[14]
16.
Input2 Delay
Setting
:
0.2~5.0(Seconds)
Default
:
0.4
Description
:
When input2 activates, timer starts before activating protection
17.
Input3 Detect
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates input3 function
18.
Input 3 Name
Setting
:
1.Low fuel level 2.User Define 3.Low battery Voltage 4. System fault 5.High fuel
level 6. System trip 7.Insulation Fail 8.Cooling Fan failure 9.Malfunction warning
10.Charge fail 11.Over load 12.Low water temperature 13.Preheat
Default
:
6.
Description
:
Define function for AUX 3
19.
In3 Protection
Setting
:
1.Warning 2.Alarm 3.Trip 4.Stop
Default
:
4.
Description
:
Setup the action when input 3 activates
20.
In3 Switch Type
Setting
:
NC/NO
Default
:
Normal Open
Description
:
Setup Input 3 to normally close or normally open
21.
Input3 Delay
Setting
:
0.2~5.0(Seconds)
Default
:
2
Description
:
When input 3 activates, timer starts before activating protection
22.
Input4 Detect
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates input4 function
23.
Input4 Name
Setting
:
1.Low fuel level 2.User Define 3.Low battery Voltage 4. System fault 5.High fuel
level 6. System trip 7.Insulation Fail 8.Cooling Fan failure 9.Malfunction warning
10.Charge fail 11.Over load 12.Low water temperature 13.Preheat
Default
:
5.
Description
:
Define function for input4
24.
In4 Protection
Содержание GTR-660
Страница 6: ...6 2 Dimension...