Monicon GTR-620 Скачать руководство пользователя страница 19

[19] 

 

Default

2.5 

Description

When low voltage occurred, timer starts before activating protection 

 

10.

 

Mini. ACV Detect 

Setting

Disable/ Enable

 

Default

Enable 

Description

Activates extreme low voltage protection. 

11.

 

Mini. ACV setpoint 

Setting

34~88/36~96/58~152/62~166/66~176/114~304(V) 

Default

56/60/96/110/110/198 

Description

When  sudden  drop  of  AC  voltage  blows  setting,  low  voltage  protection  is 

disabled. 

12.

 

ACV Escape Motor   

Setting

Disable/ Enable

 

Description

Disconnect starter motor by Genset voltage 

13.

 

Esc. ACV Setpoint 

Setting

44~100/48~108/76~172/84~188/88~198/152~342(V) 

Default

72/72/124/124/132/228 

Description

Disconnect starter motor when AC Voltage reaches disconnecting setting 

10.

 

  AC Ampere 

1.

 

Current Ratio: 
Range

1~31 

5:5 

10:5 

15:5 

20:5 

30:5 

40:5 

50:5 

60:5 

75:5 

80:5 

100:5 

150:5 

200:5 

250:5 

300:5 

400:5 

500:5 

600:5 

700:5 

800:5 

900:5 

1000:5 

1200:5 

1500:5 

1600:5 

2000:5 

2500:5 

3000:5 

3200:5 

4000:5 

5000:5 

Default

500:5 

Description

Setup the current transformer ratio

 

2.

 

Over load Detect

 

Setting

Disable/ Enable

 

Default

Enable 

Description

Activates overload protection 

 

3.

 

Over load Protection

 

Содержание GTR-620

Страница 1: ...1 GTR 620 User manual T E L 0 4 2 2 3 8 0 6 9 8 F A X 0 4 2 2 3 8 0 8 9 1 Web Site http www monicon com t w E m a i l s a l e s m o n i c o n c o m t w...

Страница 2: ...onnector 26 detects signal from ATS switch C Setup Keypad 1 In password entry mode this keypad switches to next digit 2 Under PARAMETER setting this keypad switches to the next parameter 1 In password...

Страница 3: ...000 1 In CODE entry mode this keypad decreases the value 2 Under the PARAMETER setting mode this keypad decreases the setting Enter or exit the parameter setting mode Confirm and save the settings The...

Страница 4: ...gine again For example if the conditions and parameter settings are given as follows 1 stop duration is 10 seconds crank attempt is 3 times The engine cranks for 10 seconds and then rest for 10 second...

Страница 5: ...CT 2 input I2 51 CT 3 input I3 52 CT Common input Com 53 Sensor V output Sensor V 54 Sensor Common GND input Common 55 Oil pressure sensor input Oil Press 56 Oil temperature sensor input Oil Temp 57...

Страница 6: ...6 2 Dimension...

Страница 7: ...W KWH 6 P F 7 RPM 8 Engine parameter settings 9 Battery voltage 10 Exerciser 11 Water temperature 12 Oil pressure 13 1024 Event log 14 64 Error record B Remote access 1 Start stop and reset 2 Paramete...

Страница 8: ...ion DC input 8 36 VDC Power consumption Max 24 W Voltage measurement 0 500VAC 0 2 Current measurement 0 5 A CT ratio 0 2 Frequency measurement 0 80 Hz 0 02 Charger or pickup voltage 5 V 70 V peak to p...

Страница 9: ...fault 10 Description Set the duration of each crank 4 Crank attempts Setting 1 10 Default 3 Description Set total number of crank attempts 5 Escape up limit Setting 15 30 Hz Default 20 Description Whe...

Страница 10: ...iggering engine shutdown failed alarm 5 Trip then shut Setting Disable Enable Default Enable Description When error occurred timer starts before shutdown the engine 6 Trip duration Setting 30 900 Seco...

Страница 11: ...Description Set the hour meter in hours 4 Acc Hour 100 Setting 0 99 100 Default 0 Description Set the hour meter in 100 hours scale 4 Sensors Switches 1 H W T Detection Setting Disable Enable Default...

Страница 12: ...tion Activates Input 0 function 3 Input 0 Name Setting 1 Emergency Stop 2 User Define 3 Low battery Voltage 4 System fault 5 High fuel level 6 System trip 7 Insulation Fail 8 Cooling failure 9 Malfunc...

Страница 13: ...ally close or normally open 11 In1 delay Setting 0 2 5 0 Seconds Default 2 0 Description When input1 activates timer starts before activating protection 12 Input 2 Detect Setting Disable Enable Defaul...

Страница 14: ...ng 1 Warning 2 Alarm 3 Trip 4 Stop Default 4 Description Setup the action when input 3 activates 20 In3 Switch Type Setting NC NO Default Normal Open Description Setup Input 3 to normally close or nor...

Страница 15: ...ressure switch 15 High water temperature switch 16 High AC voltage 17 Low AC voltage 18 Overload 19 Short circuit 20 Low battery voltage 21 High battery voltage 22 Input 0 activate 23 Input1activate 2...

Страница 16: ...n the engine and display high frequency error if high frequency protection is enable 4 Hi Freq Delay Setting 1 9 Seconds Default 1 Description When high frequency occurres timer starts before activati...

Страница 17: ...2 Batt Fault Alarm Setting Disable Enable Default Enable Description Activates battery error protections 3 L batt Set Point Setting 8 4 12 16 8 24 V Default 10 8 20 Description When battery voltage is...

Страница 18: ...120 144 190 228 208 250 220 264 380 456 V Default 122 122 210 242 242 418 Description When AC voltage is above the setting the controller outputs trip signal 5 Hi ACV Delay Setting 0 5 5 Seconds Defa...

Страница 19: ...ription Disconnect starter motor by Genset voltage 13 Esc ACV Setpoint Setting 44 100 48 108 76 172 84 188 88 198 152 342 V Default 72 72 124 124 132 228 Description Disconnect starter motor when AC V...

Страница 20: ...tio 5 Overload Delay Setting 10 300 Second Default 40 Description When overload occurres timer starts before activating protection 6 Short Detect Setting Disable Enable Default Enable Description Acti...

Страница 21: ...tion 1800 460 3 913 The R P M calculation formula is as below R P M Input pulse RPM numerator RPM denominator 1800 460 90 23 B If the engine revolution is 1500 and total count of fly wheel teeth in on...

Страница 22: ...peed is enabled 8 Over speed delay Setting 1 10 Second Default 1 Description When over speed occurres timer starts before activating protection 12 Sensors 1 LFL Value Alarm Setting Disable Enable Defa...

Страница 23: ...fault 45 Description Disconnect starter motor when oil pressure reaches setting 10 OP Sensor Brand Setting VDO 10 Bar KD 10 Bar YG 962 N 010 B2 KL 3967251 MHI 10 Bar DATCON 10 Bar SUSUKI 10 Bar VDO 5...

Страница 24: ...p monthly exercise by date or week 3 Date set point Setting 1 31 date Default 28 Description Setup date of monthly exercise 4 Week set point Setting Sunday Monday Tuesday Wednesday Thursday Friday sat...

Страница 25: ...ration between each service 15 OverLoad Protect 1 Over Load Detect Setting Disable Enable Description Activates over load detection 2 Overload protect Setting 1 Warning 2 Alarm 3 Trip 4 Stop Descripti...

Страница 26: ...ess Setting 0 255 00H FFH Default FFH Description Multiple Genset networking via RS 485 requires individual address for each controller 4 Not in AUTO Mode Setting Disable Enable Description When GTR 2...

Страница 27: ...iption Reset user password 3 Maintain Code Description Reset engineer password 4 Crank information Description a Total count Display total number of crank attempts b Fail count Display total number of...

Отзывы: