[19]
Default
:
2.5
Description
:
When low voltage occurred, timer starts before activating protection
10.
Mini. ACV Detect
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates extreme low voltage protection.
11.
Mini. ACV setpoint
Setting
:
34~88/36~96/58~152/62~166/66~176/114~304(V)
Default
:
56/60/96/110/110/198
Description
:
When sudden drop of AC voltage blows setting, low voltage protection is
disabled.
12.
ACV Escape Motor
Setting
:
Disable/ Enable
Description
:
Disconnect starter motor by Genset voltage
13.
Esc. ACV Setpoint
Setting
:
44~100/48~108/76~172/84~188/88~198/152~342(V)
Default
:
72/72/124/124/132/228
Description
:
Disconnect starter motor when AC Voltage reaches disconnecting setting
10.
AC Ampere
1.
Current Ratio:
Range
:
1~31
5:5
10:5
15:5
20:5
30:5
40:5
50:5
60:5
75:5
80:5
100:5
150:5
200:5
250:5
300:5
400:5
500:5
600:5
700:5
800:5
900:5
1000:5
1200:5
1500:5
1600:5
2000:5
2500:5
3000:5
3200:5
4000:5
5000:5
Default
:
500:5
Description
:
Setup the current transformer ratio
2.
Over load Detect
:
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates overload protection
3.
Over load Protection
: