor input OIL PRESS 56 Oil temperature sensor inp...
Страница 6: ...6 Dimensions...
Страница 7: ...tor current D Generator frequency E Engine F RPM G Battery H Exercisor I Senesors J Event logs K Error logs Remote Network 1 Start stop and reset 2 Parameter settings 3 Genset monitoring 4 Error recor...
Страница 8: ...s DC input 8 36 VDC Power consumption Max 24 W Voltage measurement 0 500VAC 0 2 Current measurement 0 5 A CT ratio 0 2 Frequency measurement 0 80 Hz 0 02 Charger or pickup voltage 5 V 70 V peak to pea...
Страница 9: ...ts Setting 1 10 Default 3 Description Set total number of crank attempts 5 Escape up limit Setting 15 30 Hz Default 20 Description When frequency reaches setting starter motor disconnects from engine...
Страница 10: ...alarm 5 Trip then shut Setting Disable Enable Default Enable Description When error occurred timer starts before shutdown the engine 6 Trip duration Setting 30 900 Seconds Default 30 Description When...
Страница 11: ...the hour meter in hours 4 Acc Hour 100 Setting 0 99 100 Default 0 Description Set the hour meter in 100 hours scale 4 Sensors Switches 1 H W T Detection Setting Disable Enable Default Enable Descript...
Страница 12: ...ivates Input 0 function 3 Input 0 Name Setting 1 Emergency Stop 2 User Define 3 Low battery Voltage 4 System fault 5 High fuel level 6 System trip 7 Insulation Fail 8 Cooling failure 9 Malfunction war...
Страница 13: ...ally close or normally open 11 In1 delay Setting 0 2 5 0 Seconds Default 2 0 Description When input1 activates timer starts before activating protection 12 Input 2 Detect Setting Disable Enable Defaul...
Страница 14: ...ip 4 Stop Default 4 Description Setup the action when input 3 activates 20 In3 Switch Type Setting NC NO Default Normal Open Description Setup Input 3 to normally close or normally open 21 Input3 Dela...
Страница 15: ...ature switch 16 High AC voltage 17 Low AC voltage 18 Overload 19 Short circuit 20 Low battery voltage 21 High battery voltage 22 Input 0 activate 23 Input1activate 24 Input 2 activate 25 Input 3 activ...
Страница 16: ...lvo Description Setup brand and model of the ECU 3 RPM Command Setting Disable Enable Default Enable 4 Idle Speed Setting 900 RPM Description Set idle speed 5 Rated Speed Setting 1800 RPM Description...
Страница 17: ...Alarm 3 Trip 4 shutdown Default 2 Description Setup the action when low frequency occurs 7 L F Set Point Setting 40 50 48 60 Hz Default 45 55Hz Description When AC frequency is lower than setting cont...
Страница 18: ...volt warning 5 Weak Batt Detect Setting Disable Enable Default Enable Description Activates weak battery protection 6 W Batt Set Point Setting 4 8 8 4 9 6 16 8 V Default 8 4 9 6 Description When batt...
Страница 19: ...ACV Protection Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 3 Description Setup the action when low voltage occurs 8 Low ACV set point Setting 78 110 84 120 134 190 146 208 154 220 266 380 V Defau...
Страница 20: ...ratio 2 Over load Detect Setting Disable Enable Default Enable Description Activates overload protection 3 Over load Protection Setting 1 Warning 2 Alarm 3 Trip 4 Stop Default 3 Description Setup the...
Страница 21: ...0 A 60 300 A 80 400 A 100 500 A 120 600 A 150 750 A 160 800 A 180 900 A 200 1000 A 240 1200 A 300 1500 A 320 1600 A 400 2000 A 500 2500 A 600 3000 A 640 3200 A 800 4000 A 1000 5000 A Description When...
Страница 22: ...P M Input pulse revolution numerator revolution denominator 1500 4437 45 133 C If the teeth count of engine flywheel is 118 Assume the rated rpm of Gen set is 1500 rpm Then the 1500 rpm 50hz 30 rpms p...
Страница 23: ...95 Description When fuel level is above setting controller displays warning message 4 LOP value alarm Setting Disable Enable Default Enable Description Activates low oil pressure warning 5 LOP set poi...
Страница 24: ...nd Setting VDO 120 KD 120 WGI 900131 KP130 YB 054 KL 3967250 MHI 98 SUSUKI PRO SCD Betung User Define Description Setup water temperature sensor brand 12 FL sensor Brand Setting SUSUKI Betung User Def...
Страница 25: ...ise 5 Hour set point Setting 0 23 hour Default 12 Description Setup the starting hour of the exercise 6 Minute set point Setting 0 59 minute Default 0 Description Setup the starting minute of the exer...
Страница 26: ...0 KW 0 1 30 0 KW 0 1 40 0 KW 0 1 50 0 KW 0 1 60 0 KW 0 1 75 0 KW 0 1 80 0 KW 0 2 100 0 KW 0 3 150 0 KW 0 4 200 0 KW 5 0 250 0 KW 6 0 300 0 KW 8 0 400 0 KW 10 0 500 0 KW 12 0 600 0 KW 14 700 0 KW 15 0...
Страница 27: ...alarm 5 Contrast Adjust Setting 1 19 Description Adjust contrast of LCD screen 18 Utility Charge 1 Cgr In Volt Low Setting 100 198 Default 100 Description Setup utility 2 Cgr In Volt High Setting 110...
Страница 28: ...cription a Total count Display total number of crank attempts b Fail count Display total number of crank fail c Succeed count Display total number of successful cranks d Reset counters Clears crank in...
Страница 29: ......